6.6.4.3 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack
The following tables list the threshold values for Oracle Exadata Database Machine Quarter Rack:
-
Table 6-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage PDU
-
Table 6-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage PDU
-
Table 6-35 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, High-voltage PDU
-
Table 6-36 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, High-voltage PDU
Table 6-33 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, low-voltage PDU.
Table 6-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
10 |
13 |
A |
Module 1, phase 2 |
0 |
6 |
8 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
6 |
8 |
B |
Module 1, phase 3 |
0 |
10 |
13 |
Table 6-34 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, low-voltage PDU.
Table 6-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
12 |
15 |
A and B |
Module 1, phase 2 |
0 |
11 |
14 |
A and B |
Module 1, phase 3 |
0 |
5 |
7 |
Table 6-35 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, high-voltage PDU.
Table 6-35 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
9 |
12 |
A |
Module 1, phase 2 |
0 |
5 |
7 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
5 |
7 |
B |
Module 1, phase 3 |
0 |
9 |
12 |
Table 6-36 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, high-voltage PDU.
Table 6-36 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
9 |
12 |
A and B |
Module 1, phase 2 |
0 |
3 |
4 |
A and B |
Module 1, phase 3 |
0 |
4 |
5 |