Electrical Requirements
The server uses AC power. The server can operate effectively over a range of voltages
and frequencies.
The following table contains the power supply specifications for Oracle Server X8-8.
Note -
The power dissipation numbers listed in the following table are the maximum rated
power numbers for the power supply used in the system. The numbers are not a rating
of the actual power consumption of the system. For up-to-date information about
power consumption, go to the Oracle Power Calculators web site
https://www.oracle.com/it-infrastructure/power-calculators/, and click the Oracle Server X8-8 link.
|
|
Voltage (nominal)
|
200-240 VAC
|
Input current (maximum)
|
-
23 A @ 200 to 240 VAC
-
12 A max per cord
|
Frequency (nominal)
|
50/60 Hz
|
Maximum power consumption
|
-
Single 4-socket –1980 W
-
Dual 4-socket – 3950 W
-
Single 8-socket – 3880 W
|
Maximum heat output
|
13,475 BTU/Hr
|
|
![Caution Caution](graphics/electrical.gif) | Caution -
Servers must have a reliable power source. Damage to the server might occur if the
input voltage levels or in input power frequency ranges are exceeded. Electrical
disturbances, such as the following, might damage the system:
-
Fluctuations caused by brownouts
-
Wide and rapid variations in input voltage levels or in input power
frequency
-
Electrical storms
-
Faults in the distribution system, such as defective wiring
|
To protect your server from such disturbances, use a dedicated power distribution
system, power-conditioning equipment, and lightning arresters or power cables for
protection from electrical storms.
See the following additional power specifications.