Rackmount Checklist
Complete the following checklist before you install the server into a rack.
|
|
|
|
|
Is the distance between the front and back mounting planes
between a minimum of 610 mm and a maximum 915 mm (24 inches to
36 inches)?
|
|
|
|
|
Is the clearance depth in the front of the front mounting
plane (distance to the front cabinet door) at least 25.4 mm (1
inch)?
|
|
|
|
|
Is the minimum clearance for service:
-
Front of server:
123.2 cm (48.5 inches)
-
Back of server:
91.4 cm (36 inches)
|
|
|
|
|
Is the rack a four-post rack (mounting at both front and
back)?
Two-post racks are not compatible.
|
|
|
|
|
Do the horizontal opening and unit vertical pitch of the rack
conform to ANSI/EIA 310-D-1992 or IEC 60297 standards?
|
|
|
|
|
Does the rack have RETMA rail support?
|
|
|
|
|
Does the rack support Oracle cable management arms
(CMAs)?
|
|
|
|
|
Does the rack support installation of Oracle vented and solid
filler panels?
|
|
|
|
|
Is there sufficient space for cable harnesses and the power
distribution units (PDUs) in the rack, if required?
|
|
|
|
|
Can a label with the server serial number be printed and
attached to the target rack?
|
|
|
|
|
Did you label the network cables that will connect to the
server?
|
|
|
|
|
Does the rack support installation of standard Oracle
PDUs?
If not, then complete this checklist.
|
|
|
|
|
Can the customer provide an equivalent pair of PDUs?
|
|
|
|
|
Can the customer provide two PDUs with capacity of 110kVA per
PDU?
|
|
|
|
|
Can the customer provide a single PDU and its circuits to
support the power requirements in case a PDU fails?
|
|
|
|
|
Can the customer ensure that power loads are evenly
distributed across all circuits of a single PDU?
|
|
|
|
|
|