Preparing MiniCluster For Service

Most service procedures are performed on a single appliance component. Service procedures that require a single compute node to be powered off can be performed without shutting down the entire MiniCluster.


Note -  The links in this table take you to instructions that are in other documents. Open the links in a new tab or use your browser's Back button to return to this document.
Task
For More Information
Review safety information.
Safety Information in the SPARC S7-2 Server Service Manual
Gather required tools.
Service Tools in the SPARC S7-2 Server Service Manual
Find the server serial number.
Find the Server Serial Number in the SPARC S7-2 Server Service Manual
Locate the server in the data center.
in the SPARC S7-2 Server Service Manual
Shut the compute nodes down gracefully.
Shut Down, Reset, or Power Cycle the System in the MiniCluster S7-2 Administration Guide.
Power off the compute nodes.
Caution – Shut both compute nodes down gracefully before powering off the server.
Power Off the Server in the SPARC S7-2 Server Service Manual
Power off the storage array.
Caution – Power off both compute nodes before powering off the storage array.
  1. Place the storage array power supply on/off switches to the "0" off position.

    Note – There are two power supplies for each array. Power off all power supplies.

  2. Disconnect both power cords from the power source.

    Note – All power cords must be disconnected to completely remove power from the storage array.

Label cables then disconnect the cables.
Disconnect Cables From the Server in the SPARC S7-2 Server Service Manual
Prevent ESD damage.
Prevent ESD Damage in the SPARC S7-2 Server Service Manual
Extend the server to the service position.
Extend the Server to the Service Position in the SPARC S7-2 Server Service Manual
Remove the server from the rack.
Remove the Server From the Rack in the SPARC S7-2 Server Service Manual
Open the server fan door.
Open the Server Fan Door in the SPARC S7-2 Server Service Manual
Remove the server top cover.
Remove the Top Cover in the SPARC S7-2 Server Service Manual