Using the SCADA Summary
The SCADA Summary provides the current values and qualities of all mapped SCADA measurements in Oracle Utilities Network Management System. Each row of this summary represents one measurement. There may be multiple unique measurements on one SCADA asset. SCADA information includes digital and analog measurements, along with the quality codes and any user comments for each measurement. You can use the summary to view measurement information, manually replace current SCADA values, and inhibit updates.
This section includes the following topics:
Understanding the SCADA Summary Window
The SCADA Summary may be opened to view all SCADA measurements or for measurements related to an asset or pressure zone selected in the Viewer. The SCADA Summary displays the following fields and buttons:
The Pressure Zone column contains the name of the pressure zone reporting the SCADA measurements.
The Lift Station column contains the lift station name.
The Asset column contains the name of the asset reporting the SCADA measurements.
The Value column contains the last reported measurement value. The value can be status, digital, or analog. For status measurements, the values are displayed as a test pair, such as open/close, on/off, and so on. Analog and digital values are shown as floating point and integer values.
The Quality column contains the Quality codes for the measurement that indicates the quality of the SCADA measurement (for example, out of scan, inhibited, manual override). Several quality codes can be listed.
The Point Name column displays the name of the SCADA measurement, as used in the SCADA system.
The Attribute column contains a description of the measurement type, as configured in the ATTRIBUTES.description column in the Oracle Utilities Network Management System database for the matching attribute.
Depending on your system's configuration, you may have the ability to enter comments when manually changing SCADA status (for example, Inhibitor Manual Override). See Adding and Modifying Comments for SCADA Status Changes for more information.
If this feature is configured, you will see the following columns:
The Comments column contains the text of a comment entered when changing asset status.
The User column displays the name of the user who entered/modified comments when changing the asset status.
The Date column displays the date and time when the comment was entered or modified.
Toolbar and Menu Options
File Menu
Menu Option
Description
Toolbar Icon
Print...
Displays the Print Preview window, from which you can view and print the summary.
Toggle Dockable Window
Changes a standalone window to a pane that may be moved or docked in another window or frame. See Understanding Docked Panes and Standalone Window Tools for more information on dockable and standalone windows.
--
Exit
Closes the SCADA Summary window.
--
 
Actions Menu
Menu Option
Description
Toolbar Icon
Inhibit
Inhibit sets the inhibit quality code for the selected SCADA measurement. This suppresses any new updates from SCADA.
Cancel Inhibit
Cancel Inhibit removes the inhibit quality code from the selected SCADA measurement. This allows any new updates from SCADA to be displayed.
Manual Entry...
Manual Entry allows you to enter a new value for the selected SCADA measurement. When a changed SCADA value is received by the system, it replaces the manually entered value.
Manual Override...
Manual Override allows you to enter a new value for the selected SCADA measurement. When a new SCADA value is received by the system, the measurement is blocked and the manually entered value remains.
Cancel Override
Cancel Override cancels the manual override for the selected measurement and reverts the selected measurement to the last received value from the SCADA system.
Control Tool
Brings up the control tool for the selected measurement's asset.
View...
View focuses the Viewer on the asset.
Load Pressure Zone
Loads additional data for all SCADA measurements on a pressure zone when the SCADA Summary is displaying asset data.
Note: This option is only available when the SCADA Summary is launched from the Control Tool.
 
Load Lift Station
Loads additional data for all lift station measurements when the SCADA Summary is displaying asset or pressure zone data.
Note: This option is only available when the SCADA Summary is launched from the Control Tool.
 
Load Adjacent Lift
Loads additional data for adjacent lift stations.
Note: This option is only available when the SCADA Summary is launched from the Control Tool.
 
Load All
Repopulates the SCADA Summary with all measurements. This clears any asset, pressure zone, or lift station filters; see Viewing SCADA Data for a Selected Asset.
Help Menu
Menu Option
Description
Toolbar Icon
SCADA Summary Help
Opens the online help system to the SCADA Summary help content.
--