Replace an FMM Power Cord
This task can take approximately 30 minutes to complete.
Before You Begin
Obtain a No. 3 Phillips screwdriver for the procedure.
-
Follow safety and ESD precautions.
See Safety and ESD Precautions.
-
Remove the node at slot 15.
See Front Components and Remove an Oracle Server X5-2M or Remove an Oracle Server X6-2M.
-
Remove the slot 15 side rail on the side corresponding to the faulty power
cord.
-
Disconnect the faulty power cord from PDU.
-
Remove the node rear support bracket from slot 20.
Notice the orientation. The shelf is on top.
-
Disconnect the faulty power cord from the FMM PSU.
The cable might be tied to the frame chassis with a Velcro strip.
-
Connect the replacement power cord to the FMM PSU.
-
Connect the replacement power cord to same location on the PDU.
There is no need to reattach the Velcro strip, because it is only needed for shipping.
-
Remove the faulty power cable, if possible.
-
Verify that the FMM PSU has power.
-
Install the node rear support bracket at slot 20.
Make sure the shelf is on top.
-
Reinstall the side rail and the node in slot 15.
See Install an Oracle Server X5-2M or Install an Oracle Server X6-2M.