| Oracle® Communications EAGLE Database Administration - GWS User's Guide Release 46.6 E93314 Revision 1 |
|
![]() Previous |
![]() Next |
This procedure is used to add an allowed signaling information octet (SIO) screen to the database using the ent-scr-sio command. The parameters used by the ent-scr-sio command are shown in the Gateway Screening Attributes section. The general rules that apply to configuring gateway screening entities are shown in the Gateway Screening Configuration section.
The examples in this procedure are used to add the allowed SIO screen data shown in Table 10-2 and based on the example configurations shown in Figure 2-4, Figure 2-6, Figure 2-7, Figure 2-8, and Figure 2-9.
Table 10-2 Example Gateway Screening Allowed SIO Configuration Table
| Screening Reference | NIC | SI | H0 | H1 | PRI | NSFI | NSR |
|---|---|---|---|---|---|---|---|
|
fld4 |
2 |
0 |
4 |
5 |
3 |
destfld |
fld5 |
|
iec |
2 |
3 |
-- |
-- |
1&&3 |
cgpa |
gw11 |
|
ls02 |
2 |
3 |
-- |
-- |
3 |
cdpa |
ls03 |
|
isp1 |
2 |
5 |
-- |
-- |
3 |
isup |
isp1 |
|
tup1 |
2 |
4 |
-- |
-- |
3 |
dpc |
tup1 |
|
tup1 |
2 |
5 |
-- |
-- |
3 |
dpc |
isp2 |
The allowed SIO screen can reference one of the following screens.
Verifying the Gateway Screening Configuration
Enter the following commands to verify that these screens are in the database.
rtrv-scr-dpc:all=yes rtrv-scr-blkdpc:all=yes rtrv-scr-destfld:all=yes rtrv-scr-isup:all=yes rtrv-scr-cgpa:all=yes rtrv-scr-cdpa:all=yes Gateway Screening Configuration Procedures
If the desired screen is not in the database, perform one of these procedures to add the desired screen to the database or change an existing screen in the database.
Specifying a Range of Values
A range of values can be specified for the pri, h0, and h1 parameters. If a range of values is specified for any of these parameters and the nic and si values in the screening reference name are not changed, the range of values for the pri, h0, or h1 parameters cannot include any values that are currently provisioned for the screening reference name.
For example, screening reference name scr1 contains these entries:
SR NIC PRI SI H0 H1 NSFI NSR/ACT SCR1 2 3 1 4 5 DPC LS03 SCR1 2 2 1 2 7 BLKDPC LS04
Another entry for screening reference scr1 with the same nic and si values cannot be specified if:
pri parameter includes the values 2 or 3 h0 parameter includes the values 2 or 4 h1 parameter includes the values 5 or 7. Specifying H0 and H1 Values
The h0 and h1 values must be specified if the si value is 0, 1, or 2. If the si value is 3 through 15, the h0 and h1 parameters cannot be specified.
The h0 and h1 parameters must be specified if either parameter is specified.
The H0 and H1 heading code values can be a single value, a range of values with the beginning and end of the range separated by double ampersands (for example, a range of values from 2 to 9, 2&&9), or with an asterisk (*). The asterisk specifies all possible values for the h0 and h1 parameters. Table 10-3 shows the valid combinations of these parameter values.
Table 10-3 Valid Value Combinations for H0 and H1 Parameters
| H0 | H1 |
|---|---|
|
Single Value |
Single Value |
|
Single Value |
Range of Values |
|
Single Value |
Asterisk |
|
Range of Values |
Asterisk |
|
Asterisk |
Asterisk |
Figure 10-3 Adding an Allowed SIO Screen
Sheet 1 of 3
Sheet 2 of 3
Sheet 3 of 3