Netra Server X5-2 Installation Guide

Exit Print View

Updated: June 2016
 
 

Electrical Specifications

The values in this table are for the power supplies. Use the online power calculator to determine the power consumption of a server with your configuration: http://www.oracle.com/goto/powercalculators.

Parameter
AC
DC
Voltage (nominal)
100 VAC (Japan only)
110 to 127 (90 to 132 range)
200 to 240 VAC (180 to 264 VAC range)
−48 or −60 VDC (−40 to −72 VDC range)
Input current (maximum)
10A @ 100 VAC
9A @ 110-127 VAC
5.5A @ 200-240 VAC
21.5A @ −48 VDC
17A @ −60VDC
Frequency (nominal)
50/60 Hz (47 to 63 Hz range)
N/A
DC input treatment
N/A
Isolated DC Return (DC-I)

Caution

Caution  -  The ports of this equipment or subassembly are suitable for connection to intra-building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly must not be metallically connected to interfaces that connect to the outside plant wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 6) and require isolation from the exposed outside plant cabling. The addition of primary protectors is not sufficient protection in order to connect these interfaces metallically to outside plant wiring.



Caution

Caution  -  The intra-building port(s) of the equipment or subassembly must use shielded intra-building cabling or wiring that is grounded at both ends, except the ethernet ports.