Inspect the Fan Connector
  1. Identify the prerequisite and subsequent service tasks you must perform in conjunction with this procedure.

    See Inspecting a Fan.

  2. Verify that the connector is clean and without damage.

  3. Verify that the connector receptacles are free from obstructions.


    Illustration shows a fan being inspected.
  4. Verify that the connector freely floats in its mounting.

  5. The fan is ready for installation.

    See Install a Fan.

Related Information