Electrical Specifications

Use these specifications only as a general planning guide. To determine power values based on expected workloads, use the SPARC T7-4 power calculator at:

http://www.oracle.com/goto/powercalculators/

Description
Value
Operating input range
200 to 240 VAC,
50-60 Hz
Maximum operating input current at 200 VAC (per cord)
Maximum operating input current at 200 VAC (all inputs)
16 A

Actual amperage draw may exceed rating by no more than 10%.

22.9 A
Maximum operating input power at 200 VAC
4498 W
Maximum heat dissipation
15,348 BTU/hr
(16,193 KJ/hr)
Maximum standby power
105 W
Maximum server configuration specification under nominal temperature and voltage conditions:
(Four 3.6 GHz T5 Processors, with sixty-four 32 GB DDR4 DIMMS, 8 HDD and 16 I/O cards)
Idle input power
2124 W
Peak AC input power (running SpecJBB)
4386 W
Minimum server configuration specification under nominal temperature and voltage conditions
(Two 3.6 GHz T5 Processors, with 32x 16GB DDR4 DIMMS, no HDD and no I/O cards)
Idle input power
1023 W
Peak AC input power (running SpecJBB)
1915 W

Note -  The maximum operating input current values are based on the formula P / (V *0.90), where P = maximum operating input power and V = input voltage. For example: 620W / (100V * 0.90) = 6.89A You can use this formula to calculate the maximum operating current at your input voltage.

Caution

Caution  -  Use only the power cords provided with the server.