6.6.2.3 PDU Thresholds for Oracle Exadata Database Machine X4-2 Quarter Rack
The following tables list the threshold values for Oracle Exadata Database Machine X4-2 Quarter Rack:
-
Table 6-9 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Single-phase, Low-voltage PDU
-
Table 6-10 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Three-phase, Low-voltage PDU
-
Table 6-11 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Single-phase, High-voltage PDU
-
Table 6-12 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Three-phase, High-voltage PDU
Table 6-9 lists the threshold values for Oracle Exadata Database Machine X4-2 Quarter Rack using a single-phase, low-voltage PDU.
Table 6-9 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
10 |
13 |
A |
Module 1, phase 2 |
0 |
5 |
7 |
A |
Module 1, phase 3 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 1 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 2 |
0 |
5 |
7 |
B |
Module 1, phase 3 |
0 |
10 |
13 |
Table 6-10 lists the threshold values for Oracle Exadata Database Machine X4-2 Quarter Rack using a three-phase, low-voltage PDU.
Table 6-10 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
11 |
14 |
A and B |
Module 1, phase 2 |
0 |
10 |
13 |
A and B |
Module 1, phase 3 |
0 |
5 |
7 |
Table 6-11 lists the threshold values for Oracle Exadata Database Machine X4-2 Quarter Rack using a single-phase, high-voltage PDU.
Table 6-11 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
9 |
12 |
A |
Module 1, phase 2 |
0 |
5 |
7 |
A |
Module 1, phase 3 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 1 |
0 |
0.1 |
0.2 |
B |
Module 1, phase 2 |
0 |
5 |
7 |
B |
Module 1, phase 3 |
0 |
9 |
12 |
Table 6-12 lists the threshold values for Oracle Exadata Database Machine X4-2 Quarter Rack using a three-phase, high-voltage PDU.
Table 6-12 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter Rack with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
9 |
11 |
A and B |
Module 1, phase 2 |
0 |
3 |
4 |
A and B |
Module 1, phase 3 |
0 |
3 |
4 |
Parent topic: PDU Thresholds for Oracle Exadata Database Machine X4-2