PDU Power Requirements

Each modular system has two preinstalled standard PDUs. The PDUs accept different power sources. The two tables in this topic show the PDUs that the modular system supports. The specifications are listed per PDU.

Table 3  Low-Voltage PDU Power Requirements
Single Phase, Low Voltage
3-Phase, Low Voltage
Number of inputs
3
2
Input connector
Hubbell CS8265C or Oracle Corporation-approved equivalent
Mennekes ME460P9W, Hubbell C460P9W, Walther Electric 269409, or Oracle Corporation approved equivalent
Input voltage range
200 to 240 VAC
200 to 220 VAC, 3ph
Frequency
50/60 Hz
50/60 Hz
Current
Maximum 36.8A RMS per phase
Maximum 34.6A RMS per phase
Power rating
22 kVA
24 kVA
Group protection
UL489 2-pole circuit breaker 50A
UL489 3-pole circuit breaker 50A
Table 4  High-Voltage PDU Power Requirements
Single Phase, High Voltage
3-Phase, High Voltage
Number of inputs
3
2
Input connector
EN60309 250V, 32A, 3 pin, IP44: Mennekes 160, Hubbell C332P6S, Walther Electric 231306, or Oracle Corporation-approved equivalent
EN60309 230/400V, 30/32A, 5 pin, IP44: Hubbell C530P6S, PC ELECTRIC, GESMBH 0259-6, or Oracle Corporation-approved equivalent
Input voltage range
220 to 240
220/380 to 240/415, 3ph
Frequency
50/60 Hz
50/60 Hz
Current
Maximum 32A RMS per phase
Maximum 18A RMS per phase
Power rating
22 kVA
24 kVA
Group protection
UL489 1-pole circuit breaker 32A
UL489 3-pole circuit breaker 25A

Before powering on the circuit breakers, review all safety notices in the Netra Modular System Safety and Compliance Guide (http://docs.oracle.com/cd/E59318_01/pdf/E59325.pdf). For more information on PDUs, refer to Servicing PDUs in Netra Modular System Service Manual Supplement.