22 Cabling Tables for Oracle Exadata Storage Expansion Rack X8M and Earlier
Note:
For ease of reading, the name "Oracle Exadata Rack" is used when information refers to both Oracle Exadata Database Machine and Oracle Exadata Storage Expansion Rack.- Storage Expansion Rack Layout Diagrams
These tables show the component placement within Oracle Exadata Storage Expansion Rack. - Integrated Lights Out Manager (ILOM) Cabling Tables
These tables show the ILOM network cabling for the Oracle Exadata Storage Expansion Racks. - Administrative Network Cabling Tables
These tables show the Administrative network cabling for the Oracle Exadata Storage Expansion Racks. - Single Phase Power Distribution Unit Cabling Tables
These tables show the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack. - Three Phase Power Distribution Unit Cabling Tables
These tables show the cabling routes from each three-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack. - RDMA Network Fabric Network Cabling Tables
These tables show the RDMA Network Fabric network cabling connections for the Oracle Exadata Storage Expansion Rack.
Parent topic: Cabling Information for Oracle Exadata Database Machine
22.1 Storage Expansion Rack Layout Diagrams
These tables show the component placement within Oracle Exadata Storage Expansion Rack.
Oracle Exadata Storage Expansion Rack X5 to X8M
The following image shows the front and rear of Oracle Exadata Storage Expansion Full Rack for X5 to X8M. The front is shown on the left, and the rear is shown on the right.
Figure 22-1 Rack Layout of Oracle Exadata Storage Expansion Full Rack X5 to X8M
Description of "Figure 22-1 Rack Layout of Oracle Exadata Storage Expansion Full Rack X5 to X8M"
Oracle Exadata Storage Expansion Rack X3-2 and X4-2
The following image shows the front and rear of Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack. The front is shown on the left, and the rear is shown on the right.
Figure 22-2 Rack Layout of Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
Description of "Figure 22-2 Rack Layout of Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack"
The following image shows the front and rear of Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack. The front is shown on the left, and the rear is shown on the right.
Figure 22-3 Rack Layout of Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
Description of "Figure 22-3 Rack Layout of Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack"
The following image shows the front and rear of Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack. The front is shown on the left, and the rear is shown on the right.
Figure 22-4 Rack Layout of Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
Description of "Figure 22-4 Rack Layout of Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack"
Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following image shows the front and rear views of Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers. The front is shown on the left, and the rear is shown on the right.
Figure 22-5 Rack Layout of Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Description of "Figure 22-5 Rack Layout of Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers"
The following image shows the front and rear views of Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers. The front is shown on the left, and the rear is shown on the right.
Figure 22-6 Rack Layout of Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Description of "Figure 22-6 Rack Layout of Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers"
The following image shows the front and rear views of Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers. The front is shown on the left, and the rear is shown on the right.
Figure 22-7 Rack Layout of Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Description of "Figure 22-7 Rack Layout of Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers"
22.2 Integrated Lights Out Manager (ILOM) Cabling Tables
These tables show the ILOM network cabling for the Oracle Exadata Storage Expansion Racks.
The ILOM port on the servers is labeled NET MGT, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.
-
Table 22-1 ILOM Cabling for Oracle Exadata Storage Expansion Rack X6-2, X7-2, X8-2, and X8M-2
-
Table 22-2 ILOM Cabling for Oracle Exadata Storage Expansion Rack X5-2
-
Table 22-3 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack
-
Table 22-4 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack
-
Table 22-5 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack
-
Table 22-6 ILOM Cabling for Oracle Exadata Storage Expansion Rack Full Rack with Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-7 ILOM Cabling for Oracle Exadata Storage Expansion Rack Half Rack with Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-8 ILOM Cabling for Oracle Exadata Storage Expansion Rack Quarter Rack with Storage Server with Sun Fire X4270 M2 Servers
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X6-2 and X7-2:
Table 22-1 ILOM Cabling for Oracle Exadata Storage Expansion Rack X6-2, X7-2, X8-2, and X8M-2
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U41 |
Storage Server |
16 |
U39 |
Storage Server |
2 |
U37 |
Storage Server |
4 |
U35 |
Storage Server |
6 |
U33 |
Storage Server |
8 |
U31 |
Storage Server |
10 |
U29 |
Storage Server |
12 |
U27 |
Storage Server |
14 |
U25 |
Storage Server |
18 |
U23 |
Storage Server |
22 |
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
PDU-A |
PDU |
19 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X5-2:
Table 22-2 ILOM Cabling for Oracle Exadata Storage Expansion Rack X5-2
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U41 |
Storage Server |
16 |
U39 |
Storage Server |
2 |
U37 |
Storage Server |
4 |
U35 |
Storage Server |
6 |
U33 |
Storage Server |
8 |
U31 |
Storage Server |
10 |
U29 |
Storage Server |
12 |
U27 |
Storage Server |
14 |
U25 |
Storage Server |
18 |
U23 |
Storage Server |
22 |
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack:
Table 22-3 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U39 |
Storage Server |
2 |
U37 |
Storage Server |
4 |
U35 |
Storage Server |
6 |
U33 |
Storage Server |
8 |
U31 |
Storage Server |
10 |
U29 |
Storage Server |
12 |
U27 |
Storage Server |
14 |
U25 |
Storage Server |
18 |
U23 |
Storage Server |
22 |
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack:
Table 22-4 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack:
Table 22-5 ILOM Cabling for Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-6 ILOM Cabling for Oracle Exadata Storage Expansion Rack Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U41 |
Storage Server |
2 |
U39 |
Storage Server |
4 |
U37 |
Storage Server |
6 |
U35 |
Storage Server |
8 |
U33 |
Storage Server |
10 |
U31 |
Storage Server |
12 |
U29 |
Storage Server |
14 |
U27 |
Storage Server |
18 |
U25 |
Storage Server |
22 |
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-7 ILOM Cabling for Oracle Exadata Storage Expansion Rack Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-8 ILOM Cabling for Oracle Exadata Storage Expansion Rack Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
22.3 Administrative Network Cabling Tables
These tables show the Administrative network cabling for the Oracle Exadata Storage Expansion Racks.
The port on the storage servers is labeled NET0, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.
-
Table 22-9 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X6-2, X7-2, X8-2, and X8M-2
-
Table 22-10 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X5-2
-
Table 22-11 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack
-
Table 22-12 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack
-
Table 22-13 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack
-
Table 22-14 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-15 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-16 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X6-2, X7-2, X8-2, and X8M-2
Table 22-9 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X6-2, X7-2, X8-2, and X8M-2
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U41 |
Storage Server |
15 |
U39 |
Storage Server |
1 |
U37 |
Storage Server |
3 |
U35 |
Storage Server |
5 |
U33 |
Storage Server |
7 |
U31 |
Storage Server |
9 |
U29 |
Storage Server |
11 |
U27 |
Storage Server |
13 |
U25 |
Storage Server |
17 |
U23 |
Storage Server |
21 |
U22 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X5-2
Table 22-10 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X5-2
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U41 |
Storage Server |
15 |
U39 |
Storage Server |
1 |
U37 |
Storage Server |
3 |
U35 |
Storage Server |
5 |
U33 |
Storage Server |
7 |
U31 |
Storage Server |
9 |
U29 |
Storage Server |
11 |
U27 |
Storage Server |
13 |
U25 |
Storage Server |
17 |
U23 |
Storage Server |
21 |
U22 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
PDU-A |
PDU |
19 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack:
Table 22-11 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U39 |
Storage Server |
1 |
U37 |
Storage Server |
3 |
U35 |
Storage Server |
5 |
U33 |
Storage Server |
7 |
U31 |
Storage Server |
9 |
U29 |
Storage Server |
11 |
U27 |
Storage Server |
13 |
U25 |
Storage Server |
17 |
U23 |
Storage Server |
21 |
U24 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack:
Table 22-12 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U22 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack:
Table 22-13 Administrative Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U22 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Exadata Storage Server |
43 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-14 Administrative Network Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U41 |
Storage Server |
1 |
U39 |
Storage Server |
3 |
U37 |
Storage Server |
5 |
U35 |
Storage Server |
7 |
U33 |
Storage Server |
9 |
U31 |
Storage Server |
11 |
U29 |
Storage Server |
13 |
U27 |
Storage Server |
17 |
U25 |
Storage Server |
21 |
U24 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-15 Administrative Network Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U24 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
Table 22-16 Administrative Network Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U24 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
PDU-A |
PDU |
16 |
PDU-B |
PDU |
20 |
22.4 Single Phase Power Distribution Unit Cabling Tables
These tables show the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
-
Table 22-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
-
Table 22-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
-
Table 22-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
-
Table 22-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
-
Table 22-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
-
Table 22-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
-
Table 22-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
-
Table 22-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
-
Table 22-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 22-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8M-2.
Table 22-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
Rack Unit | PS | PDU-A | PDU-B/PS1 | Cable Length |
---|---|---|---|---|
U42 |
PS0 |
G5-3 |
G0-3 |
2 meters |
U41 |
PS0 |
G5-5 |
G0-1 |
2 meters |
U40 |
PS0 |
G5-6 |
G0-0 |
2 meters |
U39 |
PS0 |
G3-6 |
G2-0 |
2 meters |
U37 |
PS0 |
G3-0 |
G2-6 |
2 meters |
U35 |
PS0 |
G5-4 |
G0-2 |
2 meters |
U33 |
PS0 |
G4-1 |
G1-5 |
2 meters |
U31 |
PS0 |
G5-2 |
G0-4 |
2 meters |
U29 |
PS0 |
G5-1 |
G0-5 |
2 meters |
U27 |
PS0 |
G4-3 |
G1-3 |
2 meters |
U26 |
PS0 |
G4-6 |
G1-0 |
2 meters |
U25 |
PS0 |
G4-5 |
G1-1 |
2 meters |
U24 |
PS0 |
G4-2 |
G1-4 |
2 meters |
U23 |
PS0 |
G4-0 |
G1-6 |
2 meters |
U22 |
PS2 |
G1-6 |
G4-0 |
2 meters |
U21 |
PS2 |
G1-5 |
G4-1 |
2 meters |
U20 |
PS2 |
G1-2 |
G4-4 |
2 meters |
U19 |
PS0 |
G3-2 |
G2-4 |
2 meters |
U18 |
PS0 |
G2-6 |
G3-0 |
2 meters |
U17 |
PS0 |
G0-6 |
G5-0 |
2 meters |
U16 |
PS0 |
G0-3 |
G5-3 |
2 meters |
U14 |
PS0 |
G2-3 |
G3-3 |
2 meters |
U12 |
PS0 |
G2-4 |
G3-2 |
2 meters |
U10 |
PS0 |
G2-0 |
G3-6 |
2 meters |
U8 |
PS0 |
G2-5 |
G3-1 |
2 meters |
U6 |
PS0 |
G0-0 |
G5-6 |
2 meters |
U4 |
PS0 |
G0-1 |
G5-5 |
2 meters |
U2 |
PS0 |
G1-0 |
G4-6 |
2 meters |
U1 |
PS2 |
G3-5 |
G2-1 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8-2.
Table 22-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G3-5 |
G2-1 |
2 meters |
U41 |
G5-5 |
G0-1 |
2 meters |
U40 |
G3-3 |
G2-3 |
2 meters |
U39 |
G5-4 |
G0-2 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-2 |
G0-4 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-3 |
G1-3 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-0 |
G2-6 |
2 meters |
U26 |
G5-1 |
G0-5 |
2 meters |
U25 |
G5-0 |
G0-6 |
2 meters |
U24 |
G4-1 |
G1-5 |
2 meters |
U23 |
G3-6 |
G2-0 |
2 meters |
U22 |
G1-2 |
G4-4 |
2 meters |
U21 |
G0-5 |
G5-1 |
2 meters |
U20 |
G0-4 |
G5-2 |
2 meters |
U19 |
G2-4 |
G3-2 |
2 meters |
U18 |
G1-1 |
G4-5 |
2 meters |
U17 |
G0-3 |
G5-3 |
2 meters |
U16 |
G0-2 |
G5-4 |
2 meters |
U14 |
G2-3 |
G3-3 |
2 meters |
U12 |
G2-2 |
G3-4 |
2 meters |
U10 |
G2-1 |
G3-5 |
2 meters |
U8 |
G2-0 |
G3-6 |
2 meters |
U6 |
G1-0 |
G4-6 |
2 meters |
U4 |
G0-1 |
G5-5 |
2 meters |
U2 |
G0-0 |
G5-6 |
2 meters |
U1 |
G4-0 |
G1-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X7-2.
Table 22-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-5 |
G0-1 |
2 meters |
U41 |
G3-6 |
G2-0 |
2 meters |
U40 |
G5-2 |
G0-4 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-1 |
G0-5 |
2 meters |
U33 |
G5-0 |
G0-6 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-3 |
G1-3 |
2 meters |
U27 |
G3-5 |
G2-1 |
2 meters |
U26 |
G4-5 |
G1-1 |
2 meters |
U25 |
G4-2 |
G1-4 |
2 meters |
U24 |
G4-1 |
G1-5 |
2 meters |
U23 |
G2-5 |
G3-1 |
2 meters |
U22 |
G1-4 |
G4-2 |
2 meters |
U21 |
G1-3 |
G4-3 |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U19 |
G2-3 |
G3-3 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U17 |
G1-6 |
G4-0 |
2 meters |
U16 |
G1-2 |
G4-4 |
2 meters |
U14 |
G2-4 |
G3-2 |
2 meters |
U12 |
G2-1 |
G3-5 |
2 meters |
U10 |
G2-0 |
G3-6 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G4-0 |
G1-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X6-2.
Table 22-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U42 |
G3-6 |
G2-0 |
2 meters |
U41 |
G4-5 |
G1-1 |
2 meters |
U40 |
G5-4 |
G0-2 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X5-2.
Table 22-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G4-5 |
G1-1 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack.
Table 22-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack.
Table 22-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack.
Table 22-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G0-0 |
2 meters |
U39 |
G5-3 |
G0-3 |
2 meters |
U37 |
G5-0 |
G0-6 |
2 meters |
U35 |
G4-6 |
G1-0 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-2 |
G1-4 |
2 meters |
U29 |
G3-6 |
G2-0 |
2 meters |
U27 |
G3-5 |
G2-1 |
2 meters |
U25 |
G3-3 |
G2-3 |
2 meters |
U24 |
G3-1 |
G2-5 |
2 meters |
U23 |
N/A |
G3-0 |
included |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
22.5 Three Phase Power Distribution Unit Cabling Tables
These tables show the cabling routes from each three-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
The following tables are in this section:
- Table 22-28 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
- Table 22-29 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
- Table 22-30 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
- Table 22-31 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
- Table 22-32 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
- Table 22-33 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
- Table 22-34 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
- Table 22-35 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
- Table 22-36 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
- Table 22-37 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
- Table 22-38 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8M-2.
Table 22-28 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-4 |
G2-2 |
2 meters |
U41 |
G5-2 |
G2-4 |
2 meters |
U40 |
G5-1 |
G2-5 |
2 meters |
U39 |
G5-6 |
G2-0 |
2 meters |
U37 |
G3-5 |
G0-1 |
2 meters |
U35 |
G3-0 |
G0-6 |
2 meters |
U33 |
G5-5 |
G2-1 |
2 meters |
U31 |
G5-3 |
G2-3 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-2 |
G0-4 |
2 meters |
U26 |
G5-0 |
G2-6 |
2 meters |
U25 |
G4-5 |
G1-1 |
2 meters |
U24 |
G3-1 |
G0-5 |
2 meters |
U23 |
G4-1 |
G1-5 |
2 meters |
U22 |
G1-6 |
G4-0 |
2 meters |
U21 |
G2-6 |
G5-0 |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U19 |
G1-1 |
G4-5 |
2 meters |
U18 |
G1-4 |
G4-2 |
2 meters |
U17 |
G2-1 |
G5-5 |
2 meters |
U16 |
G2-3 |
G5-3 |
2 meters |
U14 |
G0-5 |
G3-1 |
2 meters |
U12 |
G2-5 |
G5-1 |
2 meters |
U10 |
G0-3 |
G3-3 |
2 meters |
U8 |
G1-3 |
G4-3 |
2 meters |
U6 |
G2-4 |
G5-2 |
2 meters |
U4 |
G0-6 |
G3-0 |
2 meters |
U2 |
G0-0 |
G3-6 |
2 meters |
U1 |
G1-0 |
G4-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8-2.
Table 22-29 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-6 |
G2-0 |
2 meters |
U41 |
G5-3 |
G2-3 |
2 meters |
U40 |
G3-5 |
G0-1 |
2 meters |
U39 |
G4-3 |
G1-3 |
2 meters |
U37 |
G5-2 |
G2-4 |
2 meters |
U35 |
G3-2 |
G0-4 |
2 meters |
U33 |
G4-2 |
G1-4 |
2 meters |
U31 |
G5-1 |
G2-5 |
2 meters |
U29 |
G3-6 |
G0-0 |
2 meters |
U27 |
G4-1 |
G1-5 |
2 meters |
U26 |
G3-1 |
G0-5 |
2 meters |
U25 |
G4-0 |
G1-6 |
2 meters |
U24 |
G3-0 |
G0-6 |
2 meters |
U23 |
G2-6 |
G5-0 |
2 meters |
U22 |
G1-5 |
G4-1 |
2 meters |
U21 |
G2-4 |
G5-2 |
2 meters |
U20 |
G1-4 |
G4-2 |
2 meters |
U19 |
G0-6 |
G3-0 |
2 meters |
U18 |
G2-3 |
G5-3 |
2 meters |
U17 |
G0-2 |
G3-4 |
2 meters |
U16 |
G0-1 |
G3-5 |
2 meters |
U14 |
G1-3 |
G4-3 |
2 meters |
U12 |
G1-2 |
G4-4 |
2 meters |
U10 |
G1-1 |
G4-5 |
2 meters |
U8 |
G2-2 |
G5-4 |
2 meters |
U6 |
G0-0 |
G3-6 |
2 meters |
U4 |
G2-1 |
G5-5 |
2 meters |
U2 |
G2-0 |
G5-6 |
2 meters |
U1 |
G1-0 |
G4-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X7-2.
Table 22-30 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-4 |
G2-2 |
2 meters |
U41 |
G5-6 |
G2-0 |
2 meters |
U40 |
G4-6 |
G1-0 |
2 meters |
U39 |
G4-5 |
G1-1 |
2 meters |
U37 |
G3-5 |
G0-1 |
2 meters |
U35 |
G5-5 |
G2-1 |
2 meters |
U33 |
G4-3 |
G1-3 |
2 meters |
U31 |
G3-1 |
G0-5 |
2 meters |
U29 |
G4-0 |
G1-6 |
2 meters |
U27 |
G5-3 |
G2-3 |
2 meters |
U26 |
G5-1 |
G2-5 |
2 meters |
U25 |
G3-3 |
G0-3 |
2 meters |
U24 |
G4-4 |
G1-2 |
2 meters |
U23 |
G3-2 |
G0-4 |
2 meters |
U22 |
G2-6 |
G5-0 |
2 meter |
U21 |
G1-0 |
G4-6 |
2 meters |
U20 |
G0-0 |
G3-6 |
2 meters |
U19 |
G2-5 |
G5-1 |
2 meters |
U18 |
G0-6 |
G3-0 |
2 meters |
U17 |
G1-6 |
G4-0 |
2 meters |
U16 |
G2-1 |
G5-5 |
2 meters |
U14 |
G1-4 |
G4-2 |
2 meters |
U12 |
G2-3 |
G5-3 |
2 meters |
U10 |
G2-0 |
G5-6 |
2 meters |
U8 |
G1-2 |
G4-4 |
2 meters |
U6 |
G1-1 |
G4-5 |
2 meters |
U4 |
G0-2 |
G3-4 |
2 meters |
U2 |
G0-1 |
G3-5 |
2 meters |
U1 |
G2-2 |
G5-4 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X6-2.
Table 22-31 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-4 |
G2-2 |
2 meters |
U41 |
G5-5 |
G2-1 |
2 meters |
U40 |
G3-6 |
G0-0 |
2 meters |
U39 |
G5-6 |
G2-0 |
2 meters |
U37 |
G5-3 |
G2-3 |
2 meters |
U35 |
G5-0 |
G2-6 |
2 meters |
U33 |
G5-2 |
G2-4 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G4-1 |
G1-5 |
2 meters |
U26 |
G5-1 |
G2-5 |
2 meters |
U25 |
G3-5 |
G0-1 |
2 meters |
U24 |
G3-4 |
G0-2 |
2 meters |
U23 |
G3-3 |
G0-3 |
2 meters |
U22 |
G3-2 |
G0-4 |
2 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U19 |
G2-3 |
G5-3 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U17 |
G2-1 |
G5-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G1-5 |
G4-1 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X5-2.
Table 22-32 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G4-5 |
G1-1 |
2 meters |
U39 |
G5-6 |
G2-0 |
2 meters |
U37 |
G5-3 |
G2-3 |
2 meters |
U35 |
G5-0 |
G2-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G0-0 |
2 meters |
U25 |
G3-5 |
G0-1 |
2 meters |
U23 |
G3-3 |
G0-3 |
2 meters |
U22 |
G2-5 |
G5-1 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack.
Table 22-33 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U39 |
G5-6 |
G2-0 |
2 meters |
U37 |
G5-3 |
G2-3 |
2 meters |
U35 |
G5-0 |
G2-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G0-0 |
2 meters |
U25 |
G3-5 |
G0-1 |
2 meters |
U23 |
G3-3 |
G0-3 |
2 meters |
U22 |
G2-5 |
G5-1 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack.
Table 22-34 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G0-5 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack.
Table 22-35 Three Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G0-5 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-36 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G2-0 |
2 meters |
U39 |
G5-3 |
G2-3 |
2 meters |
U37 |
G5-0 |
G2-6 |
2 meters |
U35 |
G4-6 |
G1-0 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-2 |
G1-4 |
2 meters |
U29 |
G3-6 |
G0-0 |
2 meters |
U27 |
G3-5 |
G0-1 |
2 meters |
U25 |
G3-3 |
G0-3 |
2 meters |
U24 |
G3-1 |
G0-5 |
2 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-37 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U24 |
G3-1 |
G0-5 |
2 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-38 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U24 |
G3-1 |
G0-5 |
2 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
1 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
22.6 RDMA Network Fabric Network Cabling Tables
These tables show the RDMA Network Fabric network cabling connections for the Oracle Exadata Storage Expansion Rack.
- RDMA Network Fabric Cabling for Oracle Exadata Storage Expansion Rack X8M-2
Use the following RDMA Network Fabric cabling information for the Oracle Exadata Storage Expansion Rack X8M-2 - InfiniBand Network Cabling for Oracle Exadata Storage Expansion X7-2, X6-2 and X5-2
Use the following InfiniBand cabling information for the Exadata Storage Expansion X7-2, X6-2 and X5-2 systems. - InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2
Use the following InfiniBand cabling information for the Oracle Exadata Storage Expansion Rack X4-2 and X3-2. - InfiniBand Network Cabling for Oracle Exadata Storage Expansion with Sun Fire X4270 M2 Servers
Use the following InfiniBand cabling information for the Oracle Exadata Storage Expansion Server with Sun Fire X4270 M2 servers.
22.6.1 RDMA Network Fabric Cabling for Oracle Exadata Storage Expansion Rack X8M-2
Use the following RDMA Network Fabric cabling information for the Oracle Exadata Storage Expansion Rack X8M-2
Table 22-39 RDMA Network Fabric Cabling for Oracle Exadata Storage Expansion Rack X8M-2 Full Rack
From Rack Unit | Port | To RDMA Network Fabric Switch Rack Unit | Port | Description |
---|---|---|---|---|
U41 |
PCIe 1, P2 |
U22 |
15 |
3 meters |
U41 |
PCIe 1, P1 |
U20 |
15 |
3 meters |
U39 |
PCIe 1, P2 |
U22 |
08 |
3 meters |
U39 |
PCIe 1, P1 |
U20 |
08 |
3 meters |
U37 |
PCIe 1, P2 |
U22 |
09 |
3 meters |
U37 |
PCIe 1, P1 |
U20 |
09 |
3 meters |
U35 |
PCIe 1, P2 |
U22 |
10 |
3 meters |
U35 |
PCIe 1, P1 |
U20 |
10 |
3 meters |
U33 |
PCIe 1, P2 |
U22 |
11 |
3 meters |
U33 |
PCIe 1, P1 |
U20 |
11 |
3 meters |
U31 |
PCIe 1, P2 |
U22 |
12 |
3 meters |
U31 |
PCIe 1, P1 |
U20 |
12 |
3 meters |
U29 |
PCIe 1, P2 |
U22 |
13 |
3 meters |
U29 |
PCIe 1, P1 |
U20 |
13 |
3 meters |
U27 |
PCIe 1, P2 |
U22 |
14 |
3 meters |
U27 |
PCIe 1, P1 |
U20 |
14 |
3 meters |
U25 |
PCIe 1, P2 |
U22 |
16 |
3 meters |
U25 |
PCIe 1, P1 |
U20 |
16 |
3 meters |
U23 |
PCIe 1, P2 |
U22 |
18 |
3 meters |
U23 |
PCIe 1, P1 |
U20 |
18 |
3 meters |
U18 |
PCIe 1, P2 |
U22 |
20 |
3 meters |
U18 |
PCIe 1, P1 |
U20 |
20 |
3 meters |
U14 |
PCIe 1, P2 |
U22 |
23 |
3 meters |
U14 |
PCIe 1, P1 |
U20 |
23 |
3 meters |
U12 |
PCIe 1, P2 |
U22 |
24 |
3 meters |
U12 |
PCIe 1, P1 |
U20 |
24 |
3 meters |
U10 |
PCIe 1, P2 |
U22 |
25 |
3 meters |
U10 |
PCIe 1, P1 |
U20 |
25 |
3 meters |
U08 |
PCIe 1, P2 |
U22 |
26 |
3 meters |
U08 |
PCIe 1, P1 |
U20 |
26 |
3 meters |
U06 |
PCIe 1, P2 |
U22 |
27 |
3 meters |
U06 |
PCIe 1, P1 |
U20 |
27 |
3 meters |
U04 |
PCIe 1, P2 |
U22 |
28 |
3 meters |
U04 |
PCIe 1, P1 |
U20 |
28 |
3 meters |
U02 |
PCIe 1, P2 |
U22 |
29 |
3 meters |
U02 |
PCIe 1, P1 |
U20 |
29 |
3 meters |
U1 |
PCIe 1, P2 |
U22 |
3 meters |
|
U1 |
PCIe 1, P1 |
U20 |
3 meters |
Parent topic: RDMA Network Fabric Network Cabling Tables
22.6.2 InfiniBand Network Cabling for Oracle Exadata Storage Expansion X7-2, X6-2 and X5-2
Use the following InfiniBand cabling information for the Exadata Storage Expansion X7-2, X6-2 and X5-2 systems.
Table 22-40 InfiniBand Network Cabling for Oracle Exadata Storage Expansion X7-2, X6-2 and X5-2 Full Rack
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Port |
---|---|---|---|
U22 |
6B |
U41 |
PCIe 3, P1 |
U22 |
0A |
U39 |
PCIe 3, P1 |
U22 |
0B |
U37 |
PCIe 3, P1 |
U22 |
1A |
U35 |
PCIe 3, P1 |
U22 |
1B |
U33 |
PCIe 3, P1 |
U22 |
2A |
U31 |
PCIe 3, P1 |
U22 |
2B |
U29 |
PCIe 3, P1 |
U22 |
3B |
U27 |
PCIe 2, P1 |
U22 |
4A |
U25 |
PCIe 2, P1 |
U22 |
5A |
U23 |
PCIe 2, P1 |
U20 |
13A |
U18 |
PCIe 2, P1 |
U20 |
14B |
U16 |
PCIe 3, P1 |
U20 |
14A |
U14 |
PCIe 3, P1 |
U20 |
15A |
U12 |
PCIe 3, P1 |
U20 |
15B |
U10 |
PCIe 3, P1 |
U20 |
16A |
U08 |
PCIe 3, P1 |
U20 |
16B |
U06 |
PCIe 3, P1 |
U20 |
17A |
U04 |
PCIe 3, P1 |
U20 |
17B |
U02 |
PCIe 3, P1 |
U20 |
6B |
U41 |
PCIe 3, P2 |
U20 |
0A |
U39 |
PCIe 3, P2 |
U20 |
0B |
U37 |
PCIe 3, P2 |
U20 |
1A |
U35 |
PCIe 3, P2 |
U20 |
1B |
U33 |
PCIe 3, P2 |
U20 |
2A |
U31 |
PCIe 3, P2 |
U20 |
2B |
U29 |
PCIe 3, P2 |
U20 |
3B |
U27 |
PCIe 2, P2 |
U20 |
4A |
U25 |
PCIe 2, P2 |
U20 |
5A |
U23 |
PCIe 2, P2 |
U22 |
13A |
U18 |
PCIe 2, P2 |
U22 |
14B |
U16 |
PCIe 3, P2 |
U22 |
14A |
U14 |
PCIe 3, P2 |
U22 |
15A |
U12 |
PCIe 3, P2 |
U22 |
15B |
U10 |
PCIe 3, P2 |
U22 |
16A |
U08 |
PCIe 3, P2 |
U22 |
16B |
U06 |
PCIe 3, P2 |
U22 |
17A |
U04 |
PCIe 3, P2 |
U22 |
17B |
U02 |
PCIe 3, P2 |
U1 |
1B |
U20 |
8B |
U1 |
0B |
U22 |
8B |
Parent topic: RDMA Network Fabric Network Cabling Tables
22.6.3 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2
Use the following InfiniBand cabling information for the Oracle Exadata Storage Expansion Rack X4-2 and X3-2.
-
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Full Rack InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Full Rack
-
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Half Rack InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Half Rack
-
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Quarter Rack InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Quarter Rack
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Full Rack
The following table lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Rack X4-2 Full Rack, and Oracle Exadata Storage Expansion Rack X3-2 Full Rack.
Table 22-41 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Full Rack
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U22 |
0A |
U39 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
0B |
U37 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
1A |
U35 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
1B |
U33 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
2A |
U31 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
2B |
U29 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
3A |
U27 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U22 |
4A |
U25 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U22 |
5A |
U23 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U22 |
13A |
U18 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U22 |
14A |
U16 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U22 |
14B |
U14 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
15A |
U12 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
15B |
U10 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
0A |
U39 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
0B |
U37 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
1A |
U35 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
1B |
U33 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
2A |
U31 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
2B |
U29 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
3A |
U27 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
4A |
U25 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
3 meter QDR InfiniBand cable |
U20 |
5A |
U23 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
3 meter QDR InfiniBand cable |
U20 |
13A |
U18 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
3 meter QDR InfiniBand cable |
U20 |
14A |
U16 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
3 meter QDR InfiniBand cable |
U20 |
14B |
U14 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15A |
U12 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15B |
U10 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
U1 |
1B |
U20 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
U1 |
0B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Half Rack
The following table lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Rack X4-2 Half Rack, and Oracle Exadata Storage Expansion Rack X3-2 Half Rack.
Table 22-42 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Half Rack
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U22 |
13A |
U18 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
3 meter QDR InfiniBand cable |
U22 |
14A |
U16 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
3 meter QDR InfiniBand cable |
U22 |
14B |
U14 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
15A |
U12 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
15B |
U10 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
13A |
U18 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
3 meter QDR InfiniBand cable |
U20 |
14A |
U16 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
3 meter QDR InfiniBand cable |
U20 |
14B |
U14 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15A |
U12 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15B |
U10 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
U1 |
1B |
U20 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
U1 |
0B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Quarter Rack
The following table lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Rack X4-2 Quarter Rack, and Oracle Exadata Storage Expansion Rack X3-2 Quarter Rack.
Table 22-43 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Rack X4-2 and X3-2 Quarter Rack
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U22 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 2, P2 |
3 meter QDR InfiniBand cable |
U22 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U22 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Oracle Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Oracle Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
U1 |
1B |
U20 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
U1 |
0B |
U22 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
Parent topic: RDMA Network Fabric Network Cabling Tables
22.6.4 InfiniBand Network Cabling for Oracle Exadata Storage Expansion with Sun Fire X4270 M2 Servers
Use the following InfiniBand cabling information for the Oracle Exadata Storage Expansion Server with Sun Fire X4270 M2 servers.
Exadata Storage Expansion Full Rack with Sun Fire X4270 M2 Servers
Table 22-44 lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-44 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Full Rack with Sun Fire X4270 M2 Servers
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U24 |
0A |
U41 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
0B |
U39 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
1A |
U37 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
1B |
U35 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
2A |
U33 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
2B |
U31 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
3A |
U29 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U24 |
4A |
U27 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U24 |
5A |
U25 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U24 |
13A |
U18 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U24 |
14A |
U16 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U24 |
14B |
U14 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
15A |
U12 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
15B |
U10 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
16A |
U8 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
0A |
U41 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
0B |
U39 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
1A |
U37 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
1B |
U35 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
2A |
U33 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
2B |
U31 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
3A |
U29 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
4A |
U27 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U20 |
5A |
U25 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U20 |
13A |
U18 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
14A |
U16 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
14B |
U14 |
Exadata Storage Server |
PCIe 3, P1 |
2 meter QDR InfiniBand cable |
U20 |
15A |
U12 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15B |
U10 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
U1 |
1B |
U20 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
U1 |
0B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
Exadata Storage Expansion Half Rack with Sun Fire X4270 M2 Servers
Table 22-45 lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-45 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Half Rack with Sun Fire X4270 M2 Servers
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U24 |
13A |
U18 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U24 |
14A |
U16 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U24 |
14B |
U14 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
15A |
U12 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
15B |
U10 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
16A |
U8 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
13A |
U18 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
14A |
U16 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
14B |
U14 |
Exadata Storage Server |
PCIe 3, P1 |
2 meter QDR InfiniBand cable |
U20 |
15A |
U12 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
15B |
U10 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
U1 |
1B |
U20 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
U1 |
0B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
8B |
3 meter QDR InfiniBand cable |
Exadata Storage Expansion Quarter Rack with Sun Fire X4270 M2 Servers
Table 22-46 lists the location, ports and cables for the InfiniBand connections for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 22-46 InfiniBand Network Cabling for Oracle Exadata Storage Expansion Quarter Rack with Sun Fire X4270 M2 Servers
From InfiniBand Switch Rack Unit | Port | To Rack Unit | Type of Equipment | Port | Cable Description |
---|---|---|---|---|---|
U24 |
16A |
U8 |
Exadata Storage Server |
PCIe 2, P2 |
2 meter QDR InfiniBand cable |
U24 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U24 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P2 |
3 meter QDR InfiniBand cable |
U20 |
16A |
U8 |
Exadata Storage Server |
PCIe 2, P1 |
2 meter QDR InfiniBand cable |
U20 |
16B |
U6 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17A |
U4 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
17B |
U2 |
Exadata Storage Server |
PCIe 3, P1 |
3 meter QDR InfiniBand cable |
U20 |
9B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9A |
2 meter QDR InfiniBand cable |
U20 |
10B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10A |
2 meter QDR InfiniBand cable |
U20 |
11B |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11A |
2 meter QDR InfiniBand cable |
U20 |
8A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
8A |
2 meter QDR InfiniBand cable |
U20 |
9A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
9B |
2 meter QDR InfiniBand cable |
U20 |
10A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
10B |
2 meter QDR InfiniBand cable |
U20 |
11A |
U24 |
Sun Datacenter InfiniBand Switch 36 switch |
11B |
2 meter QDR InfiniBand cable |
Parent topic: RDMA Network Fabric Network Cabling Tables