C H A P T E R  3

Installing the Server Into a Rack With Slide-Rails

This chapter describes how to place the server into a rack using the rail assembly in the rackmount kit. Perform this procedure if the rail assembly is purchased.

This chapter includes the following topics:



Note - In this guide, the term rack means either an open rack or a closed cabinet.



Before You Begin

Read the following overview and see the service label on the top cover before you begin to install the server into a rack.

Server Installation Process Overview

To install your server into a four-post rack using the slide-rail and cable management arm options, perform the following tasks in the order listed.

1. Checking Rack Compatibility

2. Disassembling Slide-Rails

3. Installing the Mounting Brackets Onto the Server

4. Installing the Cable Management Arm

5. Verifying Operation of the Slide-Rails and CMA

6. Connecting the Cables

Rail Assemblies

The server might include either tool-less or bolt-on rail assemblies in rackmount kits. Instructions for both types are included in this chapter.

Service Label

Refer to the service label on the server top cover for instructions on how to install your server into a four-post rack, using the slide-rail and cable management arm options. The service label includes instructions for both tool-less and bolt-on rail assemblies.


Checking Rack Compatibility

Check that your rack is compatible with the slide-rail and cable management arm (CMA) options. The optional slide-rails are compatible with a wide range of equipment racks that meet the following standards.


TABLE 3-1 Rack Compatibility

Item

Requirement

Structure

Four-post rack (mounting at both front and rear). Two-post racks are not compatible.

Rack horizontal opening and unit vertical pitch

Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards.

Distance between front and rear mounting planes

Minimum 610 mm and maximum 915 mm
(24 inches to 36 inches).

Clearance depth in front of front mounting plane

Distance to front cabinet door is at least 25.4 mm
(1 inch).

Clearance depth behind front mounting plane

Distance to rear cabinet door is at least 800 mm (31.5 inches) with the cable management arm, or 700 mm (27.5 inches) without the cable management arm.

Clearance width between front and rear mounting planes

Distance between structural supports and cable troughs is at least 456 mm (18 inches).

Server dimensions

See TABLE 3-1 for server dimensions.




caution icon Caution - Always load equipment into a rack from the bottom up so that it will not become top-heavy and tip over. Deploy your rack’s anti-tip bar to prevent the rack from tipping during equipment installation.




caution icon Caution - Elevated Operating Ambient Temperature: If the server is installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment might be greater than room ambient temperature. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified for the server. For server environmental requirements, see Environmental Requirements.




caution icon Caution - Reduced Air Flow: Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.




caution icon Caution - Mechanical Loading: Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading.




caution icon Caution - Circuit Overloading:Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on over-current protection and supply wiring. Appropriate consideration of equipment nameplate power ratings should be used when addressing this concern.


  

caution icon Caution - Reliable Earthing:Reliable earthing of rackmounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (for example, use of power strips).



Disassembling Slide-Rails

Complete one of the following procedures before installation:


procedure icon  Disassemble Bolt-On Slide-Rails

To remove the mounting brackets from the bolt-on slide-rail assemblies:

1. Unpack the slide-rails.

2. Locate the slide-rail lock at the front of one of the slide-rail assemblies, as shown in FIGURE 3-1.

3. Squeeze and hold the tabs at the top and bottom of the lock while you pull the mounting bracket out of the slide-rail assembly until it reaches the stop (see FIGURE 3-1).

4. Push the mounting bracket release button toward the front of the mounting bracket, as shown in FIGURE 3-1, and simultaneously withdraw the mounting bracket from the slide-rail assembly.

5. Repeat for the remaining slide-rail assembly.

FIGURE 3-1 Disassembling the Bolt-On Slide-Rail Before Installation


Graphic showing slide-rail lock tabs and mounting bracket release button.


Figure Legend

1

Slide-rail lock

2

Mounting bracket release button



procedure icon  Disassemble Tool-less Slide-Rails

To remove the mounting brackets from the tool-less slide-rail assemblies, refer to the installation card instructions included with the rackmount kit.


Installing the Mounting Brackets Onto the Server

You must install the mounting brackets onto the server before you can rackmount the server.


procedure icon  Install Mounting Brackets

To install the mounting brackets onto the sides of the server:

1. Position a mounting bracket against the chassis so that the slide-rail lock is at the server front, and the four keyed openings on the mounting bracket are aligned with the four locating pins on the side of the chassis.

FIGURE 3-2 Aligning the Mounting Bracket With the Server Chassis


Graphic of mounting bracket aligned with server chassis locating pins.


Figure Legend

1

Chassis front

2

Slide-rail lock

3

Mounting bracket

4

Mounting bracket clip


2. With the heads of the four chassis locating pins protruding though the four keyed openings in the mounting bracket, pull the mounting bracket toward the front of the chassis until the mounting bracket clip locks into place with an audible click (see FIGURE 3-2).

3. Verify that the rear locating pin has engaged the mounting bracket clip (see FIGURE 3-2).

4. Repeat to install the remaining mounting bracket on the other side of the server.


Attaching the Slide-Rail Assemblies to the Rack

Complete one of the following procedures to attach the slide-rail assemblies to the rack:


procedure icon  Attach Bolt-On Slide-Rail Assemblies

To attach bolt-on slide-rail assemblies to the rack:

1. Position a slide-rail assembly in your rack so that the brackets at each end of the slide-rail assembly are on the outside of the front and rear rack posts (see FIGURE 3-3).

2. Attach the slide-rail assembly to the rack posts, but do not tighten the screws completely.

Choose one of the following methods to attach the slide-rails. The method you use varies, depending on the type of rack:

FIGURE 3-3 Attaching Slide-Rail Assembly to Rack Post


Graphic showing the mounting bracket being aligned with the rack post.


Figure Legend

1

Sllide-rail assembly

2

Rack post

3

Slide-raid assembly bracket on outside of rack post


3. Repeat Step 1 and Step 2 for the remaining slide-rail assembly.

4. From the front of the rack, set the proper width of the rails with the spacer (see FIGURE 3-4).

FIGURE 3-4 Setting the Rail Width


Graphic showing setting the rail width.


Figure Legend

1

Rail-width spacer

2

Attaching the spacer to the rails


5. Tighten the screws on both brackets.

6. Remove the spacer and confirm that the rails are attached tightly to the rack.

7. Repeat Step 4 through Step 6 for the side-rail assembly at the rear of the rack.

8. If available, extend the anti-tip bar at the bottom of the rack (see FIGURE 3-5).

FIGURE 3-5 Extending the Anti-tip Bar


Graphic showing the anti-tip bar extended.



caution icon Caution - If your rack does not have an anti-tip bar, the rack could tip over.



procedure icon  Attach Tool-less Slide-Rail Assemblies

To attach tool-less slide-rail assemblies to the rack, refer to the installation card instructions included with the rackmount kit.


Installing the Server Into the Slide-Rail Assemblies

Use this procedure to install the server chassis, with mounting brackets, into the slide-rail assemblies that are mounted to the rack.



caution icon Caution - This procedure requires a minimum of two people because of the weight of the server. Attempting this procedure alone could result in equipment damage or personal injury.


 

caution icon Caution - Always load equipment into a rack from the bottom up so that it will not become top-heavy and tip over. Extend your rack’s anti-tip bar to prevent the rack from tipping during equipment installation.



procedure icon  Install Server Into the Slide-Rail Assemblies

1. Push the slide-rails into the slide-rail assemblies in the rack as far as possible.

2. Raise the server so that the rear ends of the mounting brackets are aligned with the slide-rail assemblies that are mounted in the equipment rack (see FIGURE 3-6).

3. Insert the mounting brackets into the slide-rails, then push the server into the rack until the mounting brackets encounter the slide-rail stops (approximately 12 inches, or 30 cm).

FIGURE 3-6 Inserting the Server With Mounting Brackets Into the Slide-Rails


Graphic of inserting the server with mounting brackets into the slide-rails.


Figure Legend

1

Inserting mounting bracket into slide rail

1

Sllide-rail release button

1

Slide-rail lock


4. Simultaneously push and hold the slide-rail release buttons on each mounting bracket while you push the server into the rack (see FIGURE 3-7). Continue pushing until the slide-rail locks (on the front of the mounting brackets) engage the slide-rail assemblies.

You will hear an audible click.

FIGURE 3-7 Sliding the Server Back Into the Rack


Graphic showing the server being push back into the rack.



caution icon Caution - Verify that the server is securely mounted in the rack and that the slide-rail locks are engaged with the mounting brackets before continuing.



Installing the Cable Management Arm

The cable management arm (CMA) is an optional assembly that you can use to route the server cables in the rack.


procedure icon  Install Cable Management Arm

Use this procedure to install the optional CMA (see FIGURE 3-8).

FIGURE 3-8 Cable Management Arm (CMA)


Graphic showing the cable management arm.


Figure Legend

1

CMA rail extension


1. Unpack the CMA parts.

2. Take the CMA to the back of the equipment rack and ensure that you have adequate room to work around the back of the server.



Note - References to “left” or “right” in this procedure assume that you are facing the back of the equipment rack.


3. Remove tape to separate parts.

The CMA rail extension might be taped to the CMA arm.

4. Attach the CMA rail extension into the left slide-rail until the extension locks into place with an audible click (see FIGURE 3-9).

FIGURE 3-9 Inserting the CMA Rail Extension Into the Back of the Left Slide-Rail


Graphic showing the CMA rail extension being inserted into the rear of the left slide-rail.


Figure Legend

1

CMA rail extension

2

Left slide-rail


5. Verify that the CMA rail extension engages the slide-rail (see FIGURE 3-10).

FIGURE 3-10 Engaging the CMA Rail Extension With the Left Slide-Rail


Graphic showing close-up view of CMA rail extension locked into rail assembly.



Note - Support the CMA in the remaining installation steps. Do not allow the arm to hang by its own weight until it is secured by all three attachment points.


6. Insert the CMA’s mounting bracket connector into the right slide-rail until the connector locks into place with an audible click (see FIGURE 3-11).

FIGURE 3-11 Inserting the CMA Mounting Bracket Into the Back of the Right Slide-Rail


Graphic showing CMA mounting bracket inserted into rear of the right slide rail.


Figure Legend

1

CMA mounting bracket

2

Right slide-rail


7. Insert the right CMA slide-rail connector into the right slide-rail assembly until the connector locks into place with an audible click (see FIGURE 3-12).

FIGURE 3-12 Inserting CMA Slide-Rail Connector Into the Back of the Right Slide-Rail Assembly


Graphic showing CMA slide-rail connector inserting into the rear of the right slide-rail.


Figure Legend

1

CMA slide-rail connector

2

Right slide-rail assembly


8. Insert the left CMA slide-rail connector into the rail extension on the left slide-rail assembly until the connector locks into place with an audible click (see FIGURE 3-13).

FIGURE 3-13 Connecting the CMA to the Rail Extension Connector


Graphic of connecting the CMA to the rail extension connector.


Figure Legend

1

CMA extension arm (on left slide-rail)

2

CMA extension


9. Install and route cables to your server, as required.



Note - Instructions for installing the server cables are provided in Connecting the Cables.


10. Attach the cable hook and loop straps to the CMA, and press them into place to secure the cables (see FIGURE 3-14).

For best results, place three cable straps, evenly spaced, on the rear-facing side of the CMA and three cable straps on the side of the CMA nearest the server.

FIGURE 3-14 Installing CMA Cable Straps


Graphic showing CMA cable hangers being attached to the CMA arm.


Figure Legend

1

CMA cable strap

2

CMA arm



Verifying Operation of the Slide-Rails and CMA

Use the following procedure to ensure that the slide-rails and CMA are operating correctly.


procedure icon  Verify Operation of Slide-Rails and CMA



Note - Two people are recommended for this procedure: one to move the server in and out of the rack, and one to observe the cables and CMA.


1. Slowly pull the server out of the rack until the slide-rails reach their stops.

2. Inspect the attached cables for any binding or kinks.

3. Verify that the CMA extends fully from the slide-rails.

4. Push the server back into the rack, as described in the following sub-steps.

When the server is fully extended, you must release two sets of slide-rail stops to return the server to the rack:

a. The first set of stops are levers, located on the inside of each slide-rail, just behind the back panel of the server. These levers are labeled “PUSH.” Push in both levers simultaneously and slide the server toward the rack.

The server will slide in approximately 18 inches (46 cm) and stop.

Verify that the cables and the CMA retract without binding before you continue.

b. The second set of stops are the slide-rail release buttons, located near the front of each mounting bracket (see FIGURE 3-7). Simultaneously push or pull both of the slide-rail release buttons, and push the server completely into the rack until both slide-rail locks engage.

5. Adjust the cable straps and CMA, as required.