PDU Electrical Specifications

The following tables describe the standard PDU electrical specifications, including the number and type of connectors and receptacles.

Table 1  Specifications for North and South America, Japan, and Taiwan Low-Voltage PDUs
Specification
22 kVA
24 kVA
Number of inputs
3 x 50A single phase
2 x 60A 3 phase
Voltage
200 to 240 VAC single phase
200 to 220 VAC 3 phase
Frequency
50/60Hz
50/60Hz
Current
36.8A max. per input
34.6A max. per phase
Power rating
22 kVA
24 kVA
Output current
110.4A (3 x 36.8A)
120A (6 x 20A)
Outlets
42 x C13 6x C19
42 x C13 6 x C19
Outlet groups
6
6
Group protection

UL489 2-pole circuit breaker.

20A
20A
Data center receptacle
Hubbell CS8264C
IEC309 60A 4 PIN 250VAC 3 phase IP67
Table 2  Specifications for EMEA and APAC High-Voltage PDUs
Specification
22 kVA
24 kVA
Number of inputs
3x32A single phase
2 x 25A 3 phase
Voltage
220 to 240 VAC
220/380 to 240/415 VAC 3 phase
Frequency
50/60Hz
50/60Hz
Current
32A max per input
18A max. per phase
Power rating
22 kVA
24 kVA
Output current
96A (3x32A)
109A (6 x 18.1A)
Outlets
42 x C13 6 x C19
42 x C13 6 x C19
Outlet groups
6
6
Group protection

UL489 1-pole circuit breaker.

20A
20A
Data center receptacle
IEC309 32A 3 PIN 250 VAC single phase IP44
IEC309 32A 5 PIN 230/400V 3 phase IP44