Install the CMA
Attach the CMA to the rear posts of the rack.
Note -
The CMA installation might block some of the power outlets in the rack,
making them unavailable.
-
Confirm that you have the correct hardware to install the CMA.
See Determine Correct Rackmount Hardware.
-
Attach the bracket adapters to the CMA comb.
Use six M6 x 6mm screws, three on each side.
-
If the server is already installed in the rack, do the following:
-
Remove the four faceplate screws, two on each side.
| Caution -
Do not loosen or remove the screws that secure the shelf rail
brackets to the rack.
|
-
At the rear of the server, on square hole racks, remove the middle
adapter screw on each side.
| Caution -
Do not remove the top adapter screw on the square hole
racks.
|
-
Push the server forward 3 in. (76 mm).
-
Attach the CMA to the rack posts, using two M6 screws for each
side.
-
Consider your next steps:
-
If the server is already installed, do the following:
-
At the front of the server, push the server back until it
touches the rails.
-
Reinstall the four faceplate screws, two for each
side.
-
If the server is not already installed, install the server.
See Install the Server.