You do not have to power off the server to service the fan modules.
You should not begin this procedure unless you have a replacement fan and you are ready to install it right away.
Caution - When removing and replacing a fan module in the Oracle Server X6-2, you must complete the entire procedure within 20 seconds to maintain adequate cooling within the system. Remove and replace only one fan module at a time. Ensure that you have obtained the replacement fan module and that is it is ready for installation before starting the replacement procedure. Each fan module contains two fans, with two fan motors per fan. The four fan motors provide separate tachometer signals so that the fan module reports four tach signals to Oracle ILOM. Even if only one fan motor is faulted within the fan module, the Oracle ILOM service processor detects that four fan motors have failed to spin while the fan module is removed. If the fan module is not replaced within 20 seconds of removal, Oracle ILOM will take the protective action to shut down the system to prevent thermal damage to the system. |
Caution - Close the server fan door within 60 seconds to maintain adequate airflow to properly cool the server. Leaving the door open for more than 60 seconds, while the server is running, might cause the server to overheat and shut down. |
Each fan module has a status indicator (LED). If the LED is off, the fan is good. If the LED is lit amber, the fan has failed. The LEDs are located on the chassis mid-wall adjacent to and aligned with the fan modules, as shown in the following figure.
|
Caution - When removing a fan module, do not rock it back and forth. Rocking a fan module can cause damage to the motherboard connectors. |
Caution - Do not service any other components in the fan compartment unless the system is shut down and the power cords are removed. |
If you removed the fan assembly as part of another procedure, return to that procedure.
Otherwise, continue to Install a Fan Module.