Go to main content

Oracle® Exadata X8-2 Database Server Service Manual

Exit Print View

Updated: July 2020
 
 

Install a Power Supply


Caution

Caution  -  Always replace the failed power supply with the same type model of power supply.


  1. Remove the replacement power supply from its packaging and place it on an antistatic mat.
  2. Align the replacement power supply with the empty power supply slot [1].
  3. Slide the power supply into the bay until it is fully seated [2].

    You hear an audible click when the power supply fully seats.


    image:Figure showing a power supply being installed into the
                            chassis.
  4. Reconnect the power cord to the power supply.
  5. Verify that the amber Fault-Service Required LED on the replaced power supply and the Fault-Service Required LEDs are not lit on the front and back panels.

    Note -  After you have replaced Power Supply 0, you must reset the Oracle ILOM service processor (SP) to propagate the key identity properties (KIP) data to the new power supply. For instructions on resetting the SP, refer to the Oracle Integrated Lights Out Manager (ILOM) 4.0 Configuration and Maintenance Guide Firmware Release 4.0.x at https://www.oracle.com/goto/ilom/docs. Power Supply 1 does not contain KIP data, and therefore does not require an SP reset after replacement.
  6. If you disconnected the two CMA left-side connectors, reconnect the connectors.

    Refer to Install the Cable Management Arm (Optional) in Oracle Servers X8-2 and X8-2L Installation Guide.

Related Information