6.6.5.2 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack

The following tables list the threshold values for Oracle Exadata Database Machine Half Rack:

  • Table 6-41 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, Low-voltage PDU

  • Table 6-42 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, Low-voltage PDU

  • Table 6-43 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, High-voltage PDU

  • Table 6-44 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, High-voltage PDU

Table 6-41 lists the threshold values for Oracle Exadata Database Machine Half Rack using a single-phase, low-voltage PDU.

Table 6-41 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

21

24

A

Module 1, phase 2

0

13

17

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

13

17

B

Module 1, phase 3

0

21

24

Table 6-42 lists the threshold values for Oracle Exadata Database Machine Half Rack using a three-phase, low-voltage PDU.

Table 6-42 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

19

24

A and B

Module 1, phase 2

0

20

25

A and B

Module 1, phase 3

0

19

24

Table 6-43 lists the threshold values for Oracle Exadata Database Machine Half Rack using a single-phase, high-voltage PDU.

Table 6-43 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

19

21

A

Module 1, phase 2

0

12

15

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

12

15

B

Module 1, phase 3

0

19

21

Table 6-44 lists the threshold values for Oracle Exadata Database Machine Half Rack using a three-phase, high-voltage PDU.

Table 6-44 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

11

14

A and B

Module 1, phase 2

0

11

14

A and B

Module 1, phase 3

0

10

13