Rackmount Checklist
            Complete the following checklist before you install the server into a rack. 
            
                
                    
                    
                
                
                    
                    
                
                
                    
                
                
                    
                    
                
                
                | 
                    
                    
                    
                    
                    
                    
                        
                            |  |  |  |  |  |  
                            | Is the distance between the front and back mounting planes
                                    between a minimum of 610 mm and a maximum 915 mm (24 inches to
                                    36 inches)? |  |  |  |  |  
                            | Is the clearance depth in the front of the front mounting
                                    plane (distance to the front cabinet door) at least 25.4 mm (1
                                    inch)? |  |  |  |  |  
                            | Does the target rack meet the following minimum load
                                    capacity: 
                                    
                                        19 kg/rack unit
                                        785 kg total |  |  |  |  |  
                            | Is the rack a four-post rack (mounting at both front and
                                    back)? Two-post racks are not compatible. |  |  |  |  |  
                            | Do the horizontal opening and unit vertical pitch of the rack
                                    conform to ANSI/EIA 310-D-1992 or IEC 60297 standards? |  |  |  |  |  
                            | Does the rack have RETMA rail support? |  |  |  |  |  
                            | Does the rack support Oracle cable management arms
                                    (CMAs)? |  |  |  |  |  
                            | Does the rack support installation of Oracle vented and solid
                                    filler panels? |  |  |  |  |  
                            | Is there sufficient space for cable harnesses and the power
                                    distribution units (PDUs) in the rack, if required? |  |  |  |  |  
                            | Can a label with the server serial number be printed and
                                    attached to the target rack? |  |  |  |  |  
                            | Did you label the network cables that will connect to the
                                    server? |  |  |  |  |  
                            | Does the rack support installation of standard Oracle
                                    PDUs? If not, then complete this checklist. |  |  |  |  |  
                            | Can the customer provide an equivalent pair of PDUs? |  |  |  |  |  
                            | Can the customer provide two PDUs with capacity of 110kVA per
                                    PDU?  |  |  |  |  |  
                            | Can the customer provide a single PDU and its circuits to
                                    support the power requirements in case a PDU fails? |  |  |  |  |  
                            | Can the customer ensure power loads are evenly distributed
                                    across all circuits of a single PDU? |  |  |  |  |  |