Rack Requirements
The Oracle Exadata Storage Server X5-2 High Capacity is a 2 rack unit (2U) storage server that fits inside Oracle's
Exadata rack. The rack specifications are listed in the following table.
Table 6 Exadata Rack Specifications
|
|
Usable rack units
|
42
|
Height
|
199.8 cm (78.6 inches)
|
Width (with side panels)
|
60 cm (23.6 inches)
|
Depth
(front door handle to rear door handle)
|
120 cm (47.24 inches)
|
Weight
|
150.6 kg (332 lbs)
|
Maximum dynamic load
|
1005 kg (2215 lbs)
|
Structure
|
Four-post rack (mounting at both front and rear). Supported rack
types: square hole (9.5 mm) and round hole (M6 or 1/4-20 threaded
only).
Two-post racks are not compatible.
|
Rack horizontal opening and unit vertical pitch
|
Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards.
|
Distance between front and rear mounting planes
|
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
|
Clearance depth in front of front mounting plane
|
Distance to front cabinet door is at least 2.54 cm (1
inch).
|
Clearance depth behind front mounting plane
|
Distance to rear cabinet door is at least 90 cm (35.43 inches)
with the cable management arm, or 80 cm (31.49 inches) without the
cable management arm.
|
Clearance width between front and rear mounting planes
|
Distance between structural supports and cable troughs is at least
45.6 cm (18 inches).
|
Minimum clearance for service access
|
Clearance, front of storage server: 123.2 cm (48.5 inches)
Clearance, rear of storage server: 91.4 cm (36 inches)
|
|
The minimum ceiling height for the cabinet is 230 cm (90 inches), measured from the
true floor or raised floor, whichever is higher. An additional 91.4 cm (36 inches) is
for top clearance. The space above the cabinet and its surroundings must not restrict
the movement of cool air between the air conditioner and the cabinet, or the movement of
hot air coming out of the top of the cabinet.