Installing a DE3-24C Disk Shelf

The Oracle Storage Drive Enclosure DE3-24C requires four rack units (RU), or twelve rack holes, of vertical space in the cabinet.

Before You Begin

  • Review Prerequisites for Installation and Overview of Disk Shelves.

  • To prevent the cabinet from tipping, always load the heaviest equipment, which are disk shelves, starting from the bottom of the cabinet.

  • To best prepare for cabling disk shelves to controllers, now and in the future, mount controllers in the middle of the cabinet.

  • Screws are not provided for installation into a cabinet with M6-sized threaded holes.


Caution

Caution  -  This procedure requires a minimum of three people, or a mechanical lift, because of the weight of the chassis. Attempting this procedure alone could result in equipment damage or personal injury. Do not lift the chassis using the power supply handles.


  1. Starting at the bottom of the cabinet, locate the appropriate rack unit (RU) height.
  2. Unpack the contents of the disk shelf rail kit box, and identify the correct cage nuts for your rack type.

    There are two cage nut packets, each containing square or round hole cage nuts. Each packet also contains a template for positioning the cage nuts.


    Note -  This procedure shows rail kit installation for a square hole rack. The same steps apply for a round hole rack. Also, screws are not provided for M6-sized threaded rack holes.

    image:Rail kit parts including square and round hole cage nuts
    Callout
    Description
    1
    Six 10-32 7 mm captive screws (two spares)
    2
    Two adjustable shelf rails
    3
    Two packets of four 10-32 cage nuts (only one set is required):
    • Four 9.5 mm square cage nuts (two spares)

    • Four 7 mm round cage nuts (two spares)

  3. Attach the disk shelf rails to the rack, as follows:
    1. Orient the rail so that the stamped label (LEFT or RIGHT) is facing the inside of the rack.
    2. Adjust the rail length to fit the front and rear of the rack [A and B].

      Note -  Mark which rack rail holes you will be using to ensure the shelf rails are installed evenly.
    3. Press and hold open the clamp lever on each rail end [1], and insert both rail ends into the appropriate rack holes [2].
      image:Installing a shelf rail in the rack
    4. Close the rail clamps over the rails by releasing the clamp lever [3].

      You will hear an audible click as the clamps lock in place over the rack rails.

    5. Repeat steps a through d for the second rail.
  4. Install one screw through the rack and into the rear of each rail.
    image:Install the rear rail screws
  5. Install the front cage nuts.

    Caution

    Caution  -  A mounted disk shelf is unstable if the front cage nuts are not installed. Always install the cage nuts before mounting the disk shelf.


    1. Use the template to determine cage nut placement [1].
      image:Installing front cage nuts
    2. Insert one cage nut into the appropriate hole in each rack rail [2].
  6. Using a mechanical lift or three people, one at each side of the disk shelf and one in front, carefully lift and rest the disk shelf on the bottom ledge of the left and right rails. Do not lift using the power supply handles.
    image:Picture showing storage shelf being inserted into a rack.
  7. Carefully slide the disk shelf into the cabinet. Ensure that it is fully seated within the rails. If removing the disk shelf to reseat it, support it at all times.
  8. Secure the front of the disk shelf using the four captive screws [1 - 4].
    image:Installing the front screws
  9. If shipping the racked disk shelf, install a screw [1 and 2] into each rear chassis ear [A].
    image:Securing the shelf for shipping in a rack