6.6.8 PDU Thresholds for Oracle Exadata Database Machine X2-8 Full Rack
This section contains the PDU thresholds for Oracle Exadata Database Machine X2-8 Full Rack.
-
Table 6-53 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
-
Table 6-54 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
-
Table 6-55 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
-
Table 6-56 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
Table 6-53 lists the threshold values for Oracle Exadata Database Machine X2-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.
Table 6-53 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
36 |
37 |
A |
Module 1, phase 2 |
0 |
35 |
37 |
A |
Module 1, phase 3 |
0 |
35 |
37 |
B |
Module 1, phase 1 |
0 |
35 |
37 |
B |
Module 1, phase 2 |
0 |
35 |
37 |
B |
Module 1, phase 3 |
0 |
36 |
37 |
Table 6-54 lists the threshold values for Oracle Exadata Database Machine X2-8 Full Rack using a three-phase, low-voltage 24 kVA PDU.
Table 6-54 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
32 |
40 |
A and B |
Module 1, phase 2 |
0 |
34 |
43 |
A and B |
Module 1, phase 3 |
0 |
33 |
42 |
Table 6-55 lists the threshold values for Oracle Exadata Database Machine X2-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.
Table 6-55 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
26 |
32 |
A and B |
Module 1, phase 2 |
0 |
25 |
32 |
A and B |
Module 1, phase 3 |
0 |
26 |
32 |
Table 6-56 lists the threshold values for Oracle Exadata Database Machine X2-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.
Table 6-56 Threshold Values for Oracle Exadata Database Machine X2-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
18 |
21 |
A and B |
Module 1, phase 2 |
0 |
18 |
21 |
A and B |
Module 1, phase 3 |
0 |
17 |
21 |