Go to main content

SPARC T8-4 Server Installation Guide

Exit Print View

Updated: September 2017
 
 

Environmental Requirements

This topic includes these specifications:

  • Temperature, humidity, and elevation

  • Shock and vibration

  • Acoustic

Table 1  Temperature, Humidity, and Elevation Specifications
Operating
Nonoperating
Description
Metric
U.S.
Metric
U.S.
Notes
Temperature (maximum)
5° to 35° C
at 900m
41° to 95° F at 0 to 3000 ft
-40° to 65° C
at 900m
-40° to 149° F
at 0 to 3000 ft
Decrease in maximum temperature: above 3000 ft. (900m), 1.8°F/1000 ft (1°C/300m)
Relative humidity
10 to 80%
at 27° C
10 to 80%
at 81° F
Up to 85%
at 38° C
Up to 85%
at 100° F
Maximum wet bulb, noncondensing
Altitude
0 to 3000 m
at 40° C
0 to 9840 ft at 95° F
Up to 12,000 m
Up to 40,000 ft
In China markets, regulations may limit installations to a maximum operating altitude of 2000m.
Table 2  Shock and Vibration Specifications
Description
Operating
Notes
Shock
3 G, 11 ms
Half-sine
Vibration (vertical)
0.15 G
5 to 500 HZ swept-sine
Vibration (horizontal)
0.10 G
Table 3  Acoustic Specifications
Description
Operating at 60%
Operating at 100%
Sound Power Level - LwAd
(1 B = 10 dB)
8.7 B
9.9 B
Sound Pressure Level - LpAm
(energy average of 4 bystander positions)
71.2 dBA
82.5 dBA