B Backplane Connectors

B.1 Control Shelf Connectors

This section describes the Control shelf backplanes and their connectors. The control shelf backplane provides connectors for the system circuit cards. These connectors are four column High Density Interconnect (HDI) male headers with shrouds of varying pin quantities, depending on card position.

The control shelf backplane provides –48VDC power and ground to all card positions. The power is distributed into two parts, A and B. Power is brought to the shelf from the Fuse and Alarm Panel (FAP) using two cables. The connectors on the control shelf backplane are DB-26 high density connectors. The power is distributed over two separate pins per power connection to handle the current load.

  • Power connectors

    • Fuse and Alarm Panel (FAP) connectors

    • Fan Power connectors

  • Alarm connectors

    • Remote Maintenance Center Alarm connector

    • Local Maintenance Center Alarm connector

    • Rack Alarm connectors

    • Row Alarm connector

    • External Alarm connector

    • CUST Alarm 1 connector

    • CUST Alarm 2 connector

    • OAP Alarm connector

  • System clock connectors

  • Shelf clock connectors (850-0330-04 only)

  • BITS connectors

  • Serial port connectors

  • Interface connectors

  • IMT connectors

  • General purpose relay connectors

  • General purpose serial interface connectors

B.1.1 Control Shelf Backplane 04

Figure B-1 Control Shelf Backplane 04

img/r_control_shelf_backplane_04_im-fig1.jpg

B.1.2 Control Shelf Backplane 06/07

The connectors on backplanes -06 and -07 are identical.

Figure B-2 Control Shelf Backplane 06/07)

img/r_control_shelf_backplane_06_07_im-fig1.jpg

B.1.3 Overview of the Control Shelf Backplane Connectors

Table B-1 compares the connectors of Control Shelf backplane 04 with the connectors of Control Shelf backplane 06/07.

Table B-1 Control Shelf Backplanes -04 and -06/07

Control Shelf Backplane (P/N 850-0330-04) Control Shelf Backplane (P/N 850-0330-06/07)

J-1 B POWER

J-1 B POWER PRIMARY

J-2 B FAN POWER

J-8 B FAN POWER

J-3 A FAN POWER

J-9 A FAN POWER

 

J-10 A POWER SECONDARY

 

J-2 B POWER SECONDARY

J-4 A POWER

J-11 A POWER PRIMARY

J-5 RALM0

J-13 RALM0

J-6 B CLK 0

J-3 B CLK 0

J-4 B CLK 6

J-7 A CLK 0

J-7 A CLK 0

J-6 A CLK 6

J-8 A IMT IN GND

J-23 A IMT IN

J-9 A CLK IN

N/A

J-10 A CLK OUT

J-14 CI

J-11 RALM 1

J-15 RALM 1

J-12 B CLK 2

J-16 B CLK 2

J-13 B CLK 1

J-18 B CLK 1

J-14 A CLK 2

J-21 A CLK 2

J-15 A CLK 1

J-20 A CLK 1

J-16 A IMT OUT

J-22 A IMT OUT

J-17 MMI 0

J-24 MMI 0

J-18 MMI 1

J-25 MMI 1

J-19 MMI 2

J-26 MMI 2

J-20 MMI 3

J-27 MMI 3

J-21 MMI 4

J-28 MMI 4

J-22 MMI 5

J-29 MMI 5

J-23 MMI 6

J-30 MMI 6

J-24 MMI 7

J-31 MMI 7

J-25 RALM2

J-32 RALM2

J-26 RMC

J-33 RMC

J-27 ROW ALM

J-34 ROW ALM

J-28 EXT ALARM

J-35 CUST ALM 1

J-66 CUST ALM 2

J-29 PORT 10A

J-36 PORT 10A

J-30 PORT 9A

J-37 PORT 9A

J-31 PORT 8A

J-38 PORT 8A

J-32 PORT 7A

J-39 PORT 7A

J-33 PORT 6A

J-40 PORT 6A

J-34 PORT 5A

J-41 PORT 5A

J-35 PORT 4A

J-42 PORT 4A

J-36 PORT 3A

J-43 PORT 3A

J-37 PORT 2A

J-44 PORT 2A

J-38 PORT 1A

J-45 PORT 1A

J-39 RALM 3

J-46 RALM 3

J-40 LMC

J-47 LMC

J-41 SECONDARY BITS

J-48 SECONDARY BITS

J-42 PRIMARY BITS

J-49 PRIMARY BITS

J-43 PORT 10B

J-50 PORT 10B

J-44 PORT 9B

J-51 PORT 9B

J-45 PORT 8B

J-52 PORT 8B

J-46 PORT 7B

J-53 PORT 7B

J-47 PORT 6B

J-54 PORT 6B

J-48 PORT 5B

J-55 PORT 5B

J-49 PORT 4B

J-56 PORT 4B

J-50 PORT 3B

J-57 PORT 3B

J-51 PORT 2B

J-58 PORT 2B

J-52 PORT 1B

J-59 PORT 1B

J-53 RALM4

J-61 RALM4

J-60 RALM 6

J-54 B CLK4

J-62 B CLK 4

J-55 B CLK 3

J-63 B CLK 3

J-56 A CLK 4

J-64 A CLK 4

J-57 A CLK 3

J-65 A CLK 3

J-58 B IMT IN

J-75 B IMT IN

J-59 B CLK IN

N/A

J-60 B CLK OUT

N/A

J-61 RALM5

J-68 RALM5

J-62 B CLK 5

J-70 B CLK 5

J-71 GP01

J-63 A CLK 5

J-72 A CLK 5

J-64 B IMT OUT

J-74 B IMT OUT

J-65 MMI 8

J-76 MMI 8

J-66 MMI 9

J-77 MMI 9

J-67 MMI 10

J-78 MMI 10

J-68 MMI 11

J-79 MMI 11

J-69 MMI 12

J-80 MMI 12

J-70 MMI 13

J-81 MMI 13

J-71 MMI 14

J-82 MMI 14

J-72 MMI 15

J-83 MMI 15

J-73 GP02

J-69 OAPALM

J-74 OAPALM

J-75 GP01

J-5 GP02

J-71 GP01

J-76 GPSI

J-73 GPS1

 

J-67 RALM7

 

J-17 ENET 2 MASP B

 

J-19 ENET 1 MASP A

B.1.4 Power Connectors

The control shelf backplane provides –48VDC power and ground to all card positions. The power is distributed into two parts, A and B. Power is brought to the shelf from the Fuse and Alarm Panel (FAP) using two cables. The connectors on the control shelf backplane are DB-26 high density connectors. The power is distributed over two separate pins per power connection to handle the current load.

J1, J4 on Control Shelf backplane 04 J1, J11 Primary and J2, J10 Secondary on Control Shelf backplane 06/07

Figure B-3 Power Connector


img/r_power_connectors_im-fig1.jpg

Table B-2 Power Connector

Pin Signal Pin Signal

1

P5$48VDC

14

LGND

2

P5$48RTN

15

P3$48RTN

3

P4$48VDC

16

P3$48VDC

4

P4$48RTN

17

P2$48RTN

5

LGND

18

P2$48VDC

6

P3$48RTN

19

P1$48RTN

7

P3$48VDC

20

P1$48RTN

8

P2$48RTN

21

P1$48VDC

9

P2$48VDC

22

P1$48VDC

10

P5$48VDC

23

PF$48RTN

11

P5$48RTN

24

PF$48RTN

12

P4$48VDC

25

PF$48VDC

13

P4$48RTN

26

PF$48VDC

$= A or B, A POWER (J4) or B POWER (J1)

B.1.4.1 Fuse and Alarm Panel 870-2320-01/03

The FAP provides protected distribution of power to the system. Protection is provided by fuses placed in fuse holders on the front panel. The FAP contains a fuse fail alarm circuit that operates when one or more fuses fail.

Figure B-4 Control/Extension FAP Rear View


img/r_fuse_and_alarm_panel_870_2320_01_03_im-fig1.jpg

Figure B-5 Alarm Interface Connector

img/r_fuse_and_alarm_panel_870_2320_01_03_im-fig2.jpg

Table B-3 Alarm Interface Connector

Pin

Circuit Descriptions

1 / 2 / 3 / 4

 

5

Critical Alarm

6 / 7

 

8

Fuse Normally Closed

9

 

10

Minor Alarm

11

Major Alarm

12

Common

13

 

14

Test

15

Fuse Normally Open

B.1.4.1.1 Shelf Power

The Fuse and Alarm Panel powers up to three shelves in the frame through the FAP connectors P1, P2, and P3.

Figure B-6 Shelf Power Connector

img/r_shelf_power_im-fig1.jpg

Table B-4 Shelf Power Connector

Connector Fuse Position Pin Numbers Circuit Descriptions

P1

(to top shelf in frame)

1

3 and 12

+48VDC

2 and 11

48VDC return

2

1 and 10

+48VDC

19 and 20

48VDC return

3

21 and 22

+48VDC

4 and 13

48VDC return

4

23 and 24

+48VDC

6 and 15

48VDC return

5

9 and 18

+48VDC

8 and 17

48VDC return

6

7 and 16

+48VDC

25 and 26

48VDC return

P2

(to middle shelf in frame)

7

3 and 12

+48VDC

2 and 11

48VDC return

8

1 and 10

+48VDC

19 and 20

48VDC return

9

21 and 22

+48VDC

4 and 13

48VDC return

10

23 and 24

+48VDC

6 and 15

48VDC return

11

9 and 18

+48VDC

8 and 17

48VDC return

12

7 and 16

+48VDC

25 and 26

48VDC return

P3

(to bottom shelf in frame)

13

3 and 12

+48VDC

2 and 11

48VDC return

14

1 and 10

+48VDC

19 and 20

48VDC return

15

21 and 22

+48VDC

4 and 13

48VDC return

16

23 and 24

+48VDC

6 and 15

48VDC return

17

9 and 18

+48VDC

8 and 17

48VDC return

18

7 and 16

+48VDC

25 and 26

48VDC return

P1, P2, and P3

 

5 and 14

logic ground

NOTES: A side and B side connectors, fuse positions, and pins are identical.

    All return pins are common.

B.1.4.2 Rack Alarm (Alarm Interface)

Figure B-7 Rack Alarm Connector

img/r_rack_alarm_alarm_interface_im-fig1.jpg

Table B-5 Rack Alarm Connector

Pin Circuit Descriptions

1 / 2 / 3 / 4

 

5

Critical Alarm

6 / 7

 

8

Fuse Normally Closed

9

 

10

Minor Alarm

11

Major Alarm

12

Common

13

 

14

Test

15

Fuse Normally Open

B.1.4.3 Fan Power

J2, J3 on Control Shelf backplane 04 and J8, J9 on Control Shelf backplane 06/07

Figure B-8 Fan Power Connector

img/r_fan_power_im-fig1.jpg

Table B-6 Fan Power Connector

Pin Signal Pin Signal

1

PF$48RTN

6

FAN$ALM-

2

PF$48RTN

7

 

3

 

8

CHASSIS GND

4

PF$48VDC

9

FANCNTRL

5

PF$48VDC

   

$= A or B, A fan power (J3) or B fan power (J2)

B.1.5 Alarm Connectors

B.1.5.1 Local Maintenance Center Alarm Connector

Local Maintenance Center Alarm Connector connector provides the system’s alarm condition indicators to the local maintenance center.

J40 on Control Shelf backplane 04 and J47 on Control Shelf backplane 06/07

Figure B-9 Local Maintenance Center Alarm Connector


img/r_local_maintenance_center_alarm_connector_im-fig1.jpg

Table B-7 Local Maintenance Center Alarm Connector

Pin Signal

1, 3, 4, 5, 11, 12

Not used

2

LMCANC - Local Maintenance Center Audible Alarm, Normally Closed

6

LMCVMJNC - Local Maintenance Center Major Alarm, Normally Closed

7

LMCVMNNC - Local Maintenance Center Minor Alarm, Normally Closed

8

LMCVCRNC - Local Maintenance Center Critical Alarm, Normally Closed

9

LMCACOM - Local Maintenance Center Audible Alarm Common

10

LMCANO - Local Maintenance Center Audible alarm, normally Open

13

LMCVCOM - Local Maintenance Center Common

14

LMCVMJNO - Local Maintenance Center Major Alarm, Normally Open

15

LMCVMNNO - Local Maintenance Center Minor Alarm, Normally Open

B.1.5.2 Remote Maintenance Center Alarm Connector

The Remote Maintenance Center Alarm connector provides system alarm condition indicators to the remote maintenance center.

J26 on Control Shelf backplane 04 and J33 on Control Shelf backplane 06/07

Figure B-10 Remote Maintenance Center Alarm Connector


img/r_remote_maintenance_center_alarm_connector_im-fig1.jpg

Table B-8 Remote Maintenance Center Alarm Connector

Pin Signal

1, 3, 4, 5, 9, 11, 12

not used

2

RMCANC - Remote Maintenance Center Audible Alarm, Normally Closed

6

RMCMJNC - Remote Maintenance Center Major Alarm, Normally Closed

7

RMCMNNC - Remote Maintenance Center Minor Alarm, Normally Closed

8

RMCCRNC - Remote Maintenance Center Critical Alarm, Normally Closed

10

RMCANO - Remote Maintenance Center Audible Alarm, Normally Open

13

RMCCOM - Remote Maintenance Center Common

14

RMCMJNO - Remote Maintenance Center Major Alarm, Normally Open

15

RMCMNNO - Remote Maintenance Center Minor Alarm, Normally Open

B.1.5.3 Rack Alarm Connectors

The output of the Rack Alarm Connectors control the alarm condition indicators on each control or extension frame fuse and alarm panel.

J5, J11, J25, J39, J53, J61 on Control Shelf backplane 04 and J13, J15, J32, J46, J61, J68 on Control Shelf backplane 06/07

Figure B-11 Rack Alarm Connector

img/r_rack_alarm_connectors_im-fig1.jpg

Table B-9 Rack Alarm Connector

Pin Signal

1, 2, 6, 7, 9, 13, 14

Not used

3

R$MNNC - Rack Alarm, Minor, Normally Closed

4

R$MJNC - Rack Alarm, Major, Normally Closed

5

R$CRNC - Rack Alarm, Critical, Normally Closed

8

R$FA+ - Rack Fuse Alarm (+)

10

R$MNNO - Rack Alarm, Minor, Normally Open

11

R$MJNO - Rack Alarm, Major, Normally Open

12

R$COM - Rack Alarm, Common

15

R$FA- - Rack Fuse Alarm (-)

$= 0 through 5, RALM0 through RALM5 (J5, J11, J25, J39, J53, J61 respectively)

B.1.5.4 Row Alarm Connector

Row Alarm Connector controls the alarm condition indicators on an end panel at the end of a set of the frames.

J27 on Control Shelf backplane 04 and J34 on Control Shelf backplane 06/07

Figure B-12 Row Alarm Connector

img/r_row_alarm_connector_im-fig1.jpg

Table B-10 Row Alarm Connector

Pin Signal

1, 2, 3, 6, 7, 8, 9, 13, 14, 15

Not used

4

–48VDC

5

RACRNC - Row Alarm, Critical, Normally Closed

10

RAMNNO - Row Alarm, Minor, Normally Open

11

RAMJNO - Row Alarm, Major, Normally Open

12

48VDC return

B.1.5.5 External Alarm Connector

External Alarm Connector is also used for alarm condition inputs from an optional holdover clock.

J28 on Control Shelf backplane 04 External Alarm J35 on Control Shelf backplane 06/07 CUST ALM 1 J66 on Control Shelf backplane 06/07 CUST ALM 2 (not supported by software)

Figure B-13 External Alarm Connector


img/r_external_alarm_connector_im-fig1.jpg

Table B-11 External Alarm Connector

Pin Signal Description

2

CUFA13

Signals a customer defined trouble #13 to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

3

CUFA14

Signals a customer defined trouble #14 to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

4

CUFA3

Signals a customer defined critical alarm (trouble #3) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

5

CUFA1

Reserved

6

CUFA9

Reserved

7

CUFA2

Signals a holdover clock critical alarm to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

8

CUFA4

Signals a customer defined critical alarm (trouble #4) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

9

CUFA10

Signals a holdover clock minor alarm to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

10

P5A48RTN

Signal return path

11

P4B48RTN

Signal return path

19

CUFA8

Signals customer defined major alarm (trouble #8) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

20

CUFA16

Signals a customer defined trouble #16 to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

21

CUFA7

Signals a customer defined major alarm (trouble #7) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

22

CUFA15

Signals a customer defined trouble #15 to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

23

CUFA12

Signals a customer defined minor alarm (trouble #12) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

24

CUFA6

Signals a holdover clock major alarm to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

25

CUFA5

Reserved

26

CUFA11

Signals a customer defined minor alarm (trouble #11) to the system when connected to P5A48RTN (pin 10) or P4B48RTN (pin 11).

B.1.5.6 OAP Alarm Connector

The OAP alarm connector controls the alarm condition indicators on an OAP frame.

J74 on Control Shelf backplane 04 and J69 on Control Shelf backplane 06/07

Figure B-14 OAP Alarm Connector

img/c_oap_alarm_connector_im-fig1.jpg

Table B-12 OAP Alarm Connector

Pin Signal

1, 2, 6, 7, 13, 14

Not used

3

OAPMNNC - OAP Alarm, Minor, Normally Closed

4

OAPMJNC - OAP Alarm, Major, Normally Closed

5

OAPCRNC - OAP Alarm, Critical, Normally Closed

8

OAPFA+ - OAP Fuse Alarm (+)*

9

OAPBNO - OAP Alarm, busy, Normally Open*

10

OAPMNNO - OAP Alarm, minor, normally Open

11

OAPMJNO - OAP Alarm, Major, Normally Open

12

OAPCOM - OAP Alarm, Common

15

OAPFA- - Row Fuse Alarm (-)*

* not currently supported

B.1.6 System Clock Connectors

The control shelf backplane provides system clock output to the rest of the system from the TDMs. Redundancy is accomplished by allowing TDM A and TDM B to distribute clocks independently of each other.

B.1.6.1 A Clock 0 through A Clock 5

J7, J14, J15, J56, J57, J63 on Control Shelf backplane 04 and J7, J21, J20, J64, J65, J72 on Control Shelf backplane 06/07

Figure B-15 A Clock 0 Through A Clock 5 Connectors


img/r_a_clock_0_through_a_clock_5_im-fig1.jpg

Table B-13 A Clock 0 Through A Clock 5 Connectors

Connector Pin Signal Pin Signal Pin Signal Pin Signal

850-0330-04

J7

(CF00)

(rack 0)

850-0330-06/07

J7

1

 

8

MBUS1RX-_50

15

A56KHZ0-_50

22

A56KHZ2+_50

2

MBUS0TX-_50

9

MBUS1RX+_50

16

A8KHZ0+_50

23

A56KHZ2-_50

3

MBUS0TX+_50

10

MBUS2TX-_50

17

A8KHZ0-_50

24

A8KHZ2+_50

4

MBUS0RX-_50

11

MBUS2TX+_50

18

A56KHZ1+_50

25

A8KHZ2-_50

5

MBUS0RX+_50

12

MBUS2RX-_50

19

A56KHZ1-_50

   

6

MBUS1TX-_50

13

MBUS2RX+_50

20

A8KHZ1+_50

   

7

MBUS1TX+_50

14

A56KHZ0+_50

21

A8KHZ1-_50

   

850-0330-06/07

J64, J65, J72

not currently supported

B.1.6.2 B Clock 0 through B Clock 5

J6, J12, J13, J54, J55, J62 on Control Shelf backplane 04 and J3, J16, J18, J62, J63, J70 on Control Shelf backplane 06/07

Figure B-16 B Clock 0 through B Clock 5 Connectors


img/r_b_clock_0_through_b_clock_5_im-fig1.jpg

Table B-14 B Clock 0 through B Clock 5 Connectors

Connector Pin Signal Pin Signal Pin Signal Pin Signal

850-0330-03

J6

(CF00)

(rack 0)

850-0330-06/07

J3

1

R0FAALM-

8

 

15

B56KHZ0-_50

22

B56KHZ2+_50

2

 

9

 

16

B8KHZ0+_50

23

B56KHZ2-_50

3

 

10

 

17

B8KHZ0-_50

24

B8KHZ2+_50

4

 

11

 

18

B56KHZ1+_50

25

B8KHZ2-_50

5

 

12

 

19

B56KHZ1-_50

   

6

 

13

R0FBALM-

20

B8KHZ1+_50

   

7

R0FANCTRL

14

B56KHZ0+_50

21

B8KHZ1-_50

   

850-0330-06/07

J62, J63, J70

not currently supported

B.1.7 Shelf Clock Connectors (for Control Shelf Backplane -04 only)

Connectors for both A and B clocks are provided using 25 pin D type connectors at J9, J10, J59, and J60 on Control Shelf backplane 04.

System clock connectors are used on Control Shelf backplane 06/07.

B.1.7.1 Clock A In Connector

J9 on backplane (P/N 850-0330-04).

Figure B-17 Clock A In Connector on Backplane

img/r_clock_a_in_connector_im-fig1.jpg

Table B-15 Clock A In Connector on Control Shelf Backplane 04

Pin Signal Pin Signal

1

 

14

MA56KHZ+_50

2

MBUSSTX-_50

15

MA56KHZ-_50

3

MBUSSTX+_50

16

MA8KHZ+_50

4

MBUSSRX-_50

17

MA8KHZ-_50

5

MBUSSRX+_50

18

SH2A56KHZ+_50

6

SH2MBUSTX-_50

19

SH2A56KHZ-_50

7

SH2MBUSTX+_50

20

SH2A8KHZ+_50

8

SH2MBUSRX-_50

21

SH2A8KHZ-_50

9

SH2MBUSRX+_50

22

SH3A56KHZ+_50

10

SH3MBUSTX-_50

23

SH3A56KHZ-_50

11

SH3MBUSTX-_50

24

SH3A8KHZ+_50

12

SH3MBUSRX-_50

25

SH3A8KHZ-_50

13

SH3MBUSRX+_50

   
B.1.7.2 Clock A Out Connector

J10 on Control Shelf backplane 04.

Figure B-18 Clock A Out Connector

img/r_clock_a_out_connector_im-fig1.jpg

Table B-16 Clock A Out Connector

Pin Signal Pin Signal

1

 

14

SH2A56KHZ+_50

2

SH2MBUSTX-_50

15

SH2A56KHZ-_50

3

SH2MBUSTX+_50

16

SH2A8KHZ+_50

4

SH2MBUSRX-_50

17

SH2A8KHZ-_50

5

SH2MBUSRX+_50

18

SH3A56KHZ+_50

6

SH3MBUSTX-_50

19

SH3A56KHZ-_50

7

SH3MBUSTX+_50

20

SH3A8KHZ+_50

8

SH3MBUSRX-_50

21

SH3A8KHZ-_50

9

SH3MBUSRX+_50

22

 

10

 

23

 

11

 

24

 

12

 

25

 

13

     
B.1.7.3 Clock B In Connector

J59 on Control Shelf backplane 04

Figure B-19 Clock B In Connector on Backplane

img/r_clock_b_in_connector_im-fig1.jpg

Table B-17 Clock B In Connector on Control Shelf backplane 04

Pin Signal Pin Signal

1

FANAALM-

14

MB56KHZ+_50

2

 

15

MB56KHZ-_50

3

 

16

MB8KHZ+_50

4

 

17

MB8KHZ-_50

5

 

18

SH2B56KHZ+_50

6

 

19

SH2B56KHZ-_50

7

FANCNTRL

20

SH2B8KHZ+_50

8

 

21

SH2B8KHZ-_50

9

 

22

SH3B56KHZ+_50

10

 

23

SH3B56KHZ-_50

11

 

24

SH3B8KHZ+_50

12

 

25

SH3B8KHZ-_50

13

FANBALM-

   
B.1.7.4 Clock B Out Connector

J60 on Control Shelf backplane 04.

Figure B-20 Clock B Out Connector on Backplane

img/r_clock_b_out_connector_im-fig1.jpg

Table B-18 Clock B Out Connector on Control Shelf backplane 04

Pin Signal Pin Signal

1

FANAALM-

14

SH2B56KHZ+_50

2

 

15

SH2B56KHZ-_50

3

 

16

SH2B8KHZ+_50

4

 

17

SH2B8KHZ-_50

5

 

18

SH3B56KHZ+_50

6

 

19

SH3B56KHZ-_50

7

FANCNTRL

20

SH3B8KHZ+_50

8

 

21

SH3B8KHZ-_50

9

 

22

 

10

 

23

 

11

 

24

 

12

 

25

 

13

FANBALM-

   

B.1.8 BITS Clock Connectors

The system connects to the Building Integrated Timing System (BITS) clocks using two DB-15 style connectors. The two clocks are labeled Primary and Secondary and are supplied from the central office clock. Both clocks go to both TDMs, where one is selected to provide the system clocks used to provide system timing.

J41, J42 on Control Shelf backplane 04 and J48, J49 on Control Shelf backplane 06/07

Figure B-21 BITS Clock Connector

img/r_bits_clock_connectors_im-fig1.jpg

Table B-19 BITS Clock Connector

Pin Signal Pin Signal

1

 

9

 

2

 

10

 

3

 

11

 

4

 

12

$BITSIN-_60

5

$BITSIN+_60

13

 

6

 

14

 

7

 

15

 

8

     

$= P for primary BITS clock (J42), S for secondary BITS clock (J41)

B.1.9 Serial Port Connectors

The control shelf backplane provides an interface for 16 separate serial port connections from the TDMs. These connections provide RS-232 interfaces for terminals, printers, and modems. The system is set up as Data Terminal Equipment (DTE).

J17 - J24, J65 - J72 on Control Shelf backplane 04 and J24 - J31, J76 - J83 on Control Shelf backplane 06/07

Figure B-22 Serial Port Connector

img/r_serial_port_connectors_im-fig1.jpg

Table B-20 Serial Port Connector

Pin Signal Pin Signal

1

 

9

 

2

 

10

 

3

DCD$

11

 

4

RX$

12

 

5

TX$

13

CTS$

6

DTR$

14

RTS$

7

logic ground

15

 

8

     

$= 0 through 15, MMI0 through MMI15 respectively, J17 through J24 and J65 through J72 respectively

B.1.10 Interface Connectors

For slots 1 through 8, 11, and 12 on the control shelf backplane, there are two associated DB-26 interface connectors for each slot. These provide interfacing to the outside world in the form of Ethernet networks or SS7 links networks.

J29 - J38, J43 - J52 on Control Shelf backplane 04 and J36 - J45, J50 - J59 on Control Shelf backplane 06/07

Figure B-23 Interface Connector


img/r_interface_connectors_im-fig1.jpg

Table B-21 Interface Connector Pins and Signal

DB-26 Pin DS0A/ OCU Signal DB-26 Pin DS0A/OCU Signal ATM

1

 

14

 

2

 

15

 

3

 

16

 

4

 

17

 

5

 

18

 

6

 

19

 

7

 

20

TX-RING

8

 

21

TX-TIP

9

 

22

RX-RING

10

 

23

RX-TIP

11

 

24

 

12

 

25

 

13

 

26

 

Table B-22 Interface Connectors, Ports, and Card Slots

Card slot Port Connector Port Connector

01

1A

J38

1B

J52

02

2A

J37

2B

J51

03

3A

J36

3B

J50

04

4A

J35

4B

J49

05

5A

J34

5B

J48

06

6A

J33

6B

J47

07

7A

J32

7B

J46

08

8A

J31

8B

J45

11

9A

J30

9B

J44

12

10A

J29

10B

J43

B.1.10.1 Control Shelf Modules

This section details the backplane circuit board connectors used for

  • Link Interface Module (LIM)
  • E5 Interface Modules
  • E5-TSM Modules
  • E5-STC Modules
  • E5-IPSM Modules
  • E5-MCPM-B Modules

Control Shelf Backplane top connectors are P6, P7, and P9 through P16; bottom connectors are P22, P23, and P25 through P32.

B.1.10.1.1 Control Shelf Backplane Pin-Outs, Top Connector

Table B-23 lists pinouts for connectors P6, P7, and P9 through P16 on the control shelf.

Refer to Table B-25 for signal symbol values ($, #, &, @, and ^).

Figure B-24 Control Shelf Backplane Pin-Outs, Top Connector


img/r_pin_outs_top_connector_im-fig1.jpg

Table B-23 Control Shelf Backplane Pin-Outs, Top Connector

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LGND

B01

LGND

C01

LGND

D01

LGND

A02

ASEROD-_50

B02

LGND

C02

ASEROE-_50

D02

LGND

A03

ASEROD+_50

B03

LGND

C03

ASEROE+_50

D03

LGND

A04

LGND

B04

ASELD-

C04

LGND

D04

ASELE-

A05

ASERID-_50

B05

LGND

C05

ASERIE-_50

D05

LGND

A06

ASERID+_50

B06

LGND

C06

ASERIE+_50

D06

LGND

A07

LGND

B07

AIND-

C07

LGND

D07

AINE-

A08

ASEROC-_50

B08

LGND

C08

ASEROF-_50

D08

LGND

A09

ASEROC+_50

B09

LGND

C09

ASEROF+_50

D09

LGND

A10

ABMUXIN-

B10

ASELC-

C10

LGND

D10

ASELF-

A11

ASERIC-_50

B11

LGND

C11

ASERIF-_50

D11

LGND

A12

ASERIC+_50

B12

LGND

C12

ASERIF+_50

D12

LGND

A13

LGND

B13

AINC-

C13

LGND

D13

AINF-

A14

ASEROB-_50

B14

LGND

C14

ASEROG-_50

D14

LGND

A15

ASEROB+_50

B15

LGND

C15

ASEROG+_50

D15

LGND

A16

LGND

B16

ASELB-

C16

LGND

D16

ASELG-

A17

ASERIB-_50

B17

LGND

C17

ASERIG-_50

D17

LGND

A18

ASERIB+_50

B18

LGND

C18

ASERIG+_50

D18

LGND

A19

LGND

B19

AINB-

C19

LGND

D19

AING-

A20

 

B20

LGND

C20

ASEROH-_50

D20

LGND

A21

 

B21

LGND

C21

ASEROH+_50

D21

LGND

A22

LGND

B22

 

C22

LGND

D22

ASELH-

A23

 

B23

LGND

C23

ASERIH-_50

D23

LGND

A24

 

B24

LGND

C24

ASERIH+_50

D24

LGND

A25

LGND

B25

 

C25

LGND

D25

AINH-

A26

ASEROA-_50

B26

LGND

C26

ASEROI-_50

D26

LGND

A27

ASEROA+_50

B27

LGND

C27

ASEROI+_50

D27

LGND

A28

LGND

B28

ASELA-

C28

LGND

D28

ASELI-

A29

ASERIA-_50

B29

LGND

C29

ASERII-_50

D29

LGND

A30

ASERIA+_50

B30

LGND

C30

ASERII+_50

D30

LGND

A31

LGND

B31

AINA-

C31

LGND

D31

AINI-

A32

 

B32

LGND

C32

ASEROJ-_50

D32

LGND

A33

 

B33

LGND

C33

ASEROJ+_50

D33

LGND

A34

LGND

B34

 

C34

LGND

D34

ASELJ-

A35

 

B35

LGND

C35

ASERIJ-_50

D35

LGND

A36

 

B36

LGND

C36

ASERIJ+_50

D36

LGND

A37

LGND

B37

 

C37

LGND

D37

AINJ-

A38

 

B38

LGND

C38

ASEROK-_50

D38

LGND

A39

 

B39

LGND

C39

ASEROK+_50

D39

LGND

A40

LGND

B40

 

C40

LGND

D40

ASELK-

A41

 

B41

LGND

C41

ASERIK-_50

D41

LGND

A42

 

B42

LGND

C42

ASERIK+_50

D42

LGND

A43

LGND

B43

 

C43

LGND

D43

AINK-

A44

 

B44

LGND

C44

ASEROL-_50

D44

LGND

A45

 

B45

LGND

C45

ASEROL+_50

D45

LGND

A46

LGND

B46

 

C46

LGND

D46

ASELL-

A47

 

B47

LGND

C47

ASERIL-_50

D47

LGND

A48

 

B48

LGND

C48

ASERIL+_50

D48

LGND

A49

LGND

B49

 

C49

LGND

D49

AINL-

A50

AIN-_78

B50

LGND

C50

AIMTOUT-_78

D50

LGND

A51

AIMTIN+_78

B51

LGND

C51

AIMTOUT+_78

D51

LGND

A52

LGND

B52

LGND

C52

LGND

D52

LGND

A53

 

B53

MBUSSRX-_50

C53

MBUSSRX+_50

D53

 

A54

 

B54

MBUSSTX-_50

C54

MBUSSTX+_50

D54

LGND

A55

CHASSIS GND

B55

CHASSIS GND

C55

CHASSIS GND

D55

CHASSIS GND

E2

P3A48RTN

B.1.10.1.2 Control Shelf Backplane Pin-Outs, Bottom Connector

Table B-24 Pinouts for DCM/DSM/LIM/MPL/TSM Control Shelf Backplane bottom connectors P22, P23, and P25 through P32

Figure B-25 Control Shelf Backplane Pin-Outs, Bottom Connector


img/r_pin_outs_bottom_connector_im-fig1.jpg

Table B-24 Control Shelf Backplane Pin-Outs, Bottom Connector

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LGND

B01

&-IF1_60

C01

&-IF10_60

D01

IN2-

A02

&-IF3_60

B02

&-IF2_60

C02

&-IF19_60

D02

LGND

A03

LGND

B03

 

C03

&-IF20_60

D03

LGND

A04

&-IF4_60

B04

 

C04

&-IF21_60

D04

LGND

A05

&-IF5_60

B05

 

C05

&-IF22_60

D05

LGND

A06

&-IF6_60

B06

&-IF24_60

C06

&-IF23_60

D06

LGND

A07

&-IF7_60

B07

&-IF26_60

C07

 

D07

@-IF25_60

A08

&-IF8_60

B08

&-IF9_60

C08

&-IF18_60

D08

LGND

A09

LGND

B09

 

C09

 

D09

LGND

A10

 

B10

 

C10

EBI_^XSP2

D10

EBI_^XSP3

A11

LGND

B11

LGND

C11

EBI_^XBE0-

D11

EBI_^XD00

A12

BSERO@-_50

B12

LGND

C12

EBI_^XBE1-

D12

EBI_^XD01

A13

BSERO@-_50

B13

LGND

C13

EBI_^XBE2-

D13

EBI_^XD02

A14

LGND

B14

LGND

C14

EBI_^XBE3-

D14

EBI_^XD03

A15

 

B15

LGND

C15

EBI_^XBS8-

D15

EBI_^XD04

A16

 

B16

LGND

C16

EBI_^XBS16-

D16

EBI_^XD05

A17

LGND

B17

LGND

C17

EBI_^ADS0-

D17

EBI_^XD06

A18

BSEL@-

B18

 

C18

EBI_^ADS1-

D18

EBI_^XD07

A19

 

B19

 

C19

EBI_^XW/R

D19

EBI_^XD08

A20

BMUXIN-

B20

 

C20

EBI_^XM/IO

D20

EBI_^XD09

A21

LGND

B21

BIN@-

C21

EBI_^XSP1

D21

EBI_^XD10

A22

 

B22

LGND

C22

EBI_^XINTA-

D22

EBI_^XD11

A23

 

B23

LGND

C23

EBI_^XRDY-

D23

EBI_^XD12

A24

LGND

B24

LGND

C24

EBI_^XCAS0-

D24

EBI_^XD13

A25

BSERI@-_50

B25

LGND

C25

EBI_^XCAS1-

D25

EBI_^XD14

A26

BSERI@+_50

B26

LGND

C26

EBI_^XCAS2-

D26

EBI_^XD15

A27

LGND

B27

LGND

C27

 

D27

 

A28

 

B28

 

C28

 

D28

LGND

A29

LGND

B29

 

C29

 

D29

 

A30

 

B30

 

C30

 

D30

LGND

A31

LGND

B31

 

C31

MB56KHZ+_50

D31

 

A32

 

B32

 

C32

MB56KHZ-_50

D32

LGND

A33

LGND

B33

 

C33

MB8KHZ+_50

D33

 

A34

 

B34

 

C34

MB8KHZ-_50

D34

LGND

A35

CHASSIS GND

B35

CHASSIS GND

C35

CHASSIS GND

D35

CHASSIS GND

B.1.10.1.3 Control Shelf Backplane Pin-Out Symbols

Table B-25 lists the signal symbol values used in Table B-23 through Table B-43.

Table B-25 Backplane Pin-Out Symbols

Slot/Connector Interface Port Address Signal Symbol Values
$ # & @ ^

1 top / P16

0A

0

1A

L

0A

 

0

1 bottom / P32

0B

0

1A

 

0B

A

0

2 top / P15

1A

1

1A

K

1A

 

0

2 bottom / P31

1B

1

1A

 

1B

B

0

3 top / P14

2A

2

1B

J

2A

 

2

3 bottom / P30

2B

2

1B

 

2B

C

2

4 top / P13

3A

3

1B

I

3A

 

2

4 bottom / P29

3B

3

1B

 

3B

D

2

5 top / P12

4A

4

2A

H

4A

 

4

5 bottom / P28

4B

4

2A

 

4B

E

4

6 top / P11

5A

5

2A

G

5A

 

4

6 bottom / P27

5B

5

2A

 

5B

F

4

7 top / P10

6A

6

2B

F

6A

 

6

7 bottom / P26

6B

6

2B

 

6B

G

6

8 top / P9

7A

7

2B

E

7A

 

6

8 bottom / P25

7B

7

2B

 

7B

H

6

11 top/P7

8A

8

4A

D

8A

 

8

11 bottom/P23

8B

8

4A

 

8B

I

8

12 top/P6

9A

9

4A

C

9A

 

8

12 bottom/P22

9B

9

4A

 

9B

J

8

B.1.10.2 Maintenance Disk and Alarm Connector
B.1.10.2.1 MDAL Pin-Outs, Top Connector

Table B-26Table B-26 lists pinouts for connectors P1on the control shelf.

Figure B-26 Maintenance Disk and Alarm Connector, Top


img/r_pin_outs_top_connector_1_im-fig1.jpg

Table B-26 MDAL Backplane, Top

Pin Signal Pin Signal Pin Signal Pin Signal

A01

BALMEN0-

B01

BALMD0-

C01

 

D01

LGND

A02

BALMEN1-

B02

BALMD1-

C02

LGND

D02

LGND

A03

BALMEN2-

B03

BALMD2-

C03

LGND

D03

 

A04

BALMEN3-

B04

BALMD3-

C04

LGND

D04

 

A05

BALMEN4-

B05

BALMD4-

C05

 

D05

LGND

A06

BALMCK-

B06

BALMD5-

C06

 

D06

 

A07

BALMD7-

B07

BALMD6-

C07

R0CRNC

D07

LGND

A08

R0FANCTRL

B08

LGND

C08

R0MJNC

D08

R0COM

A09

AALMEN0-

B09

AALMD0-

C09

R0MNNC

D09

R0MJNO

A10

AALMEN1-

B10

AALMD1-

C10

R0BNC

D10

R0MNNO

A11

AALMEN2-

B11

AALMD2-

C11

 

D11

R0BNO

A12

AALMEN3-

B12

AALMD3-

C12

LGND

D12

LGND

A13

AALMEN4-

B13

AALMD4-

C13

 

D13

LGND

A14

AALMCK-

B14

AALMD5-

C14

LGND

D14

LGND

A15

AALMD7-

B15

AALMD6-

C15

 

D15

LGND

A16

CHASSIS GND

B16

CHASSIS GND

C16

CHASSIS GND

D16

CHASSIS GND

A17

 

B17

LGND

C17

 

D17

 

A18

LGND

B18

LGND

C18

LGND

D18

 

A19

LGND

B19

LGND

C19

 

D19

 

A20

R0FBALM-

B20

 

C20

R1FBALM-

D20

 

A21

R0FAALM-

B21

LGND

C21

R1FAALM-

D21

 

A22

LGND

B22

R2FBALM-

C22

 

D22

 

A23

LGND

B23

R2FAALM-

C23

R1CRNC

D23

R1COM

A24

LGND

B24

 

C24

R1MJNC

D24

R1MJNO

A25

R1FANCTRL

B25

LGND

C25

R1MNNC

D25

R1MNNO

A26

R2FANCTRL

B26

LGND

C26

R1BNC

D26

R1BNO

A27

LGND

B27

 

C27

 

D27

 

A28

RACRNC

B28

RACOM

C28

R2CRNC

D28

R2COM

A29

RAMJNC

B29

RAMJNO

C29

R2MJNC

D29

R2MJNO

A30

RAMNNC

B30

RAMNNO

C30

R2MNNC

D30

R2MNNO

A31

RABNC

B31

RABNO

C31

R2BNC

D31

R2BNO

A32

RMCANC

B32

 

C32

 

D32

LGND

A33

RMCBNC

B33

 

C33

LGND

D33

RMCANO

A34

RMCMJNC

B34

RMCMNNC

C34

RMCCOM

D34

RMCBNO

A35

RMCCRNC

B35

 

C35

RMCMNNO

D35

RMCMJNO

E2

LGND

           
B.1.10.2.2 MDAL Pin-Outs, Bottom Connector

Table B-27 lists pinouts of the bottom connector P17 on the control shelf.

Figure B-27 MDAL Backplane, Bottom


img/r_pin_outs_bottom_connector_1_im-fig1.jpg

Table B-27 MDAL Backplane, Bottom

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LMCANO

B01

 

C01

LMCACOM

D01

LMCANC

A02

LMCVMJNC

B02

 

C02

 

D02

LMCVCOM

A03

LMCVCRNC

B03

LMCVMNNC

C03

LMCVMJNO

D03

LMCVMNNO

A04

R3FANCTRL

B04

 

C04

LGND

D04

 

A05

R4FANCTRL

B05

R4FBALM-

C05

R3CRNC

D05

R3COM

A06

 

B06

R4FAALM-

C06

R3MJNC

D06

R3MJNO

A07

R3FBALM-

B07

 

C07

R3MNNC

D07

R3MNNO

A08

R3FAALM-

B08

 

C08

R3BNC

D08

R3BNO

A09

LGND

B09

LGND

C09

 

D09

LGND

A10

 

B10

 

C10

R4CRNC

D10

R4COM

A11

LGND

B11

LGND

C11

R4MJNC

D11

R4MJNO

A12

 

B12

 

C12

R4MNNC

D12

R4MNNO

A13

LGND

B13

LGND

C13

R4CRNC

D13

R4BNO

A14

 

B14

 

C14

 

D14

 

A15

TPWR

B15

LGND

C15

 

D15

 

A16

AUDCTOFF-

B16

 

C16

LGND

D16

 

A17

ALMTRANS-

B17

LGND

C17

R5FBALM-

D17

 

A18

AMS/BMS-

B18

SDB0-_100

C18

R5FAALM-

D18

 

A19

MASBSAN-

B19

SDB1-_100

C19

 

D19

 

A20

MASASAN-

B20

SDB2-_100

C20

 

D20

 

A21

LGND

B21

SDB3-_100

C21

 

D21

LGND

A22

 

B22

SDB4-_100

C22

 

D22

 

A23

 

B23

SDB5-_100

C23

 

D23

 

A24

 

B24

SDB6-_100

C24

 

D24

 

A25

 

B25

SDB7-_100

C25

 

D25

 

A26

 

B26

SDBP-_100

C26

 

D26

 

A27

 

B27

SBSY-_100

C27

 

D27

 

A28

 

B28

SATN-_100

C28

R5CRNC

D28

R5COM

A29

 

B29

SACK-_100

C29

R5MJNC

D29

R5MJNO

A30

LGND

B30

SRST-_100

C30

R5MNNC

D30

R5MNNO

A31

LGND

B31

SMSG-_100

C31

R5CRNC

D31

R5BNO

A32

R5FANCTRL

B32

SSEL-_100

C32

 

D32

 

A33

 

B33

SI/O-_100

C33

 

D33

 

A34

 

B34

SC/D-_100

C34

 

D34

 

A35

LGND

B35

SREQ-_100

C35

 

D35

 

E2

P5B48RTN

           
B.1.10.3 Terminal Disk Module

Terminal Disk Module P2, P4, P18, P20

B.1.10.3.1 TDM Pin-Outs, Top Connectors

TDM, Top Connectors P2, P4

Figure B-28 TDM, Top


img/r_pin_outs_top_connectors_im-fig1.jpg

Table B-28 TDM Backplane, Top

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LGND

B01

R0FA+

C01

$ALMEN0-

D01

$ALMD0-

A02

LGND

B02

R0FA-

C02

$ALMEN1-

D02

$ALMD1-

A03

CUFA1

B03

 

C03

$ALMEN2-

D03

$ALMD2-

A04

CUFA2

B04

LGND

C04

$ALMEN3-

D04

$ALMD3-

A05

MBUS2RX+_50

B05

LGND

C05

$ALMEN4-

D05

$ALMD4-

A06

MBUS2RX-_50

B06

$8KHZ2-_50

C06

$ALMCK-

D06

$ALMD5-

A07

MBUS2TX+_50

B07

$8KHZ2+_50

C07

$ALMD7-

D07

$ALMD6-

A08

MBUS2TX-_50

B08

$56KHZ2-_50

C08

EBI_$XA02

D08

EBI_$XA14

A09

MBUS1RX+_50

B09

$56KHZ2+_50

C09

EBI_$XA03

D09

EBI_$XA15

A10

MBUS1RX-_50

B10

$8KHZ1-_50

C10

EBI_$XA04

D10

EBI_$XA16

A11

MBUS1TX+_50

B11

$8KHZ1+_50

C11

EBI_$XA05

D11

EBI_$XA17

A12

MBUS1TX-_50

B12

$56KHZ1-_50

C12

EBI_$XA06

D12

EBI_$XA18

A13

MBUS0RX+_50

B13

$56KHZ1+_50

C13

EBI_$XA07

D13

EBI_$XA19

A14

MBUS0RX-_50

B14

$8KHZ0-_50

C14

EBI_$XA08

D14

EBI_$XA20

A15

MBUS0TX+_50

B15

$8KHZ0+_50

C15

EBI_$XA09

D15

EBI_$XA21

A16

MBUS0TX-_50

B16

$56KHZ0-_50

C16

EBI_$XA10

D16

EBI_$XA22

A17

 

B17

$56KHZ0+_50

C17

CUFA13

D17

EBI_$XA23

A18

LGND

B18

 

C18

CUFA14

D18

EBI_$XA24

A19

CUFA3

B19

CUFA9

C19

HST/GST

D19

EBI_$XA25

A20

CUFA4

B20

CUFA10

C20

 

D20

EBI_$XA26

A21

LGND

B21

LGND

C21

LGND

D21

EBI_$XA27

A22

CUFA5

B22

CUFA11

C22

 

D22

MBUS8RX+_50

A23

CUFA6

B23

CUFA12

C23

LGND

D23

$8KHZ8-_50

A24

LGND

B24

LGND

C24

CUFA15

D24

MBUS8RX-_50

A25

CUFA7

B25

LGND

C25

CUFA16

D25

$8KHZ8+_50

A26

CUFA8

B26

LGND

C26

MBUS8TX+_50

D26

$56KHZ8-_50

A27

LGND

B27

 

C27

MBUS8TX-_50

D27

$56KHZ8+_50

A28

EBI_$XSP5

B28

R1FA+

C28

MBUS7RX+_50

D28

$8KHZ7-_50

A29

EBI_$XSP4

B29

R1FA-

C29

MBUS7RX-_50

D29

$8KHZ7+_50

A30

EBI_$XA11

B30

EBI_$XA12

C30

MBUS7TX+_50

D30

$56KHZ7-_50

A31

EBI_$XA13

B31

EBI_$BREQ-

C31

MBUS7TX-_50

D31

$56KHZ7+_50

A32

EBI_$BG-

B32

EBI_$XIRQ-

C32

MBUS6RX+_50

D32

$8KHZ6-_50

A33

EBI_$HOSTSAN-

B33

EBI_$GSTSAN-

C33

MBUS6RX-_50

D33

$8KHZ6+_50

A34

MBUS5RX+_50

B34

$8KHZ5-_50

C34

MBUS6TX+_50

D34

$56KHZ6-_50

A35

MBUS5RX-_50

B35

$8KHZ5+_50

C35

MBUS6TX-_50

D35

$56KHZ6+_50

A36

MBUS5TX+_50

B36

$56KHZ5-_50

C36

RTS0

D36

RTS4

A37

MBUS5TX-_50

B37

$56KHZ5+_50

C37

CTS0

D37

CTS4

A38

MBUS4RX+_50

B38

$8KHZ4-_50

C38

TX0

D38

TX4

A39

MBUS4RX-_50

B39

$8KHZ4+_50

C39

RX0

D39

RX4

A40

MBUS4TX+_50

B40

$56KHZ4-_50

C40

DCD0

D40

DCD4

A41

MBUS4TX-_50

B41

$56KHZ4+_50

C41

RTS1

D41

RTS5

A42

MBUS3RX+_50

B42

$8KHZ3-_50

C42

CTS1

D42

CTS5

A43

MBUS3RX-_50

B43

$8KHZ3+_50

C43

TX1

D43

TX5

A44

MBUS3TX+_50

B44

$56KHZ3-_50

C44

RX1

D44

RX5

A45

MBUS3TX-_50

B45

$56KHZ3+_50

C45

DCD1

D45

DCD5

A46

 

B46

 

C46

RTS2

D46

RTS6

A47

 

B47

 

C47

CTS2

D47

CTS6

A48

LGND

B48

LGND

C48

TX2

D48

TX6

A49

 

B49

LGND

C49

RX2

D49

RX6

A50

 

B50

 

C50

DCD2

D50

DCD6

A51

LGND

B51

LGND

C51

RTS3

D51

RTS7

A52

 

B52

 

C52

CTS3

D52

CTS7

A53

RAFA+

B53

 

C53

TX3

D53

TX7

A54

RAFA-

B54

R2FA+

C54

RX3

D54

RX7

A55

 

B55

R2FA-

C55

DCD3

D55

DCD7

E1

P#$48VDC

$= A or B, for TDM connectors P4 and P2 respectively

# = 4 or 5, for TDM connectors P4 and P2 respectively

E2

P#$48RTN

           
B.1.10.3.2 TDM Pin-Outs, Bottom Connector

TDM, Bottom Connectors P18, P20 Control Shelf Backplane

Figure B-29 TDM Backplane Pin-outs, Bottom


img/r_pin_outs_bottom_connector_2_im-fig1.jpg

Table B-29 TDM Backplane Pin-outs, Bottom

Pin Signal Pin Signal Pin Signal Pin Signal

A01

CHASSIS GND

B01

CHASSIS GND

C01

CHASSIS GND

D01

CHASSIS GND

A02

 

B02

 

C02

LGND

D02

 

A03

PBITSIN+_60

B03

LGND

C03

SBITSIN+_60

D03

LGND

A04

PBITSIN-_60

B04

 

C04

SBITSIN-_60

D04

 

A05

LGND

B05

LGND

C05

 

D05

 

A06

LGND

B06

 

C06

 

D06

SPARE1

A07

 

B07

LGND

C07

LGND

D07

R3FA+

A08

 

B08

 

C08

 

D08

R3FA-

A09

 

B09

 

C09

 

D09

R4FA+

A10

LGND

B10

LGND

C10

LGND

D10

R4FA-

A11

MBUS11RX+_50

B11

$8KHZ11-_50

C11

MBUS14RX+_50

D11

 

A12

MBUS11RX-_50

B12

$8KHZ11+_50

C12

MBUS14RX-_50

D12

$8KHZ14-_50

A13

MBUS11TX+_50

B13

$56KHZ11-_50

C13

MBUS14TX+_50

D13

$8KHZ14+_50

A14

MBUS11TX-_50

B14

$56KHZ11+_50

C14

MBUS14TX-_50

D14

$56KHZ14-_50

A15

 

B15

 

C15

MBUS13RX+_50

D15

$56KHZ14+_50

A16

MBUS10RX+_50

B16

$8KHZ10-_50

C16

MBUS13RX-_50

D16

$8KHZ13-_50

A17

MBUS10RX-_50

B17

$8KHZ10+_50

C17

MBUS13TX+_50

D17

$8KHZ13+_50

A18

MBUS10TX+_50

B18

$56KHZ10-_50

C18

MBUS13TX-_50

D18

$56KHZ13-_50

A19

MBUS10TX-_50

B19

$56KHZ10+_50

C19

MBUS12RX+_50

D19

$56KHZ13+_50

A20

MBUS9RX+_50

B20

$8KHZ9-_50

C20

MBUS12RX-_50

D20

$8KHZ12-_50

A21

MBUS9RX-_50

B21

$8KHZ9+_50

C21

MBUS12TX+_50

D21

$8KHZ12+_50

A22

MBUS9TX+_50

B22

$56KHZ9-_50

C22

MBUS12TX-_50

D22

$56KHZ12-_50

A23

MBUS9TX-_50

B23

$56KHZ9+_50

C23

 

D23

$56KHZ12+_50

A24

EBI_$XD00

B24

EBI_$XBE0-

C24

EBI_$XSP2

D24

EBI_$XSP3

A25

EBI_$XD01

B25

EBI_$XBE1-

C25

 

D25

LGND

A26

EBI_$XD02

B26

EBI_$XBE2-

C26

 

D26

 

A27

EBI_$XD03

B27

EBI_$XBE3-

C27

LGND

D27

SPARE2

A28

EBI_$XD04

B28

EBI_$XBS8-

C28

LGND

D28

TPWR

A29

EBI_$XD05

B29

EBI_$XBS16-

C29

 

D29

AUDCTOFF-

A30

EBI_$XD06

B30

EBI_$ADS0-

C30

 

D30

ALMTRANS-

A31

EBI_$XD07

B31

EBI_$ADS1-

C31

SDB0-_100

D31

AMS/BMS

A32

EBI_$XD08

B32

EBI_$XW/R

C32

SDB1-_100

D32

MASASAN-

A33

EBI_$XD09

B33

EBI_$XM/IO

C33

SDB2-_100

D33

MASBSAN-

A34

EBI_$XD10

B34

EBI_$XSP1

C34

SDB3-_100

D34

R5FA+

A35

EBI_$XD11

B35

EBI_$XINTA-

C35

LGND

D35

R5FA-

A36

EBI_$XD12

B36

EBI_$XRDY-

C36

RTS8

D36

RTS12

A37

EBI_$XD13

B37

EBI_$XCAS0-

C37

CTS8

D37

CTS12

A38

EBI_$XD14

B38

EBI_$XCAS1-

C38

TX8

D38

TX12

A39

EBI_$XD15

B39

EBI_$XCAS2-

C39

RX8

D39

RX12

A40

LGND

B40

 

C40

DCD8

D40

DCD12

A41

 

B41

 

C41

RTS9

D41

RTS13

A42

LGND

B42

SDB4-_100

C42

CTS9

D42

CTS13

A43

 

B43

SDB5-_100

C43

TX9

D43

TX13

A44

LGND

B44

SDB6-_100

C44

RX9

D44

RX13

A45

MBUS15RX+_50

B45

SDB7-_100

C45

DCD9

D45

DCD13

A46

$8KHZ15-_50

B46

SDBP-_100

C46

RTS10

D46

RTS14

A47

MBUS15RX-_50

B47

SBSY-_100

C47

CTS10

D47

CTS14

A48

$8KHZ15+_50

B48

SATN-_100

C48

TX10

D48

TX14

A49

MBUS15TX+_50

B49

SACK-_100

C49

RX10

D49

RX14

A50

$56KHZ15-_50

B50

SRST-_100

C50

DCD10

D50

DCD14

A51

MBUS15TX-_50

B51

SMSG-_100

C51

RTS11

D51

RTS15

A52

$56KHZ15+_50

B52

SSEL-_100

C52

CTS11

D52

CTS15

A53

+12VB

B53

SI/O-_100

C53

TX11

D53

TX15

A54

SIG GND

B54

SC/D-_100

C54

RX11

D54

RX15

A55

SIG GND

B55

SREQ-_100

C55

DCD11

D55

DCD15

B.1.11 Interprocessor Message Transport Connectors

Inter-processor Message Transport (IMT) connectors on the control shelf backplane provide connections between the system shelves as part of the two high speed IMT buses.

J8, J16, J58, J64 on Control Shelf backplane 04 and J23, J22, J75, J74 on Control Shelf backplane 06/07

Figure B-30 IMT Connector


img/r_interprocessor_message_transport_connectors_im-fig1.jpg

Table B-30 IMT Connector Pins

Connector Pin Signal

A IMT IN backplane (P/N 850-0330-04)(J8)

A IMT IN backplane (P/N 850-0330-06/07)(J23)

1

AIMTIN+_78

2

AIMTIN-_78

A IMT OUT backplane (P/N 850-0330-04)(J16)

A IMT OUT backplane (P/N 850-0330-06/07)(J22)

1

AIMTOUT+_78

2

AIMTOUT-_78

B IMT IN backplane (P/N 850-0330-04)(J58)

B IMT IN backplane (P/N 850-0330-06/07)(J75)

1

BIMTIN+_78

2

BIMTIN-_78

B IMT OUT backplane (P/N 850-0330-04)(J64)

B IMT OUT backplane (P/N 850-0330-06/07)(J74)

1

BIMTOUT+_78

2

BIMTOUT-_78

B.1.12 General Purpose Relay Connectors

General Purpose Relay connectors provide software controlled, general purpose outputs for the system. Currently, Generic Program (GP01) provides reset signals for any optional OAPs that may be present in the system.

B.1.12.1 GP01

J75 on Control Shelf backplane 04 and J71 on Control Shelf backplane 06/07

Figure B-31 General Purpose Relay Connector 01

img/r_gp01_im-fig1.jpg

Table B-31 General Purpose Relay Connector 01

Pin

Signal

4, 8, 10, 15

not used

1

GPRNO0 - General Purpose Relay 0, Normally Open

2

GPRCOM0 - General Purpose Relay 0, Common

3

GPRNC0 - General Purpose Relay 0, Normally Closed

5

GPRNO1 - General Purpose Relay 1, Normally Open

6

GPRCOM1 - General Purpose Relay 1, Common

7

GPRNC1 - General Purpose Relay 1, Normally Closed

9

Logic ground

11

OAP1_RST+ - OAP 1 reset, +

12

OAP1_RST- - OAP 1 reset, -

13

OAP2_RST+ - OAP 2 reset, +

14

OAP2_RST- - OAP 2 reset, -

B.1.12.2 GP02

J73 on Control Shelf backplane 04 and J75 on Control Shelf backplane 06/07

Figure B-32 General Purpose Relay Connector 02

img/r_gp02_im-fig1.jpg

Table B-32 General Purpose Relay Connector 02

Pin Signal

1, 2, 13, 14, 18, 25

not used

3

GPRNC2 - General Purpose Relay 2, Normally Closed

4

GPRCOM2 - General Purpose Relay 2, Common

5

GPRNO2 - General Purpose Relay 2, Normally Open

6

GPRNC2 - General Purpose Relay 3, Normally Closed

7

GPRCOM2 - General Purpose Relay 3, Common

8

GPRNO2 - General Purpose Relay 3, Normally Open

9

GPRNC2 - General Purpose Relay 4, Normally Closed

10

GPRCOM2 - General Purpose Relay 4, Common

11

GPRNO2 - General Purpose Relay 4, Normally Open

12

Logic ground

15

GPRNC2 - General Purpose Relay 5, Normally Closed

16

GPRCOM2 - General Purpose Relay 5, Common

17

GPRNO2 - General Purpose Relay 5, Normally Open

19

GPRNC2 - General Purpose Relay 6, Normally Closed

20

GPRCOM2 - General Purpose Relay 6, Common

21

GPRNO2 - General Purpose Relay 6, Normally Open

22

GPRNC2 - General Purpose Relay 7, Normally Closed

23

GPRCOM2 - General Purpose Relay 7, Common

24

GPRNO2 - General Purpose Relay 7, Normally Open

B.1.13 General Purpose Serial Interface Connectors

The General Purpose Serial Interface connector provides a General Purpose Serial Interfaces (GPSI) for the system. The GPSI also provides communications between an optional holdover clock system and the rest of the system.

J76 on Control Shelf backplane 04 and J73 on Control Shelf backplane 06/07

Figure B-33 General Purpose Serial Interface Connector 01, GPSI

img/r_general_purpose_serial_interface_connectors_im-fig1.jpg

Table B-33 General Purpose Serial Interface Connector 01, GPSI

Pin Signal

1, 2, 3, 8, 9, 10, 11, 12, 13, 14, 15

Not used

4

RX_HO - Holdover Clock Receive Data

5

TX_HO - Holdover Clock Transmit Data

6

DTR_HO - Holdover Clock Data Terminal Ready

7

Logic ground

B.2 Extension Shelf

The extension shelf backplane provides connectors for 18 circuit cards. These connectors are four column High Density Interconnect (HDI) male headers with shrouds of varying pin quantities depending on card position. The reverse or component side of the backplane contains DB style connectors for interfacing to the rest of the system.

  • Power connectors

  • System clock connectors

  • Interface connectors

  • IMT connectors

B.2.1 Extension Shelf Backplane 04

Figure B-34 Extension Shelf Backplane 04

img/r_extension_shelf_backplane_04_im-fig1.jpg

B.2.2 Power Connectors

The extension shelf backplane provides –48VDC power and return to all card positions. The power is divided into parts A and B and brought to the shelf from the Fuse and Alarm Panel (FAP) using two cables. The power connectors on the extension shelf backplane are DB-26 high density connectors with two pins per power connection to handle the current load.

J1, J4 on Extension Shelf backplane 01

J1, J4, Primary and J45, J46 Secondary on Extension Shelf backplane 03

Figure B-35 Power Connector


img/r_power_connectors_1_im-fig1.jpg

Table B-34 Power Connector

Pin Signal Pin Signal

1

P5$48VDC

14

LGND

2

P5$48RTN

15

P3$48RTN

3

P4$48VDC

16

P3$48VDC

4

P4$48RTN

17

P2$48RTN

5

LGND

18

P2$48VDC

6

P3$48RTN

19

P1$48RTN

7

P3$48VDC

20

P1$48RTN

8

P2$48RTN

21

P1$48VDC

9

P2$48VDC

22

P1$48VDC

10

P5$48VDC

23

PF$48RTN

11

P5$48RTN

24

PF$48RTN

12

P4$48VDC

25

PF$48VDC

13

P4$48RTN

26

PF$48VDC

$= A or B, A POWER (J4) or B POWER (J1)

B.2.3 System Clock Connectors

Each extension shelf receives and passes along Clock signals A (J5 and J6) and B (J41and J42).

B.2.3.1 Clock A In Connector J5

Figure B-36 Clock A In Extension Shelf Connector

img/r_clock_a_in_connector_j5_im-fig1.jpg

Table B-35 Clock A In Extension Shelf Connector

Pin Signal Pin Signal

1

 

14

MA56KHZ+_50

2

MBUSSTX-_50

15

MA56KHZ-_50

3

MBUSSTX+_50

16

MA8KHZ+_50

4

MBUSSRX-_50

17

MA8KHZ-_50

5

MBUSSRX+_50

18

SH2A56KHZ+_50

6

SH2MBUSTX-_50

19

SH2A56KHZ-_50

7

SH2MBUSTX+_50

20

SH2A8KHZ+_50

8

SH2MBUSRX-_50

21

SH2A8KHZ-_50

9

SH2MBUSRX+_50

22

SH3A56KHZ+_50

10

SH3MBUSTX-_50

23

SH3A56KHZ-_50

11

SH3MBUSTX-_50

24

SH3A8KHZ+_50

12

SH3MBUSRX-_50

25

SH3A8KHZ-_50

13

SH3MBUSRX+_50

   
B.2.3.2 Clock A Out Connector J6

Figure B-37 Clock A Out Extension Shelf Connector

img/r_clock_a_out_connector_j6_im-fig1.jpg

Table B-36 Clock A Out Extension Shelf Connector

Pin Signal Pin Signal

1

 

14

SH2A56KHZ+_50

2

SH2MBUSTX-_50

15

SH2A56KHZ-_50

3

SH2MBUSTX+_50

16

SH2A8KHZ+_50

4

SH2MBUSRX-_50

17

SH2A8KHZ-_50

5

SH2MBUSRX+_50

18

SH3A56KHZ+_50

6

SH3MBUSTX-_50

19

SH3A56KHZ-_50

7

SH3MBUSTX+_50

20

SH3A8KHZ+_50

8

SH3MBUSRX-_50

21

SH3A8KHZ-_50

9

SH3MBUSRX+_50

22

 

10

 

23

 

11

 

24

 

12

 

25

 

13

     
B.2.3.3 Clock B In Extension Shelf Connector J41

Figure B-38 Clock B In Extension Shelf Connector

img/r_clock_b_in_extension_shelf_connector_j41_im-fig1.jpg

Table B-37 Clock B In Extension Shelf Connector

Pin Number Signal Pin Number Signal

1

FANAALM-

14

MB56KHZ+_50

2

 

15

MB56KHZ-_50

3

 

16

MB8KHZ+_50

4

 

17

MB8KHZ-_50

5

 

18

SH2B56KHZ+_50

6

 

19

SH2B56KHZ-_50

7

FANCNTRL

20

SH2B8KHZ+_50

8

 

21

SH2B8KHZ-_50

9

 

22

SH3B56KHZ+_50

10

 

23

SH3B56KHZ-_50

11

 

24

SH3B8KHZ+_50

12

 

25

SH3B8KHZ-_50

13

FANBALM-

   
B.2.3.4 Clock B Out Extension Shelf Connector J42

Figure B-39 Clock B Out Extension Shelf Connector

img/r_clock_b_out_extension_shelf_connector_j42_im-fig1.jpg

Table B-38 Clock B Out Extension Shelf Connector

Pin Number Signal Pin Number Signal

1

FANAALM

14

SH2B56KHZ+_50

2

 

15

SH2B56KHZ-_50

3

 

16

SH2B8KHZ+_50

4

 

17

SH2B8KHZ-_50

5

 

18

SH3B56KHZ+_50

6

 

19

SH3B56KHZ-_50

7

FANCNTRL

20

SH3B8KHZ+_50

8

 

21

SH3B8KHZ-_50

9

 

22

 

10

 

23

 

11

 

24

 

12

 

25

 

13

FANBALM

   

B.2.4 Interface Connectors

Behind each slot on the extension shelf backplane are two DB-26 connectors. These provide connection to the outside world in the form of TCP/IP networks or SS7 links networks. The interface connectors are designated as J9 through J40.

Extension Shelf Interface Connectors J9 through J40

Figure B-40 Extension Shelf Interface Connector


img/r_interface_connectors_1_im-fig1.jpg

Table B-39 Extension Shelf Interface Connector Pins and Signals

Pin DS0A/OCU Signal ATM Pin DS0A/OCU Signal ATM

1

 

14

 

2

 

15

 

3

 

16

 

4

 

17

 

5

 

18

 

6

 

19

 

7

 

20

TX-RING

8

 

21

TX-TIP

9

 

22

RX-RING

10

 

23

RX-TIP

11

 

24

 

12

 

25

 

13

 

26

 

Table B-40 Connectors, Ports, and Card Slots

Card Slot Port Connector Port Connector

01

1A

J24

1B

J40

02

2A

J23

2B

J39

03

3A

J22

3B

J38

04

4A

J21

4B

J37

05

5A

J20

5B

J36

06

6A

J19

6B

J35

07

7A

J18

7B

J34

08

8A

J17

8B

J33

11

9A

J16

9B

J32

12

10A

J15

10B

J31

13

11A

J14

11B

J30

14

12A

J13

12B

J29

15

13A

J12

13B

J28

16

14A

J11

14B

J27

17

15A

J10

15B

J26

18

16A

J9

16B

J25

B.2.4.1 Extension Shelf Modules

This section details the Extension Shelf backplane circuit board pin-outs used for

  • Link Interface Module (LIM)
  • E5 Interface Modules
  • E5-TSM Modules
  • E5-STC Modules
  • E5-MCPM-B Modules

Refer to Table B-43 for signal symbol values ($, #, &, @, and ^).

B.2.4.1.1 Extension Shelf Backplane Pin-Outs, Top Connector

Table B-41 lists pinouts for DCM/DSM/LIM/MPL/TSM Extension Shelf Backplane Top Connectors P1 through P8 and P10 through P17.

Figure B-41 Extension Shelf Backplane Pin-Outs, Top Connector


img/r_pin_outs_top_connector_2_im-fig1.jpg

Table B-41 Extension Shelf Backplane Pin-Outs, Top Connector

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LGND

B01

LGND

C01

EBI_^XA02

D01

EBI_^XA14

A02

ASERO#-_50

B02

LGND

C02

EBI_^XA03

D02

EBI_^XA15

A03

ASERO#+_50

B03

LGND

C03

EBI_^XA04

D03

EBI_^XA16

A04

LGND

B04

LGND

C04

EBI_^XA05

D04

EBI_^XA17

A05

 

B05

LGND

C05

EBI_^XA06

D05

EBI_^XA18

A06

 

B06

LGND

C06

EBI_^XA07

D06

EBI_^XA19

A07

LGND

B07

LGND

C07

EBI_^XA08

D07

EBI_^XA20

A08

ASEL#-

B08

 

C08

EBI_^XA09

D08

EBI_^XA21

A09

 

B09

 

C09

EBI_^XA10

D09

EBI_^XA22

A10

AMUXIN-

B10

 

C10

 

D10

EBI_^XA23

A11

LGND

B11

AIN#-

C11

 

D11

EBI_^XA24

A12

 

B12

LGND

C12

 

D12

EBI_^XA25

A13

 

B13

LGND

C13

 

D13

EBI_^XA26

A14

LGND

B14

LGND

C14

 

D14

EBI_^XA27

A15

ASERI#-_50

B15

LGND

C15

 

D15

 

A16

ASERI#+_50

B16

LGND

C16

 

D16

 

A17

LGND

B17

LGND

C17

 

D17

 

A18

 

B18

 

C18

 

D18

 

A19

LGND

B19

MBUSSRX+_50

C19

LGND*

D19

 

A20

 

B20

MBUSSRX-_50

C20

 

D20

LGND

A21

LGND

B21

MBUSSTX+_50

C21

MA56KHZ+_50

D21

 

A22

 

B22

MBUSSTX-_50

C22

MA56KHZ-_50

D22

LGND

A23

LGND

B23

 

C23

MA8KHZ+_50

D23

 

A24

&-IF1_60

B24

 

C24

MA8KHZ-_50

D24

LGND

A25

LGND

B25

 

C25

EBI_^XSP4

D25

EBI_^XSP5

A26

&-IF2_60

B26

 

C26

EBI_^XA11

D26

 

A27

LGND

B27

 

C27

EBI_^XA12

D27

 

A28

&-IF3_60

B28

&-IF10_60

C28

EBI_^XA13

D28

LGND

A29

LGND

B29

&-IF19_60

C29

EBI_^BREQ-

D29

 

A30

&-IF4_60

B30

&-IF20_60

C30

EBI_^BG-

D30

LGND

A31

&-IF5_60

B31

&-IF21_60

C31

EBI_^XIRQ-

D31

 

A32

&-IF6_60

B32

&-IF22_60

C32

EBI_^HOSTSAN-

D32

LGND

A33

&-IF7_60

B33

&-IF23_60

C33

EBI_^GSTSAN-

D33

 

A34

&-IF8_60

B34

&-IF25_60

C34

&-IF24_60

D34

LGND

A35

&-IF9_60

B35

&-IF18_60

C35

&-IF26_60

D35

 

E2 LGND *Connection to logic ground for slots 2 (P16), 4 (P14), 6 (P12), 8 (P10) only.

B.2.4.1.2 Extension Shelf Backplane Pin-Outs, Bottom Connector

Table B-42 lists Pinouts for DCM/DSM/LIM/MPL/TSM Extension Shelf Backplane Bottom Connectors P18 through P25, and P27 through P34.

Figure B-42 Extension Shelf Backplane Pin-Outs, Bottom Connector


img/r_pin_outs_bottom_connector_3_im-fig1.jpg

Table B-42 Extension Shelf Backplane Pin-Outs, Bottom Connector

Pin Signal Pin Signal Pin Signal Pin Signal

A01

LGND

B01

&-IF1_60

C01

&-IF10_60

D01

IN2-

A02

&-IF3_60

B02

&-IF2_60

C02

&-IF19_60

D02

LGND

A03

LGND

B03

 

C03

&-IF20_60

D03

LGND

A04

&-IF4_60

B04

 

C04

&-IF21_60

D04

LGND

A05

&-IF5_60

B05

 

C05

&-IF22_60

D05

LGND

A06

&-IF6_60

B06

&-IF24_60

C06

&-IF23_60

D06

LGND

A07

&-IF7_60

B07

&-IF26_60

C07

 

D07

@-IF25_60

A08

&-IF8_60

B08

&-IF9_60

C08

&-IF18_60

D08

LGND

A09

LGND

B09

 

C09

 

D09

LGND

A10

 

B10

 

C10

EBI_^XSP2

D10

EBI_^XSP3

A11

LGND

B11

LGND

C11

EBI_^XBE0-

D11

EBI_^XD00

A12

BSERO@-_50

B12

LGND

C12

EBI_^XBE1-

D12

EBI_^XD01

A13

BSERO@-_50

B13

LGND

C13

EBI_^XBE2-

D13

EBI_^XD02

A14

LGND

B14

LGND

C14

EBI_^XBE3-

D14

EBI_^XD03

A15

 

B15

LGND

C15

EBI_^XBS8-

D15

EBI_^XD04

A16

 

B16

LGND

C16

EBI_^XBS16-

D16

EBI_^XD05

A17

LGND

B17

LGND

C17

EBI_^ADS0-

D17

EBI_^XD06

A18

BSEL@-

B18

 

C18

EBI_^ADS1-

D18

EBI_^XD07

A19

 

B19

 

C19

EBI_^XW/R

D19

EBI_^XD08

A20

BMUXIN-

B20

 

C20

EBI_^XM/IO

D20

EBI_^XD09

A21

LGND

B21

BIN@-

C21

EBI_^XSP1

D21

EBI_^XD10

A22

 

B22

LGND

C22

EBI_^XINTA-

D22

EBI_^XD11

A23

 

B23

LGND

C23

EBI_^XRDY-

D23

EBI_^XD12

A24

LGND

B24

LGND

C24

EBI_^XCAS0-

D24

EBI_^XD13

A25

BSERI@-_50

B25

LGND

C25

EBI_^XCAS1-

D25

EBI_^XD14

A26

BSERI@+_50

B26

LGND

C26

EBI_^XCAS2-

D26

EBI_^XD15

A27

LGND

B27

LGND

C27

 

D27

 

A28

 

B28

 

C28

 

D28

LGND

A29

LGND

B29

 

C29

 

D29

 

A30

 

B30

 

C30

 

D30

LGND

A31

LGND

B31

 

C31

MB56KHZ+_50

D31

 

A32

 

B32

 

C32

MB56KHZ-_50

D32

LGND

A33

LGND

B33

 

C33

MB8KHZ+_50

D33

 

A34

 

B34

 

C34

MB8KHZ-_50

D34

LGND

A35

CHASSIS GND

B35

CHASSIS GND

C35

CHASSIS GND

D35

CHASSIS GND

E1

P$48VDC

           

E2

LGND

           
B.2.4.1.3 Extension Shelf Backplane Pin-Out Symbols

Table B-43 lists the signal symbol values used in Table B-23 through Table B-43.

Table B-43 Extension Shelf Backplane Pin-Out Symbols

Slot/Connector Interface Address Signal Symbol Values
$ # & @ ^

1 top / P17

0A

0

1A

P

0A

 

0

1 bottom / P34

0B

0

1A

P

0B

A

0

2 top / P16

1A

1

1A

O

1A

 

0

2 bottom / P33

1B

1

1A

O

1B

B

0

3 top / P15

2A

2

1B

N

2A

 

2

3 bottom / P32

2B

2

1B

N

2B

C

2

4 top / P14

3A

3

1B

M

3A

 

2

4 bottom / P31

3B

3

1B

M

3B

D

2

5 top / P13

4A

4

2A

L

4A

 

4

5 bottom / P30

4B

4

2A

L

4B

E

4

6 top / P12

5A

5

2A

K

5A

 

4

6 bottom / P29

5B

5

2A

K

5B

F

4

7 top / P11

6A

6

2B

J

6A

 

6

7 bottom / P28

6B

6

2B

J

6B

G

6

8 top / P10

7A

7

2B

I

7A

 

6

8 bottom / P27

7B

7

2B

I

7B

H

6

11 top / P8

8A

8

4A

H

8A

 

8

11 bottom / P25

8B

8

4A

H

8B

I

8

12 top / P7

9A

9

4A

G

9A

 

8

12 bottom / P24

9B

9

4A

G

9B

J

8

13 top / P6

10A

A

4B

F

10A

 

A

13 bottom / P23

10B

A

4B

F

10B

K

A

14 top / P5

11A

B

4B

E

11A

 

A

14 bottom / P22

11B

B

4B

E

11B

L

A

15 top / P4

12A

C

5A

D

12A

 

C

15 bottom / P21

12B

C

5A

D

12B

M

C

16 top / P3

13A

D

5A

C

13A

 

C

16 bottom / P20

13B

D

5A

C

13B

N

C

17 top / P2

14A

E

5B

B

14A

 

E

17 bottom / P19

14B

E

5B

B

14B

O

E

18 top / P1

15A

F

5B

A

15A

 

E

18 bottom / P18

15B

F

5B

A

15B

P

E

B.2.5 Interprocessor Message Transport Connectors

The extension shelf backplane provides connections for the two high speed Inter-processor Message Transport (IMT) buses. The connections use twin-axial type connectors at J7, J8, J43, and J44.

Figure B-43 IPMX Connector


img/r_interprocessor_message_transport_connectors_1_im-fig1.jpg

Table B-44 IPMX Connector

Connector

Pin

Signal

A IMT IN J8

1

AIMTIN+_78

2

AIMTIN+_78

A IMT OUT J7

1

AIMTOUT+_78

2

AIMTOUT+_78

B IMT IN J44

1

BIMTIN+_78

2

BIMTIN+_78

B IMT OUT J43

1

BIMTOUT+_78

2

BIMTOUT+_78