Install a Fan Module

  1. Remove the replacement fan module from its packaging, and place it on an antistatic mat.
  2. With the top cover fan assembly door open, install the replacement fan module into the storage server [1].

    The fan modules are keyed to ensure that they are installed in the correct orientation.


    image:Figure showing how to install a fan module.
  3. Press down on the fan module and apply firm pressure to fully seat the fan module.
  4. Verify that the fan module status indicator (LED) on the replacement fan module is not illuminated.
  5. Using your thumb and forefinger, tighten the captive screw to secure the fan module to the chassis. Then use a No. 2 Phillips screwdriver to tighten the screw an additional 1/4 turn to secure the fan module to the chassis [2].
  6. Close the top cover fan assembly door.
  7. Verify that the Top Fan Fault LED on the front of the storage server and the Service Required LEDs on the front and rear of the storage server are extinguished.

    See Storage Server System-Level Status Indicators for more information about identifying and interpreting system status indicators.

  8. Consider your next step: