Netra Server X5-2 Installation Guide

Exit Print View

Updated: June 2016
 
 

Environmental Requirements


Caution

Caution  -  Netra rackmounted servers are certified to meet these worst-case operating conditions only when using an approved rackmount kit. You must strictly follow the rackmounting instructions in order to meet these environmental specifications


Specification
Operating
Nonoperating
Ambient temperature

Does not apply to removable media devices.

Maximum: 5°C to 45°C (41°F to 113°F) up to 1829 meters (6000 feet)

Maximum ambient operating temperature is derated by 1°C per 500m elevation.

Optimal: 21°C to 23˚C (69.8°F to 73.4°F)
Short-term maximum: -5°C to 55°C (23°F to 131°F)
−40°C to 70°C (−40°F to 158°F)
Relative humidity
5% to 85% RH, noncondensing, not to exceed 0.024 kg water/kg dry air (0.053 lb. water/2.205 lbs. dry air)
Short-term: 5% to 90% RH, noncondensing, not to exceed 0.024 kg of water per kg of dry air (0.053 lb. water/2.205 lbs. dry air)
93%, non condensing, 40°C (104°F) maximum wet bulb
Elevation (company requirement)
Maximum 3000 meters (9840 feet) at 40°C (104°F)
Maximum 12,000 meters (39,370 feet)
Elevation (NEBS requirement)
-60 meters to 1800 meters (-200 feet to 5905 feet) at 40°C (104°F)
1800 meters to 4000 meters (5905 feet to 13,123 feet) at 30°C (86°F)
Up to 12,000 meters (39,370 feet)