23.4 Single Phase Power Distribution Unit Cabling Tables

These tables show the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

  • Table 23-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2

  • Table 23-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2

  • Table 23-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2

  • Table 23-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2

  • Table 23-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2

  • Table 23-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack

  • Table 23-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack

  • Table 23-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack

  • Table 23-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

  • Table 23-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

  • Table 23-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8M-2.

Table 23-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2

Rack Unit PS PDU-A PDU-B/PS1 Cable Length

U42

PS0

G5-3

G0-3

2 meters

U41

PS0

G5-5

G0-1

2 meters

U40

PS0

G5-6

G0-0

2 meters

U39

PS0

G3-6

G2-0

2 meters

U37

PS0

G3-0

G2-6

2 meters

U35

PS0

G5-4

G0-2

2 meters

U33

PS0

G4-1

G1-5

2 meters

U31

PS0

G5-2

G0-4

2 meters

U29

PS0

G5-1

G0-5

2 meters

U27

PS0

G4-3

G1-3

2 meters

U26

PS0

G4-6

G1-0

2 meters

U25

PS0

G4-5

G1-1

2 meters

U24

PS0

G4-2

G1-4

2 meters

U23

PS0

G4-0

G1-6

2 meters

U22

PS2

G1-6

G4-0

2 meters

U21

PS2

G1-5

G4-1

2 meters

U20

PS2

G1-2

G4-4

2 meters

U19

PS0

G3-2

G2-4

2 meters

U18

PS0

G2-6

G3-0

2 meters

U17

PS0

G0-6

G5-0

2 meters

U16

PS0

G0-3

G5-3

2 meters

U14

PS0

G2-3

G3-3

2 meters

U12

PS0

G2-4

G3-2

2 meters

U10

PS0

G2-0

G3-6

2 meters

U8

PS0

G2-5

G3-1

2 meters

U6

PS0

G0-0

G5-6

2 meters

U4

PS0

G0-1

G5-5

2 meters

U2

PS0

G1-0

G4-6

2 meters

U1

PS2

G3-5

G2-1

3 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8-2.

Table 23-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U42

G3-5

G2-1

2 meters

U41

G5-5

G0-1

2 meters

U40

G3-3

G2-3

2 meters

U39

G5-4

G0-2

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-2

G0-4

2 meters

U33

G4-4

G1-2

2 meters

U31

G4-3

G1-3

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-0

G2-6

2 meters

U26

G5-1

G0-5

2 meters

U25

G5-0

G0-6

2 meters

U24

G4-1

G1-5

2 meters

U23

G3-6

G2-0

2 meters

U22

G1-2

G4-4

2 meters

U21

G0-5

G5-1

2 meters

U20

G0-4

G5-2

2 meters

U19

G2-4

G3-2

2 meters

U18

G1-1

G4-5

2 meters

U17

G0-3

G5-3

2 meters

U16

G0-2

G5-4

2 meters

U14

G2-3

G3-3

2 meters

U12

G2-2

G3-4

2 meters

U10

G2-1

G3-5

2 meters

U8

G2-0

G3-6

2 meters

U6

G1-0

G4-6

2 meters

U4

G0-1

G5-5

2 meters

U2

G0-0

G5-6

2 meters

U1

G4-0

G1-6

3 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X7-2.

Table 23-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U42

G5-5

G0-1

2 meters

U41

G3-6

G2-0

2 meters

U40

G5-2

G0-4

2 meters

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-1

G0-5

2 meters

U33

G5-0

G0-6

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-3

G1-3

2 meters

U27

G3-5

G2-1

2 meters

U26

G4-5

G1-1

2 meters

U25

G4-2

G1-4

2 meters

U24

G4-1

G1-5

2 meters

U23

G2-5

G3-1

2 meters

U22

G1-4

G4-2

2 meters

U21

G1-3

G4-3

2 meters

U20

G1-5

G4-1

2 meters

U19

G2-3

G3-3

2 meters

U18

G2-2

G3-4

2 meters

U17

G1-6

G4-0

2 meters

U16

G1-2

G4-4

2 meters

U14

G2-4

G3-2

2 meters

U12

G2-1

G3-5

2 meters

U10

G2-0

G3-6

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G4-0

G1-6

3 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X6-2.

Table 23-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U42

G3-6

G2-0

2 meters

U41

G4-5

G1-1

2 meters

U40

G5-4

G0-2

2 meters

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-0

G0-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G2-0

2 meters

U25

G3-5

G2-1

2 meters

U23

G3-3

G2-3

2 meters

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X5-2.

Table 23-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U41

G4-5

G1-1

2 meters

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-0

G0-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G2-0

2 meters

U25

G3-5

G2-1

2 meters

U23

G3-3

G2-3

2 meters

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack.

Table 23-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-0

G0-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G2-0

2 meters

U25

G3-5

G2-1

2 meters

U23

G3-3

G2-3

2 meters

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack.

Table 23-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack.

Table 23-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G2-5

2 meters

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.

Table 23-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U41

G5-6

G0-0

2 meters

U39

G5-3

G0-3

2 meters

U37

G5-0

G0-6

2 meters

U35

G4-6

G1-0

2 meters

U33

G4-4

G1-2

2 meters

U31

G4-2

G1-4

2 meters

U29

G3-6

G2-0

2 meters

U27

G3-5

G2-1

2 meters

U25

G3-3

G2-3

2 meters

U24

G3-1

G2-5

2 meters

U23

N/A

G3-0

included

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.

Table 23-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G2-5

2 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.

Table 23-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G2-5

2 meters

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters