6.6.4.2 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine Half Rack:
-
Table 6-29 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, Low-voltage PDU
-
Table 6-30 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, Low-voltage PDU
-
Table 6-31 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, High-voltage PDU
-
Table 6-32 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, High-voltage PDU
Table 6-29 lists the threshold values for Oracle Exadata Database Machine Half Rack using a single-phase, low-voltage PDU.
Table 6-29 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
18 |
23 |
A |
Module 1, phase 2 |
0 |
13 |
17 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
13 |
17 |
B |
Module 1, phase 3 |
0 |
18 |
23 |
Table 6-30 lists the threshold values for Oracle Exadata Database Machine Half Rack using a three-phase, low-voltage PDU.
Table 6-30 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
18 |
23 |
A and B |
Module 1, phase 2 |
0 |
17 |
22 |
A and B |
Module 1, phase 3 |
0 |
18 |
23 |
Table 6-31 lists the threshold values for Oracle Exadata Database Machine Half Rack using a single-phase, high-voltage PDU.
Table 6-31 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
16 |
20 |
A |
Module 1, phase 2 |
0 |
12 |
15 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
12 |
15 |
B |
Module 1, phase 3 |
0 |
16 |
20 |
Table 6-32 lists the threshold values for Oracle Exadata Database Machine Half Rack using a three-phase, high-voltage PDU.
Table 6-32 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
9 |
12 |
A and B |
Module 1, phase 2 |
0 |
9 |
12 |
A and B |
Module 1, phase 3 |
0 |
10 |
13 |