Rackmount Checklist
Complete the following checklist prior to installing the server into a rack or
cabinet:
|
|
|
|
|
Is the distance between the front and rear mounting
planes between the minimum or 610 mm and the maximum 915 mm (24
inches to 36 inches)?
|
|
|
|
|
Is the clearance depth in the front of the front
mounting plane (distance to the front cabinet door) at least 25.4 mm
(1 inch)?
|
|
|
|
|
Does the target rack meet the following minimum load
capacity:
-
19 kg/rack unit
-
785 kg total
|
|
|
|
|
Is the rack a four-post rack (mounting at both front and
rear)?
Two-post racks are not compatible.
|
|
|
|
|
Does the rack's horizontal opening and unit vertical pitch conform
to ANSI/EIA 310-D-1992 or IEC 60927 standards?
|
|
|
|
|
Does the rack have RETMA rail support?
|
|
|
|
|
Does the rack support Oracle cable management arms (CMAs)?
|
|
|
|
|
Does the rack support installation of Oracle vented and solid
filler panels?
|
|
|
|
|
Is there sufficient space for a cable harnesses and the power
distribution units (PDUs) in the rack, if required?
|
|
|
|
|
Can a label with the server serial number be printed and attached
to the target rack?
|
|
|
|
|
Did you run the required network cables from your network
equipment to the location where the server will be installed?
|
|
|
|
|
Did you label the network cables that will connect to the
server?
|
|
|
|
|
Does the rack support installation of standard Oracle PDUs?
If not, then complete this checklist.
|
|
|
|
|
Can the customer provide equivalent PDUs?
|
|
|
|
|
Can the customer provide a single PDU and its circuits to support
the power requirements in case on PDU fails?
|
|
|
|
|
Can the customer ensure power loads are evenly distributed across
all circuits of a single PDU?
|
|
|
|
|
Can the customer provide appropriate power drops for the
PDUs?
|
|
|
|
|
|