6.6.7 PDU Thresholds for Oracle Exadata Database Machine X3-8 Full Rack

This section contains the PDU thresholds for Oracle Exadata Database Machine X3-8 Full Rack.

  • Table 6-49 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU

  • Table 6-50 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU

  • Table 6-51 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, High-voltage 22 kVA PDU

  • Table 6-52 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, High-voltage 24 kVA PDU

Table 6-49 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.

Table 6-49 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

25

31

A

Module 1, phase 2

0

26

33

A

Module 1, phase 3

0

24

30

B

Module 1, phase 1

0

24

30

B

Module 1, phase 2

0

26

33

B

Module 1, phase 3

0

25

31

Table 6-50 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a three-phase, low-voltage 24 kVA PDU.

Table 6-50 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

21

27

A

Module 1, phase 2

0

23

30

A

Module 1, phase 3

0

22

28

A

Module 2, phase 1

0

20

25

A

Module 2, phase 2

0

21

27

A

Module 2, phase 3

0

23

29

B

Module 1, phase 1

0

20

25

B

Module 1, phase 2

0

21

27

B

Module 1, phase 3

0

23

29

B

Module 2, phase 1

0

21

27

B

Module 2, phase 2

0

23

30

B

Module 2, phase 3

0

22

28

Table 6-51 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.

Table 6-51 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Single-phase, High-voltage 22 kVA PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

22

28

A and B

Module 1, phase 2

0

24

30

A and B

Module 1, phase 3

0

22

28

Table 6-52 lists the threshold values for Oracle Exadata Database Machine X3-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.

Table 6-52 Threshold Values for Oracle Exadata Database Machine X3-8 Full Rack with Three-phase, High-voltage 24 kVA PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

12

16

A

Module 1, phase 2

0

13

17

A

Module 1, phase 3

0

10

13

A

Module 2, phase 1

0

10

13

A

Module 2, phase 2

0

13

17

A

Module 2, phase 3

0

11

15

B

Module 1, phase 1

0

10

13

B

Module 1, phase 2

0

13

17

B

Module 1, phase 3

0

11

15

B

Module 2, phase 1

0

12

16

B

Module 2, phase 2

0

13

17

B

Module 2, phase 3

0

10

13