1.2.15 General Environmental Requirements for Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The environmental requirements for Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers depend on the size of the system. Table 1-14 shows the general environmental requirements for each type of Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 1-14 Environmental Requirements for Oracle Exadata Storage Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Environmental Component | Oracle Exadata Storage Expansion Full Rack | Oracle Exadata Storage Expansion Half Rack | Oracle Exadata Storage Expansion Quarter Rack |
---|---|---|---|
Weight |
917.6 kg (2023 lbs) |
578.3 kg (1275 lbs) |
396.8 kg (875 lbs) |
Acoustic levels |
83 db(A) |
82 db(A) |
81 db(A) |
Power |
Maximum: 12.6 kW (12.9 kVA) Typical: 8.8 kW (9.0 kVA) (varies based on application load) |
Maximum: 6.9 kW (7.1 kVA) Typical: 4.8 kW (5.0 kVA) (varies based on application load) |
Maximum: 3.4 kW (3.5 kVA) Typical: 2.4 kW (2.5kVA) (varies based on application load) |
Cooling |
Maximum: 43,000 BTU/hour (45,400 kJ/hour) Typical: 30,100 BTU/hour (31,800 kJ/hour) |
Maximum: 23,600 BTU/hour (24,900 kJ/hour) Typical: 16,500 BTU/hour (17,400 kJ/hour) |
Maximum: 11,600 BTU/hour (12,250 kJ/hour) Typical: 8,100 BTU/hour (8,600 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
Maximum: Approximately 1,980 CFM Typical: Approximately 1,390 CFM |
Maximum: Approximately 1,090 CFM Typical: Approximately 760 CFM |
Maximum: Approximately 530 CFM Typical: Approximately 375 CFM |
43 for Ethernet network, assuming single cluster 18 for InfiniBand network |
25 for Ethernet network, assuming single cluster 9 for InfiniBand network |
14 for Ethernet network, assuming single cluster 4 for InfiniBand network |
|
Network drops |
Minimum of 2 network drops |
Minimum of 2 network drops |
Minimum of 2 network drops |
External connectivity |
12 InfiniBand ports |
12 InfiniBand ports |
12 InfiniBand ports |
Parent topic: General Environmental Requirements