Rack Compatibility
Check that your rack is compatible with the slide rail and
cable management assembly options. The optional slide rails are
compatible with a wide range of equipment racks that meet the following
standards.
|
|
Structure |
Four-post rack (mounting at both front
and rear). Two-post racks are not compatible. |
Rack horizontal opening and unit vertical
pitch |
Conforms to ANSI/EIA 310-D-1992 or IEC
60927 standards. |
Rack rail mounting hole sizes |
Only 9.5-mm square hole and M6 round
mounting holes are supported. All other sizes, including
7.2-mm, M5, or 10-32 mounting holes, are not supported. |
Distance between front and rear mounting
planes |
Minimum: 24.5 in. (622 mm)
Maximum: 35.25 in. (895 mm) |
Clearance depth in front of front mounting
plane |
Distance to front cabinet door is at
least 1.06 in.
(27 mm). |
Clearance depth behind front mounting
plane |
Distance to rear cabinet door is at least
35.5 in. (900 mm) with the CMA, or 30.4 in. (770 mm) without the
cable management assembly. |
Clearance width between front and rear
mounting planes |
Distance between structural supports
and cable troughs is at least 18 in. (456 mm). |
Server dimensions |
Depth: 29.63 in. (752.5 mm)
Width: 17.185 in. (436.5 mm)
Height: 5.11 in. (129.8 mm) |
|