Replace an FMM Power Cord

This task can take approximately 30 minutes to complete.

Before You Begin

Obtain a No. 3 Phillips screwdriver for the procedure.

  1. Follow safety and ESD precautions.

    See Safety and ESD Precautions.

  2. Remove the node at slot 15.

    See Front Components and Remove an Oracle Server X5-2M or Remove an Oracle Server X6-2M.

  3. Remove the slot 15 side rail on the side corresponding to the faulty power cord.
  4. Disconnect the faulty power cord from PDU.
  5. Remove the node rear support bracket from slot 20.

    Notice the orientation. The shelf is on top.

  6. Disconnect the faulty power cord from the FMM PSU.

    The cable might be tied to the frame chassis with a Velcro strip.

  7. Connect the replacement power cord to the FMM PSU.
  8. Connect the replacement power cord to same location on the PDU.

    There is no need to reattach the Velcro strip, because it is only needed for shipping.

  9. Remove the faulty power cable, if possible.
  10. Verify that the FMM PSU has power.
  11. Install the node rear support bracket at slot 20.

    Make sure the shelf is on top.

  12. Reinstall the side rail and the node in slot 15.

    See Install an Oracle Server X5-2M or Install an Oracle Server X6-2M.