Temperature
|
5°C to 35°C (-23°C to 95°F), noncondensing
|
-40°C to 65°C (-40°F to 149°F),
noncondensing
|
Humidity
|
10% to 90% noncondensing relative humidity at 27°C
(80.6°F) maximum wet bulb
|
93% noncondensing relative humidity at 38°C (100.4°F)
maximum wet bulb
|
Altitude
|
3000 meters (9842.5) at 35°C (95°F) ambient
1,219 meters (4,000 feet) at 35°C (95°F) ambient
|
12,000 meters (39,370 feet)
|
Vibration
|
0.15 G z-axis; 0.10 G in x- and y-axes (5-500 Hz sine)
|
0.50 G z-axis; 0.25 G x- and y-axes (5-500 Hz sine)
|
Shock
|
3 G, 11 msec half-sine
|
1 inch roll-off front to back, 20 mm step-up
Threshold testing of castors at 0.75 m/s
|
Airflow
|
400 LFM at 55°C (131°F)
local ambient temperature
|
|