Install the Shipping Bracket With Cable Trough (Optional)
If you plan to ship the server in a rack with a space of one or more rack units below
the server, you must install the Shipping Bracket With Cable Trough to prevent damage to
the server. The bracket is required for each server in the rack that meets this
requirement.
The Shipping Bracket With Cable Trough is a separately orderable option. For
information about ordering the Shipping Bracket With Cable Trough, contact your Oracle
Sales representative.
-
Unpack the Shipping Bracket With Cable Trough and components.
The following figure shows the components that are needed for the
installation.
|
|
1
|
Shipping Bracket With Cable Trough
|
2
|
Four 16-mm M6 screws
|
3
|
Four cage nuts
|
4
|
Cage nut insertion tool
|
|
-
For racks configured with square hole RETMA rails, install the four cage nuts as
follows.
Note -
This step is not necessary for racks configured with threaded RETMA
rails.
-
Using your equipment's rack alignment template, or other equipment
documentation, locate the first and third rail holes below the rear panel of
the server, along the left and right sides of the chassis. [1]
-
Retrieve a cage nut and hook the bottom lip of the cage nut in one of the
rail holes.
-
Insert the tip of the cage nut insertion tool through the rail hole and hook
the top lip of the cage nut. [2]
-
Using the insertion tool, pull the cage nut through the hole until the top
lip snaps into place.
-
Repeat Step 2a through Step 2d for the remaining cage nuts.
-
Slide the bracket underneath the rear bottom edge of the server chassis with the
cable trough facing up, aligning the top holes in the bracket with the first rail
holes below the rear panel of the server.
-
Using a No. 2 Phillips screwdriver, secure the bracket to the rack using four
16-mm M6 screws.
Ensure that the bracket rests firmly against the bottom of the server
chassis.
-
If necessary, lay any cables protruding from the server back panel into the cable
trough.