6.6.2.2 PDU Thresholds for Oracle Exadata Database Machine X4-2 Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine X4-2 Half Rack:
-
Table 6-5 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Single-phase, Low-voltage PDU
-
Table 6-6 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Three-phase, Low-voltage PDU
-
Table 6-7 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Single-phase, High-voltage PDU
-
Table 6-8 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Three-phase, High-voltage PDU
Table 6-5 lists the threshold values for Oracle Exadata Database Machine X4-2 Half Rack using a single-phase, low-voltage PDU.
Table 6-5 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
20 |
24 |
A |
Module 1, phase 2 |
0 |
10 |
13 |
A |
Module 1, phase 3 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 1 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 2 |
0 |
10 |
13 |
B |
Module 1, phase 3 |
0 |
20 |
24 |
Table 6-6 lists the threshold values for Oracle Exadata Database Machine X4-2 Half Rack using a three-phase, low-voltage PDU.
Table 6-6 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
17 |
22 |
A and B |
Module 1, phase 2 |
0 |
19 |
24 |
A and B |
Module 1, phase 3 |
0 |
15 |
20 |
Table 6-7 lists the threshold values for Oracle Exadata Database Machine X4-2 Half Rack using a single-phase, high-voltage PDU.
Table 6-7 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
18 |
23 |
A |
Module 1, phase 2 |
0 |
9 |
12 |
A |
Module 1, phase 3 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 1 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 2 |
0 |
9 |
12 |
B |
Module 1, phase 3 |
0 |
18 |
23 |
Table 6-8 lists the threshold values for Oracle Exadata Database Machine X4-2 Half Rack using a three-phase, high-voltage PDU.
Table 6-8 Threshold Values for Oracle Exadata Database Machine X4-2 Half Rack with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
11 |
15 |
A and B |
Module 1, phase 2 |
0 |
9 |
12 |
A and B |
Module 1, phase 3 |
0 |
7 |
10 |
Parent topic: PDU Thresholds for Oracle Exadata Database Machine X4-2