Go to main content

SPARC T7-1 Server Installation Guide

Exit Print View

Updated: March 2019
 
 

Electrical Specifications

Description
Value
Notes
Voltage
200 to 240 VAC
Frequency
50 to 60 Hz
Maximum operating input current at 200 VAC (per cord)

The maximum operating input current values are based on P / (V *0.90), where P = max. operating input power, V= input voltage. Example: 620W / (120 * 0.90) = 6.89A You can use this equation to calculate your maximum operating current at your input voltage.

5.7 A
Actual amperage draw may exceed rating by no more than 10%.
Maximum operating input current at 200 VAC (all inputs)
7.0A
Maximum operating input power at 200 VAC
1370W
Maximum standby power
20W
Idle input power (maximum configuration)

Maximum server configuration specification under nominal temperature and voltage conditions (one 4.133-GHz T7 processor with sixteen 32GB DDR4 DIMMs, 4 HDDs, 4 NVMe SFFs, and 6 I/O cards).

658W
Idle input power (minimum configuration)

Minimum server configuration specification under nominal temperature and voltage conditions (one 4.133-GHz T7 processor with eight 16-GB DDR4 DIMMs, no HDD, and no I/O cards).

398W
Peak AC power (maximum configuration)
1306W
Conforms to SpecJBB.
Peak AC power (minimum configuration)
634W
Conforms to SpecJBB.
Maximum heat dissipation
4456 BTU/hr
4702 KJ/hr

For information on power specifications, use the power calculator at:

http://www.oracle.com/us/products/servers-storage/sun-power-calculators