Environmental Requirements
This topic includes these specifications:
Table 1 Temperature, Humidity, and Elevation Specifications
|
|
|
|
|
|
|
|
|
|
Temperature (maximum)
|
5° to 35° C
at 900m
|
41° to 95° F at 0 to 3000 ft
|
-40° to 65° C
at 900m
|
-40° to 149° F
at 0 to 3000 ft
|
Decrease in maximum temperature: above 3000 ft. (900m),
1.8°F/1000 ft (1°C/300m)
|
Relative humidity
|
10 to 90%
at 27° C
|
10 to 90%
at 81° F
|
Up to 93%
at 38° C
|
Up to 93%
at 100° F
|
Maximum wet bulb, noncondensing
|
Altitude
|
0 to 3000 m
at 40° C
|
0 to 9840 ft at 95° F
|
Up to 12,000 m
|
Up to 40,000 ft
|
In China markets, regulations may limit installations to a maximum
operating altitude of 2000m.
|
|
Table 2 Shock and Vibration Specifications
|
|
|
Shock
|
3 G, 11 ms
|
Half-sine
|
Vibration (vertical)
|
0.15 G
|
5 to 500 HZ swept-sine
|
Vibration (horizontal)
|
0.10 G
|
|
|
Table 3 Acoustic Specifications
|
|
|
Sound Power Level - LwAd
(1 B = 10 dB)
|
7.8 B
|
9.4 B
|
Sound Pressure Level - LpAm
(energy average of 4 bystander positions)
|
61.8 dBA
|
79.7 dBA
|
|