Go to main content

Oracle® Exadata Storage Server X7-2 EF and HC Installation Guide

Exit Print View

Updated: November 2018
 
 

Electrical Requirements

The servers use AC power. The following table contains the power supply specifications for the servers.


Note -  The power dissipation numbers listed in the following table are the maximum rated power numbers for the power supply used in the server. The numbers are not a rating of the actual power consumption of the server.

The servers can operate effectively over a range of voltages and frequencies.

Parameter
Specification
Voltage (nominal)
100-240 VAC
Input current (maximum)
100-127 VAC 7.2 A and 200-240 VAC 3.4 A
Frequency (nominal)
50/60 Hz (47 to 63 Hz range)
Maximum power consumption
2400 W
Maximum heat output
11600 BTU/Hr

Caution

Caution  -  Servers must have a reliable power source. If the system exceeds the ranges, damage to the server might occur. Electrical disturbances, such as the following, might damage the system:

  • Fluctuations caused by brownouts
  • Wide and rapid variations in input voltage levels or in input power frequency
  • Electrical storms
  • Faults in the distribution system, such as defective wiring


To protect your server from such disturbances, use a dedicated power distribution system, power-conditioning equipment, and lightning arresters or power cables for protection from electrical storms.

See the following additional power specifications.