6.6.5.1 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack

The following tables list the threshold values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack:

  • Table 6-37 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, Low-voltage PDU

  • Table 6-38 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, Low-voltage PDU

  • Table 6-39 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, High-voltage PDU

  • Table 6-40 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, High-voltage PDU

Table 6-37 lists the threshold values for Oracle Exadata Database Machine Full Rack using a single-phase, low-voltage PDU.

Table 6-37 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

22

24

A

Module 1, phase 2

0

22

24

A

Module 1, phase 3

0

21

24

B

Module 1, phase 1

0

21

24

B

Module 1, phase 2

0

22

24

B

Module 1, phase 3

0

22

24

Table 6-38 lists the threshold values for Oracle Exadata Database Machine Full Rack using a three-phase, low-voltage PDU.

Table 6-38 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

36

45

A and B

Module 1, phase 2

0

39

44

A and B

Module 1, phase 3

0

38

45

Table 6-39 lists the threshold values for Oracle Exadata Database Machine Full Rack using a single-phase, high-voltage PDU.

Table 6-39 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

20

21

A

Module 1, phase 2

0

20

21

A

Module 1, phase 3

0

19

21

B

Module 1, phase 1

0

19

21

B

Module 1, phase 2

0

20

21

B

Module 1, phase 3

0

20

21

Table 6-40 lists the threshold values for Oracle Exadata Database Machine Full Rack using a three-phase, high-voltage PDU.

Table 6-40 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

20

21

A and B

Module 1, phase 2

0

21

21

A and B

Module 1, phase 3

0

18

21