6.6.4.3 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack

The following tables list the threshold values for Oracle Exadata Database Machine Quarter Rack:

  • Table 6-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage PDU

  • Table 6-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage PDU

  • Table 6-35 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, High-voltage PDU

  • Table 6-36 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, High-voltage PDU

Table 6-33 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, low-voltage PDU.

Table 6-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

10

13

A

Module 1, phase 2

0

6

8

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

6

8

B

Module 1, phase 3

0

10

13

Table 6-34 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, low-voltage PDU.

Table 6-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

12

15

A and B

Module 1, phase 2

0

11

14

A and B

Module 1, phase 3

0

5

7

Table 6-35 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a single-phase, high-voltage PDU.

Table 6-35 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

9

12

A

Module 1, phase 2

0

5

7

A

Module 1, phase 3

0

0

0

B

Module 1, phase 1

0

0

0

B

Module 1, phase 2

0

5

7

B

Module 1, phase 3

0

9

12

Table 6-36 lists the threshold values for Oracle Exadata Database Machine Quarter Rack using a three-phase, high-voltage PDU.

Table 6-36 Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

9

12

A and B

Module 1, phase 2

0

3

4

A and B

Module 1, phase 3

0

4

5