Environmental Requirements
The following table lists the temperature, humidity, and altitude specifications, as
well as acoustic noise, vibration, and shock specifications.
Table 6 Environmental Specifications
|
|
|
Ambient temperature (Does not apply to removable media)
|
-
Maximum range: 41°F to 95°F (5°C to 35°C)
up to 2,953 feet (900 meters)
-
Optimal: 69.8°F to 73.4°F (21°C to
23°C)
Note -
Maximum ambient operating temperature is derated by 1 degree C
per 300 meters of elevation beyond 900 meters, up to a maximum
altitude of 3,000 meters.
|
–40°F to 154°F (–40°C to 68°C)
|
Relative humidity
|
-
10% to 90% noncondensing, short term 23°F to 113°F
(–5°C to 55°C)
-
5% to 90% noncondensing, but not to exceed 0.024 kg of
water per kg of dry air (0.053 lbs water/2.205 lbs dry
air)
|
Up to 93% noncondensing 95°F (35°C) maximum wet
bulb
|
|
Up to 9,840 feet (3,000 meters)
Note -
In China markets, regulations may limit installations to a
maximum altitude of 6,562 feet (2,000 meters).
|
Maximum 39,370 feet (12,000 meters)
|
Acoustic noise
|
|
Not applicable
|
Vibration
|
0.15 G (z-axis),
0.10 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
|
0.5 G (z-axis),
0.25 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
|
Shock
|
3.5 G, 11 ms half-sine
IEC 60068-2-27 Test Ea
|
Roll-off: 1.25-inch roll-off free fall, front to back rolling
directions
Threshold: 13-mm threshold height at 0.65 m/s impact
velocity
ETE-1010-02 Rev A
|
|
Set conditions to the optimal temperature and humidity ranges to minimize the chance
of downtime due to component failure. Operating the Oracle Server X6-2 for extended periods
at or near the operating range limits, or installing it in an environment when it
remains at or near nonoperating range limits could significantly increase hardware
component failure. See also: