6.6.2.1 PDU Thresholds for Oracle Exadata Database Machine X4-2 Full Rack
The following tables list the threshold values for Oracle Exadata Database Machine X4-2 Full Rack:
-
Table 6-1 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Single-phase, Low-voltage PDU
-
Table 6-2 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Three-phase, Low-voltage PDU
-
Table 6-3 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Single-phase, High-voltage PDU
-
Table 6-4 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Three-phase, High-voltage PDU
Table 6-1 lists the threshold values for Oracle Exadata Database Machine X4-2 Full Rack using a single-phase, low-voltage PDU.
Table 6-1 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
20 |
24 |
A |
Module 1, phase 2 |
0 |
17 |
22 |
A |
Module 1, phase 3 |
0 |
19 |
24 |
B |
Module 1, phase 1 |
0 |
19 |
24 |
B |
Module 1, phase 2 |
0 |
17 |
22 |
B |
Module 1, phase 3 |
0 |
20 |
24 |
Table 6-2 lists the threshold values for Oracle Exadata Database Machine X4-2 Full Rack using a three-phase, low-voltage PDU.
Table 6-2 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
32 |
40 |
A and B |
Module 1, phase 2 |
0 |
34 |
42 |
A and B |
Module 1, phase 3 |
0 |
32 |
40 |
Table 6-3 lists the threshold values for Oracle Exadata Database Machine X4-2 Full Rack using a single-phase, high-voltage PDU.
Table 6-3 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
18 |
23 |
A |
Module 1, phase 2 |
0 |
16 |
20 |
A |
Module 1, phase 3 |
0 |
18 |
23 |
B |
Module 1, phase 1 |
0 |
18 |
23 |
B |
Module 1, phase 2 |
0 |
16 |
20 |
B |
Module 1, phase 3 |
0 |
18 |
23 |
Table 6-4 lists the threshold values for Oracle Exadata Database Machine X4-2 Full Rack using a three-phase, high-voltage PDU.
Table 6-4 Threshold Values for Oracle Exadata Database Machine X4-2 Full Rack with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
18 |
21 |
A and B |
Module 1, phase 2 |
0 |
18 |
21 |
A and B |
Module 1, phase 3 |
0 |
16 |
21 |
Parent topic: PDU Thresholds for Oracle Exadata Database Machine X4-2