Electrical Specifications
Use these specifications only as a general planning guide. To determine power values
based on expected workloads, use the SPARC T8-4 power calculator at:
http://www.oracle.com/goto/powercalculators/
|
|
Operating input range
|
200 to 240 VAC,
50/60 Hz
|
Maximum operating input current at 200 VAC (per cord)
|
12.6 A
|
Maximum operating input power at 200 VAC
|
5040 W
|
|
Note -
The maximum operating input current values are based on the formula P / (V *0.90),
where P = maximum operating input power and V = input voltage. For example: 620W /
(100V * 0.90) = 6.89A You can use this formula to calculate the maximum operating
current at your input voltage.
| Caution -
Use only the power cords provided with the server.
|