Attach Tool-less Slide-Rail
Assemblies
Use this procedure to attach
tool-less slide-rail assemblies to the rack.
Note -
Right-angle AC power cables (part number 7079727 - Pwrcord, Jmpr, Bulk, SR2, 2m,
C14RA, 10A, C13) must be installed before slide-rails when installing the
Oracle Server X6-2L into a Sun Rack II 1042 (1000-mm) system rack. The standard rail kit
tool-less slide-rails impede access to the 15kVA and 22kVA Power Distribution Unit
(PDU) electrical sockets in the 1000-mm rack. If you use the standard AC power cables
and then install the slide-rails into the rack, you will be unable to disconnect or
remove the AC power cables. Once the slide-rails have been installed into the rack,
you will be unable to disconnect or remove the AC power cables.
- Orient
the slide-rail assembly so that the ball-bearing track is forward
and locked in place.
|
|
1
|
Slide-rail
|
2
|
Ball-bearing track
|
3
|
Locking mechanism
|
|
- Starting with either the left or right
side of the rack, align the rear of the slide-rail assembly against
the inside of the rear rack rail, and push until the assembly locks
into place with an audible click.
- Align the front of the slide-rail assembly
against the outside of the front rack rail, and push until the assembly
locks into place with an audible click.
- Repeat Step 1 through Step 3 to
attach the slide-rail assembly to the other side of the rack.