Go to main content

SPARC T8-4 Server Installation Guide

Exit Print View

Updated: September 2017
 
 

Electrical Specifications

Use these specifications only as a general planning guide. To determine power values based on expected workloads, use the SPARC T8-4 power calculator at:

http://www.oracle.com/goto/powercalculators/

Description
Value
Operating input range
200 to 240 VAC,
50/60 Hz
Maximum operating input current at 200 VAC (per cord)
12.6 A

Actual amperage draw may exceed rating by no more than 10%.

Maximum operating input power at 200 VAC
5040 W

Note -  The maximum operating input current values are based on the formula P / (V *0.90), where P = maximum operating input power and V = input voltage. For example: 620W / (100V * 0.90) = 6.89A You can use this formula to calculate the maximum operating current at your input voltage.

Caution

Caution  -  Use only the power cords provided with the server.


Related Information