Rack Compatibility
The rack into which you install Oracle Server X7-2 or Oracle Server X7-2L must meet the
requirements listed in the following table. Oracle Rack Cabinet 1242 and Sun Rack II are
compatible with both servers. For information about the racks, see Preparing for Server Installation.
|
|
Structure
|
|
Rack horizontal opening and unit vertical pitch
|
Conforms to ANSI/EIA 310-D-1992 or IEC 60297 standards.
|
Distance between front and back mounting planes
|
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
|
Clearance depth in front of front mounting plane
|
Distance to front cabinet door is at least 2.54 cm (1
inch).
|
Clearance depth behind front mounting plane
|
Distance to back cabinet door is at least 90 cm (35.43 inches)
with the cable management arm, or 80 cm (31.5 inches) without the
cable management arm.
|
Clearance width between front and back mounting planes
|
Distance between structural supports and cable troughs is at least
45.6 cm (18 inches).
|
Minimum clearance for service access
|
-
Clearance, front of server: 123.2 cm (48.5 inches)
-
Clearance, back of server: 91.4 cm (36 inches)
|
|
The following table contains Sun Rack II Model 1242 and Sun Rack II Model 1042 rack
specifications.
|
|
Usable rack units
|
42
|
Height
|
199.8 cm (78.66 inches)
|
Width (with side panels)
|
60 cm (23.62 inches)
|
Depth Model 1242
|
120 cm (47.24 inches)
|
Weight Model 1042
|
123.4 kg (272 lbs)
|
Depth Model 1042
|
105.8 cm (41.66 inches)
|
Weight Model 1242
|
150.6 kg (332 lbs)
|
Maximum dynamic load
|
1005 kg (2215 lbs)
|
|
The following table contains the Oracle Rack Cabinet 1242 rack specifications:
|
|
Usable rack units
|
42
|
Height
|
199. cm (78.74 inches)
|
Width (with side panels)
|
60 cm (23.62 inches)
|
Maximum dynamic load
|
1005 kg (2215 lbs)
|
|