Rack Requirements
The rack into which you install the Oracle Server X5-2 must meet the requirements listed in the
following table. Oracle's Sun Rack II is compatible with the Oracle Server X5-2. For
information about Oracle's Sun Rack II, see Preparing for Server Installation.
Table 8 Rack Requirements
|
|
Structure
|
Four-post rack (mounting at both front and rear). Supported rack types: square hole (9.5 mm)
and round hole (M6 or 1/4-20 threaded only.
Two-post racks are not compatible.
|
Rack horizontal opening and unit vertical pitch
|
Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards.
|
Distance between front and rear mounting planes
|
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
|
Clearance depth in front of front mounting plane
|
Distance to front cabinet door is at least 2.54 cm (1 inch).
|
Clearance depth behind front mounting plane
|
Distance to rear cabinet door is at least 90 cm (35.43 inches) with the cable management arm,
or 80 cm (31.5 inches) without the cable management arm.
|
Clearance width between front and rear mounting planes
|
Distance between structural supports and cable troughs is at least 45.6 cm (18 inches).
|
Minimum clearance for service access
|
-
Clearance, front of server: 123.2 cm (48.5 inches)
-
Clearance, rear of server: 91.4 cm (36 inches)
|
|