Rack Requirements
The rack into which you install the Oracle Server X6-2L must meet the requirements listed in the
following table. Oracle's Sun Rack II is compatible
with the Oracle Server X6-2L. For information about the Oracle Sun Rack II, see
Preparing for Server Installation.
Table 8 Rack Requirements
|
|
Structure |
Four-post rack (mounting at both front
and rear). Supported rack types: square hole (9.5 mm) and round
hole (M6 or 1/4-20 threaded only).
Two-post racks are not compatible. |
Rack horizontal opening and unit vertical
pitch |
Conforms to ANSI/EIA 310-D-1992 or IEC
60927 standards. |
Distance between front and rear mounting
planes |
Minimum 61 cm and maximum 91.5 cm
(24 inches to 36 inches). |
Clearance depth in front of front mounting
plane |
Distance to front cabinet door is at
least 2.54 cm
(1 inch). |
Clearance depth behind front mounting
plane |
Distance to rear cabinet door is at least
90 cm (35.43 inches) with the cable management arm, or 80 cm (31.49
inches) without the cable management arm. |
Clearance width between front and rear
mounting planes |
Distance between structural supports
and cable troughs is at least 45.6 cm (18 inches). |
Minimum clearance for service access |
Clearance, front of server: 123.2 cm
(48.5 inches)
Clearance, rear of server: 91.4 cm (36 inches) |
|