Environmental Requirements

The following table lists temperature, humidity and altitude requirements.

Condition
Operating Requirement
Non-operating Requirement
Comments
Temperature
5 to 32°C (41 to 89.6°F)
-40 to 70°C (-40 to 158°F).
For optimal rack cooling, data center temperatures from 21 to 23°C (70 to 47°F)
Relative humidity
10 to 90% relative humidity, noncondensing
Up to 93% relative humidity.
For optimal data center rack cooling, 45 to 50%, noncondensing
Altitude
3048 m (10000 ft.) maximum

Except in China where regulations may limit installations to a maximum altitude of 2000 m (6560 ft.).

12000 m (40000 ft.).
Ambient temperature is de-rated by 1 degree Celsius per 300 m above 900 m altitude above sea level