6.6.7 PDU Thresholds for Oracle Exadata Database Machine X3-8 Full Rack
This section contains the PDU thresholds for Oracle Exadata Database Machine X3-8 Full Rack.
-
Table 6-49 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
-
Table 6-50 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
-
Table 6-51 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
-
Table 6-52 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
Table 6-49 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.
Table 6-49 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
25 |
31 |
A |
Module 1, phase 2 |
0 |
26 |
33 |
A |
Module 1, phase 3 |
0 |
24 |
30 |
B |
Module 1, phase 1 |
0 |
24 |
30 |
B |
Module 1, phase 2 |
0 |
26 |
33 |
B |
Module 1, phase 3 |
0 |
25 |
31 |
Table 6-50 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a three-phase, low-voltage 24 kVA PDU.
Table 6-50 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
21 |
27 |
A |
Module 1, phase 2 |
0 |
23 |
30 |
A |
Module 1, phase 3 |
0 |
22 |
28 |
A |
Module 2, phase 1 |
0 |
20 |
25 |
A |
Module 2, phase 2 |
0 |
21 |
27 |
A |
Module 2, phase 3 |
0 |
23 |
29 |
B |
Module 1, phase 1 |
0 |
20 |
25 |
B |
Module 1, phase 2 |
0 |
21 |
27 |
B |
Module 1, phase 3 |
0 |
23 |
29 |
B |
Module 2, phase 1 |
0 |
21 |
27 |
B |
Module 2, phase 2 |
0 |
23 |
30 |
B |
Module 2, phase 3 |
0 |
22 |
28 |
Table 6-51 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.
Table 6-51 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
22 |
28 |
A and B |
Module 1, phase 2 |
0 |
24 |
30 |
A and B |
Module 1, phase 3 |
0 |
22 |
28 |
Table 6-52 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.
Table 6-52 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
12 |
16 |
A |
Module 1, phase 2 |
0 |
13 |
17 |
A |
Module 1, phase 3 |
0 |
10 |
13 |
A |
Module 2, phase 1 |
0 |
10 |
13 |
A |
Module 2, phase 2 |
0 |
13 |
17 |
A |
Module 2, phase 3 |
0 |
11 |
15 |
B |
Module 1, phase 1 |
0 |
10 |
13 |
B |
Module 1, phase 2 |
0 |
13 |
17 |
B |
Module 1, phase 3 |
0 |
11 |
15 |
B |
Module 2, phase 1 |
0 |
12 |
16 |
B |
Module 2, phase 2 |
0 |
13 |
17 |
B |
Module 2, phase 3 |
0 |
10 |
13 |