6.6.5.3 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack

The following tables list the threshold values for Oracle Exadata Database Machine Quarter Rack:

  • Table 6-45

    Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Single-phase, Low-voltage PDU
  • Table 6-46

    Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Three-phase, Low-voltage PDU
  • Table 6-47

    Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Single-phase, High-voltage PDU
  • Table 6-48

    Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Three-phase, High-voltage PDU

Table 6-45 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, low-voltage PDU.

Table 6-45 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Single-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

12

15

A

Module 1, phase 2

0

6

8

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

6

8

B

Module 1, phase 3

0

12

15

Table 6-46 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, low-voltage PDU.

Table 6-46 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Three-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

13

17

A and B

Module 1, phase 2

0

12

15

A and B

Module 1, phase 3

0

5

7

Table 6-47 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, high-voltage PDU.

Table 6-47 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Single-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

11

14

A

Module 1, phase 2

0

5

7

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

5

7

B

Module 1, phase 3

0

11

14

Table 6-48 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, high-voltage PDU.

Table 6-48 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers) Quarter Rack with Three-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

11

14

A and B

Module 1, phase 2

0

2

3

A and B

Module 1, phase 3

0

3

4