Go to main content
Oracle® SuperCluster T5-8 Owner's Guide

Exit Print View

Updated: May 2016
 
 

PDU Thresholds (Half-Populated Racks)

Table 13  22kVA Single-Phase PDUs
Low Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M1-3
M1-1
18
23
17
21
M1-2
M1-2
20
25
18
23
M1-1
M1-3
20
25
18
23
Table 14  24kVA 3-Phase PDUs
Low Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M2-3
M1-3
16
20
6
8
M2-2
M1-2
20
26
11
14
M2-1
M1-1
15
20
10
14
M1-3
M2-3
15
19
8
10
M1-2
M2-2
17
22
8
10
M1-1
M2-1
17
22
10
14